GREEN display shows the switching threshold value
◦
2 seconds after adjustment, the GREEN display will flash 3 times to confirm
•
Slide Mode switch to RUN to complete operation
Follow these steps to perform a Calibration SET:
Note: TEACH Selection must be programmed to CAL SEt (see
Program Mode
on page 5)
1. Enter Adjust Mode
Method
Action
Result
SET Button 17
•
Set Mode switch to ADJ
Display: Red - Signal Level; Green -
Threshold
Remote Input 18
No action required; sensor is ready for
Calibration SET method
2. SET Sensing Condition
Method
Action
Result
SET Button
•
Present sensing condition
•
Click the SET rocker button
Threshold Condition Accepted
Displays read "cAL SEt" then flashes
"PASS"; Sensor returns to Adjust
mode
Threshold Condition Unacceptable
Displays read "cAL SEt" then flashes
"FAIL"; Sensor returns to Adjust
mode
Remote Input
•
Present sensing condition
•
Single-pulse the remote input
T
3. Return to RUN Mode
Method
Action
Result
SET Button
Move Mode switch to RUN
Display: Red - Signal Level; Green -
Threshold
Remote Input
No action required; sensor returns to
RUN mode automatically
Troubleshooting
Percent Minimum Difference after TEACH
The Two-Point and Dynamic TEACH methods will flash a % minimum difference on the displays after a PASS or FAIL.
17 SET Button: 0.04 seconds
≤
"Click"
≤
0.8 seconds
18 Remote Input: 0.04 seconds
≤
T
≤
0.8 seconds
DF-G1 Expert
™
Dual Display Fiber Optic Light Receiver
16
www.bannerengineering.com - tel: 763-544-3164
P/N 172436 Rev. C