 Commissioning

Power Panel C70   User's manual V1.30 

85

Air circulation - Side view

Air outlet

>60 mm

>60 mm

>45 mm

Air intake

Information:

The specified air circulation clearance values are based on worst-case operation at the maximum spec-

ified ambient temperature (see "Temperature values" in chapter "Technical data").
If the specified air circulation clearance values cannot be observed, then the internal housing temper-

ature must be monitored by the user and appropriate measures taken if they are exceeded (see 

"Tem-

perature monitoring" on page 15

).

4.1.4 Mounting orientations

Important!

Possible damage to device!

An ambient temperature that is too high can cause damage to the device or faulty behavior.

For the maximum permissible ambient temperature, see the technical data for the respective

device.

The following diagrams show the permissible mounting orientations of Power Panels. The operating temperature

limit values specified in the technical data apply taking into account the permissible mounting orientations.

Summary of Contents for VICPAS 4PPC70.0573-20B

Page 1: ...Industrial Automation GmbH is not liable for technical or editorial errors and defects in this manual In addition B R Industrial Automation GmbH assumes no liability for damages that are directly or indirectly attributable to the delivery performance or use of this material We point out that the software and hardware designations and brand names of the respective companies used in this document ar...

Page 2: ...1393929349551 1 30 2019 02 14 ...

Page 3: ...rface resistance of the panel overlay 17 3 2 6 Surface resistance of the touch screen 17 3 3 Power Panel C70 5 7 display 18 3 3 1 Variants without fieldbus interfaces 18 3 3 2 Variants with 2x CAN bus 21 3 3 3 Variants with 1x CAN bus and 1x RS232 25 3 3 4 Variants with 1x CAN bus and 1x RS485 29 3 3 5 Temperature Humidity diagram 33 3 3 6 Dimensions 34 3 4 Power Panel C70 7 0 display 35 3 4 1 Var...

Page 4: ...e service life of the display or touch screen 93 5 2 1 Service life 93 5 2 2 Backlight 93 5 2 3 Image persistence 93 6 Accessories 95 6 1 Overview 95 6 2 TB6102 2 pin power supply connector 97 6 2 1 Order data 97 6 2 2 Technical data 97 6 3 TB510x 4 6 pin terminal block 98 6 3 1 Order data 98 6 3 2 Technical data 98 6 4 Data storage devices 99 6 5 Cable accessories 99 7 International and national ...

Page 5: ...anges Renamed chapter Standards and certifications to International and national certifications updated Content and editorial related corrections to Technical data Revised section Grounding Information regarding terminating resistor for some fieldbus interfaces Restructured manual Moved section System characteristics to its own chapter Merged chapter Power Panel C Series and section C70 Series and...

Page 6: ...regulations This also applies to all other connected devices such as drives All work such as installation commissioning and servicing are only permitted to be carried out by qualified person nel Qualified personnel are persons who are familiar with the transport installation assembly commissioning and operation of the product and have the appropriate qualifications for their job e g IEC 60364 Nati...

Page 7: ...ontrollers protection by protective equip ment such as emergency stops etc must be observed in accordance with applicable national and international regulations This also applies to all other connected devices such as drives All work such as installation commissioning and servicing are only permitted to be carried out by qualified person nel Qualified personnel are persons who are familiar with th...

Page 8: ...igger chemical processes that can very quickly impair or damage electronic components Blackened copper surfaces and cable ends in existing installations are indicators of aggressive gases When operated in rooms with dust and condensation that can endanger functionality operating and monitoring devices such as Automation Panels or Power Panels are protected on the front against the ingress of dust ...

Page 9: ...an result in minor injury or damage to property Notice Failure to observe these safety guidelines and notices can result in damage to property Table 2 Organization of safety notices General notices Contain useful information for users and instructions for avoiding malfunctions Signal word Description Information Useful information application tips and instructions for avoiding malfunctions Table 3...

Page 10: ...h and intelligent cable outlet arrangement Power Panels are extreme space savers that are very easy to install They also have no hard disks fans or batteries which makes them maintenance free The front of the panel provides IP65 protection making these devices extremely well suited for harsh industrial environments 2 2 Simple programming The complete integration of the HMI application in the Autom...

Page 11: ... panel overlay at the lower right corner of the display This element can easily be incorporated into the HMI application and makes it easy to switch between HMI screens or to implement a home or help function Landscape and portrait formats add even more flexibility to the machine design It is easy to switch between panel models depending on the machine In addition to the 2 format variants 2 pinstr...

Page 12: ... Examples 4 P P C 7 0 0 5 7 3 2 1 B Power Panel C70 5 7 landscape format fieldbus interfaces 2x CAN bus CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM 2 GB onboard flash drive Display and touch screen 5 0 640 x 480 VGA resolution analog resistive touch screen landscape format anthracite gray pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 2x...

Page 13: ... Resolution VGA 640 x 480 WVGA 800 x 480 WSVGA 1024 x 600 VGA 480 x 640 WVGA 480 x 800 WSVGA 600 x 1024 0573 0702 101G 057L 070M 101N Model number 4PPC70 xxxx 2xx 4PPC70 xxxx 2xx Panel overlay Pinstripe pattern in aluminum white Pinstripe pattern in anthracite 4PPC70 xxxx 2xW 4PPC70 xxxx 2xB 4PPC70 xxxx 2xx Interfaces 0 1 2 3 IF1 POWERLINK IF2 Ethernet IF3 USB IF4 USB IF5 X2X Link master IF6 CAN b...

Page 14: ...iew 14 Power Panel C70 User s manual V1 30 3 1 1 Comparison of Power Panel C70 variants Format Panel overlay Landscape Portrait Aluminum white Anthracite Aluminum white Anthracite 5 7 VGA 7 0 WVGA Display size Resolution 10 1 WSVGA ...

Page 15: ...erent panel overlay variant or customized panel over lay without having to make any changes to the Automation Studio project 1 2 0 0 AR F4 09 AR I4 10 AR B4 24 AR A4 25 3 2 2 Temperature monitoring Automatic overtemperature shutdown To prevent damage to the device the inner temperature of the device is monitored continuously If the internal temperature of the Power Panel reaches or exceeds 88 C an...

Page 16: ... real time clock is buffered for approx 1000 hours by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 3 2 4 Viewing angles For the viewing angles values U D R L of the display types see the technical data of the respective device D U R L Landscape D U R L Portrait Legend Display viewing angle U From top D From bottom L From left R From righ...

Page 17: ...phate Cutting oil Diesel oil Linseed oil Paraffin oil Ricinus oil Silicon oil Turpentine oil substitute Brake fluid Aviation fuel Gasoline Water Sea water Decon Sodium chloride 20 Hydrogen peroxide 25 Potassium carbonate Washing agents Tenside Fabric conditioner Iron II chloride Iron III chloride Dibutyl phthalate Dioctyl phthalate Sodium carbonate Information The specified characteristics feature...

Page 18: ...2 kB FRAM 2 GB onboard flash drive Display and touch screen 5 0 480 x 640 VGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 4PPC70 057L 20B Power Panel C70 5 7 portrait format CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM 2 GB onboard flash drive Display and touch scr...

Page 19: ...uency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5 years 21 9 GB day Guaranteed erase wr...

Page 20: ... conditions Permissible mounting orientations Standard mounting orientation Vertical Tilt 25 Rotation In 90 increments portrait landscape Installation elevation above sea level 0 to 2000 m No limitation 2000 m Reduction of ambient temperature by 0 5 C per 100 m Degree of protection per EN 60529 Front IP65 Back IP20 Ambient conditions Temperature Operation 0 to 50 C Storage 20 to 70 C Transport 20 ...

Page 21: ...drive Display and touch screen 5 0 480 x 640 VGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 2x CAN bus 4PPC70 057L 21B Power Panel C70 5 7 portrait format fieldbus interfaces 2x CAN bus CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM 2 GB onboard flash drive Display ...

Page 22: ...ock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5 years 21 9 GB day Guaranteed ...

Page 23: ...x distance 1000 m Max transfer rate Bus length 25 m 1 Mbit s Bus length 60 m 500 kbit s Bus length 200 m 250 kbit s Bus length 1000 m 50 kbit s Terminating resistor 5 Hardware revision G0 Integrated can be switched on using software Hardware revision G0 Must be wired externally Interface IF7 Type CAN bus Variant 3 pins of the 6 pin multipoint connector Max distance 1000 m Max transfer rate Bus len...

Page 24: ... 140 mm 172 mm Depth 51 mm Weight 0 6 kg Table 7 Power Panel C70 5 7 variants 2x CAN bus Technical data 1 The real time clock is buffered for approx 1000 hours 25 C by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 2 The size of the memory used for remanent variables is adjustable in Automation Studio 3 Value applies at an ambient temperat...

Page 25: ...onboard flash drive Display and touch screen 5 0 480 x 640 VGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 1x CAN bus 1x RS232 4PPC70 057L 22B Power Panel C70 5 7 portrait format fieldbus interfaces 1x CAN bus 1x RS232 CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM 2...

Page 26: ...20T Clock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5 years 21 9 GB day Guara...

Page 27: ...ns of the 6 pin multipoint connector Max distance 1000 m Max transfer rate Bus length 25 m 1 Mbit s Bus length 60 m 500 kbit s Bus length 200 m 250 kbit s Bus length 1000 m 50 kbit s Terminating resistor 5 Hardware revision G0 Integrated can be switched on using software Hardware revision G0 Must be wired externally Interface IF8 Type RS232 Variant 3 pins of the 6 pin multipoint connector Max dist...

Page 28: ...1x CAN bus and 1x RS232 Technical data 1 The real time clock is buffered for approx 1000 hours 25 C by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 2 The size of the memory used for remanent variables is adjustable in Automation Studio 3 Value applies at an ambient temperature of 25 C Reducing the brightness by 50 can increase the half b...

Page 29: ...onboard flash drive Display and touch screen 5 0 480 x 640 VGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 1x CAN bus 1x RS485 4PPC70 057L 23B Power Panel C70 5 7 portrait format fieldbus interfaces 1x CAN bus 1x RS485 CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM 2...

Page 30: ...0T Clock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5 years 21 9 GB day Guaran...

Page 31: ... rate Bus length 25 m 1 Mbit s Bus length 60 m 500 kbit s Bus length 200 m 250 kbit s Bus length 1000 m 50 kbit s Terminating resistor 5 Hardware revision G0 Integrated can be switched on using software Hardware revision G0 Must be wired externally Interface IF9 Type RS485 Variant 3 pins of the 6 pin multipoint connector Max distance 1200 m Transfer rate Max 115 2 kbit s Terminating resistor 5 Har...

Page 32: ... 1x CAN bus and 1x RS485 Technical data 1 The real time clock is buffered for approx 1000 hours 25 C by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 2 The size of the memory used for remanent variables is adjustable in Automation Studio 3 Value applies at an ambient temperature of 25 C Reducing the brightness by 50 can increase the half ...

Page 33: ... 3 5 Temperature Humidity diagram Temperature C Relative humidity RH non condensing 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90 Storage Transport Storage Transport Operation Operation Figure Power Panel C70 5 7 display Temperature Humidity diagram ...

Page 34: ...3 145 7 1 70 139 Dimensions of the installation cutout for this Power Panel variant 161 8 1 mm x 129 9 1 mm See also Installation cutout requirements on page 83 Portrait format for 5 7 variants 27 8 159 8 112 9 140 172 R 2 5 45 8 M5 13 8 127 9 5 1 1 12 5 70 139 26 3 145 7 Dimensions of the installation cutout for this Power Panel variant 129 9 1 mm x 161 8 1 mm See also Installation cutout require...

Page 35: ...32 kB FRAM 2 GB onboard flash drive Display and touch screen 7 0 480 x 800 WVGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 4PPC70 070M 20B Power Panel C70 7 0 portrait format CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM 2 GB onboard flash drive Display and touch s...

Page 36: ...pm accuracy at 25 C FPU Yes Processor Type Atom E620T Clock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guar...

Page 37: ...onditions Permissible mounting orientations Standard mounting orientation Vertical Tilt 25 Rotation In 90 increments portrait landscape Installation elevation above sea level 0 to 2000 m No limitation 2000 m Reduction of ambient temperature by 0 5 C per 100 m Degree of protection per EN 60529 Front IP65 Back IP20 Ambient conditions Temperature Operation 0 to 50 C Storage 20 to 70 C Transport 20 to...

Page 38: ...rive Display and touch screen 7 0 480 x 800 WVGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 2x CAN bus 4PPC70 070M 21B Power Panel C70 7 0 portrait format fieldbus interfaces 2x CAN bus CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM 2 GB onboard flash drive Display ...

Page 39: ...frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5 years 21 9 GB day Guaranteed eras...

Page 40: ...x distance 1000 m Max transfer rate Bus length 25 m 1 Mbit s Bus length 60 m 500 kbit s Bus length 200 m 250 kbit s Bus length 1000 m 50 kbit s Terminating resistor 5 Hardware revision G0 Integrated can be switched on using software Hardware revision G0 Must be wired externally Interface IF7 Type CAN bus Variant 3 pins of the 6 pin multipoint connector Max distance 1000 m Max transfer rate Bus len...

Page 41: ...140 mm 197 mm Depth 51 mm Weight 0 65 kg Table 15 Power Panel C70 7 0 variants 2x CAN bus Technical data 1 The real time clock is buffered for approx 1000 hours 25 C by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 2 The size of the memory used for remanent variables is adjustable in Automation Studio 3 Value applies at an ambient tempera...

Page 42: ...onboard flash drive Display and touch screen 7 0 480 x 800 WVGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 1x CAN bus 1x RS232 4PPC70 070M 22B Power Panel C70 7 0 portrait format fieldbus interfaces 1x CAN bus 1x RS232 CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM ...

Page 43: ...Clock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5 years 21 9 GB day Guarantee...

Page 44: ...ns of the 6 pin multipoint connector Max distance 1000 m Max transfer rate Bus length 25 m 1 Mbit s Bus length 60 m 500 kbit s Bus length 200 m 250 kbit s Bus length 1000 m 50 kbit s Terminating resistor 5 Hardware revision G0 Integrated can be switched on using software Hardware revision G0 Must be wired externally Interface IF8 Type RS232 Variant 3 pins of the 6 pin multipoint connector Max dist...

Page 45: ... 1x CAN bus and 1x RS232 Technical data 1 The real time clock is buffered for approx 1000 hours 25 C by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 2 The size of the memory used for remanent variables is adjustable in Automation Studio 3 Value applies at an ambient temperature of 25 C Reducing the brightness by 50 can increase the half ...

Page 46: ...onboard flash drive Display and touch screen 7 0 480 x 800 WVGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 1x CAN bus 1x RS485 4PPC70 070M 23B Power Panel C70 7 0 portrait format fieldbus interfaces 1x CAN bus 1x RS485 CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM ...

Page 47: ...Clock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5 years 21 9 GB day Guarantee...

Page 48: ...r rate Bus length 25 m 1 Mbit s Bus length 60 m 500 kbit s Bus length 200 m 250 kbit s Bus length 1000 m 50 kbit s Terminating resistor 5 Hardware revision G0 Integrated can be switched on using software Hardware revision G0 Must be wired externally Interface IF9 Type RS485 Variant 3 pins of the 6 pin multipoint connector Max distance 1200 m Transfer rate Max 115 2 kbit s Terminating resistor 5 Ha...

Page 49: ... 1x CAN bus and 1x RS485 Technical data 1 The real time clock is buffered for approx 1000 hours 25 C by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 2 The size of the memory used for remanent variables is adjustable in Automation Studio 3 Value applies at an ambient temperature of 25 C Reducing the brightness by 50 can increase the half ...

Page 50: ... 4 5 Temperature Humidity diagram Temperature C Relative humidity RH non condensing 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90 Storage Transport Storage Transport Operation Operation Figure Power Panel C70 7 0 display Temperature Humidity diagram ...

Page 51: ... 51 3 4 6 Dimensions Landscape format for 7 0 variants 197 140 R 2 112 9 184 8 27 8 5 45 82 127 9 M5 13 8 12 5 5 1 70 139 1 13 26 3 170 7 View A View A Dimensions of the installation cutout for this Power Panel variant 186 8 1 mm x 129 9 1 mm See also Installation cutout requirements on page 83 ...

Page 52: ...C70 User s manual V1 30 Portrait format for 7 0 variants 140 197 R 2 M5 127 9 5 45 8 13 8 27 8 184 8 112 9 70 1 139 1 13 26 3 170 7 Dimensions of the installation cutout for this Power Panel variant 129 9 1 mm x 186 8 1 mm See also Installation cutout requirements on page 83 ...

Page 53: ...32 kB FRAM 2 GB onboard flash drive Display and touch screen 10 1 600 x 1024 WSVGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 4PPC70 101N 20B Power Panel C70 10 1 portrait format CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM 2 GB onboard flash drive Display and tou...

Page 54: ...ype Atom E620T Clock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5 years 21 9 G...

Page 55: ...conditions Permissible mounting orientations Standard mounting orientation Vertical Tilt 25 Rotation In 90 increments portrait landscape Installation elevation above sea level 0 to 2000 m No limitation 2000 m Reduction of ambient temperature by 0 5 C per 100 m Degree of protection per EN 60529 Front IP65 Back IP20 Ambient conditions Temperature Operation 0 to 50 C Storage 20 to 70 C Transport 20 t...

Page 56: ...drive Display and touch screen 10 1 600 x 1024 WSVGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 2x CAN bus 4PPC70 101N 21B Power Panel C70 10 1 portrait format fieldbus interfaces 2x CAN bus CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB FRAM 2 GB onboard flash drive Dis...

Page 57: ...essor Type Atom E620T Clock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5 years...

Page 58: ... distance 1000 m Max transfer rate Bus length 25 m 1 Mbit s Bus length 60 m 500 kbit s Bus length 200 m 250 kbit s Bus length 1000 m 50 kbit s Terminating resistor 5 Hardware revision G0 Integrated can be switched on using software Hardware revision G0 Must be wired externally Interface IF7 Type CAN bus Variant 3 pins of the 6 pin multipoint connector Max distance 1000 m Max transfer rate Bus leng...

Page 59: ...172 mm 276 mm Depth 51 mm Weight 1 05 kg Table 23 Power Panel C70 10 1 variants 2x CAN bus Technical data 1 The real time clock is buffered for approx 1000 hours 25 C by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 2 The size of the memory used for remanent variables is adjustable in Automation Studio 3 Value applies at an ambient temper...

Page 60: ...onboard flash drive Display and touch screen 10 1 600 x 1024 WSVGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 1x CAN bus 1x RS232 4PPC70 101N 22B Power Panel C70 10 1 portrait format fieldbus interfaces 1x CAN bus 1x RS232 CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB F...

Page 61: ...s Processor Type Atom E620T Clock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5...

Page 62: ...s of the 6 pin multipoint connector Max distance 1000 m Max transfer rate Bus length 25 m 1 Mbit s Bus length 60 m 500 kbit s Bus length 200 m 250 kbit s Bus length 1000 m 50 kbit s Terminating resistor 5 Hardware revision G0 Integrated can be switched on using software Hardware revision G0 Must be wired externally Interface IF8 Type RS232 Variant 3 pins of the 6 pin multipoint connector Max dista...

Page 63: ...s 1x CAN bus and 1x RS232 Technical data 1 The real time clock is buffered for approx 1000 hours 25 C by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 2 The size of the memory used for remanent variables is adjustable in Automation Studio 3 Value applies at an ambient temperature of 25 C Reducing the brightness by 50 can increase the half...

Page 64: ...onboard flash drive Display and touch screen 10 1 600 x 1024 WSVGA resolution analog resistive touch screen portrait format aluminum white pinstripe Interfaces 1x POWERLINK 1x Ethernet 10 100 Mbit s 1x X2X Link 2x USB 2 0 1x CAN bus 1x RS485 4PPC70 101N 23B Power Panel C70 10 1 portrait format fieldbus interfaces 1x CAN bus 1x RS485 CPU and memory Intel Atom 333 MHz compatible 256 MB DDRAM 32 kB F...

Page 65: ...s Processor Type Atom E620T Clock frequency 333 MHz compatible L1 cache Data code 24 kB Program code 32 kB L2 cache Mode Node switches No Remanent variables 32 kB FRAM buffering 10 years 2 DRAM 256 MB Shortest task class cycle time 0 4 ms Typical instruction cycle time 0 01 µs Application memory Type 2 GB eMMC flash memory Data retention 10 years Writable data amount Guaranteed 40 TB Results for 5...

Page 66: ... rate Bus length 25 m 1 Mbit s Bus length 60 m 500 kbit s Bus length 200 m 250 kbit s Bus length 1000 m 50 kbit s Terminating resistor 5 Hardware revision G0 Integrated can be switched on using software Hardware revision G0 Must be wired externally Interface IF9 Type RS485 Variant 3 pins of the 6 pin multipoint connector Max distance 1200 m Transfer rate Max 115 2 kbit s Terminating resistor 5 Har...

Page 67: ...s 1x CAN bus and 1x RS485 Technical data 1 The real time clock is buffered for approx 1000 hours 25 C by a gold foil capacitor The gold foil capacitor is completely charged after 3 continuous hours of operation 2 The size of the memory used for remanent variables is adjustable in Automation Studio 3 Value applies at an ambient temperature of 25 C Reducing the brightness by 50 can increase the half...

Page 68: ... 5 5 Temperature Humidity diagram Temperature C Relative humidity RH non condensing 0 5 10 15 20 25 30 35 40 45 50 55 60 65 70 75 80 85 90 95 100 80 70 60 50 40 30 20 10 0 10 20 30 40 50 60 70 80 90 Storage Transport Storage Transport Operation Operation Figure Power Panel C70 10 1 display Temperature Humidity diagram ...

Page 69: ...0 69 3 5 6 Dimensions Landscape format for 10 1 variants 5 27 8 160 112 9 45 82 127 4 264 13 8 R 2 5 12 5 276 172 1 138 275 1 26 2 145 8 View A View A Dimensions of the installation cutout for this Power Panel variant 265 9 1 mm x 161 9 1 mm See also Installation cutout requirements on page 83 ...

Page 70: ...User s manual V1 30 Portrait format for 10 1 variants 264 127 4 13 8 26 2 145 8 1 1 138 275 172 276 R 2 12 5 5 5 42 8 27 8 M5 160 112 9 Dimensions of the installation cutout for this Power Panel variant 161 9 1 mm x 265 9 1 mm See also Installation cutout requirements on page 83 ...

Page 71: ...nection elements 3 4 5 6 7 8 9 A B 1 2 1 Reset button 2 Diagnostic LEDs 3 IF5 X2X Link interface 4 Fieldbus interface depends on the Power Panel variant 5 IF1 POWERLINK interface 6 IF2 Ethernet interface 7 IF3 USB interface 8 IF4 USB interface 9 Power supply A Grounding clip B Grounding plate built into the device ...

Page 72: ...the description in the following sections OPS LEDs Variant without fieldbus interfaces OPS LEDs Variant with 2x CAN bus OPS LEDs Variant with 1x CAN bus and 1x RS232 OPS LEDs Variant with 1x CAN bus and 1x RS485 3 6 1 1 LED S E LED Status Error This LED is a green red dual LED and indicates the state of the POWERLINK interface The LED states have a different meaning depending on the operating mode...

Page 73: ... this mode Cyclic communication is not yet taking place Controlled node CN The CN can be configured by the MN in this mode The CN waits until it receives an SoC frame and then switches to mode PRE_OPERATIONAL_2 Single flash approx 1 Hz On Controlled node CN If the red LED lights up in this mode this means that the MN has failed Off Mode PRE_OPERATIONAL_2 The interface is in mode PRE_OPERATIONAL_2 ...

Page 74: ...rrect configuration or defective hardware The error code is indicated by LED S E blinking red The blinking signal of the error code consists of 4 switch on phases with short 150 ms or long 600 ms duration The error code is repeated every 2 seconds All times in ms RAM error Hardware error 150 150 150 300 300 300 600 2000 150 150 300 300 300 600 2000 600 Error Error description RAM error The device ...

Page 75: ...g resistors LED Color Status Description Interface OPS1 Reserved OPS2 Yellow On RxD Data is being received OPS3 Yellow On TxD Data is being transmitted IF6 CAN bus OPS4 Yellow On RxD Data is being received OPS5 Yellow On TxD Data is being transmitted IF7 CAN bus 3 6 1 4 OPS LEDs Variant with 1x CAN bus and 1x RS232 Some Power Panel variants only have integrated terminating resistors starting with ...

Page 76: ...ors LED Color Status Description Interface OPS1 Reserved Off Terminating resistor not switched on OPS2 Yellow On Terminating resistor switched on OPS3 Yellow On TxD RxD Data is being transmitted or received IF6 CAN bus OPS4 Yellow On TxD RxD Data is being transmitted or received Off Terminating resistor not switched on OPS5 Yellow On Terminating resistor switched on IF9 RS485 Applies to hardware r...

Page 77: ...ws after pressing the reset button can be set in Automation Studio Mode SERVICE default Warm restart Cold restart Mode DIAGNOSIS Press and hold key 2 s DIAGNOSIS The device is started in mode DIAGNOSIS Program sections in User RAM and in the User FlashPROM are not initialized A warm restart always take place after exiting mode DIAGNOSIS Press key briefly 2 s Pause 2 s Press and hold key 2 s BOOT T...

Page 78: ...1 to 239 can be set in the POWERLINK configuration in Automation Studio Ethernet mode In this mode the interface is operated as an Ethernet interface The INA2000 node number is set using the B R Automation Studio software Information If interface IF1 is operated in Ethernet mode then this interface receives its own IP address and works independently of Ethernet interface IF2 3 6 4 Ethernet interfa...

Page 79: ...used Important Possible damage to USB interfaces or USB devices Peripheral USB devices can be connected to the USB interfaces Due to the large number of USB devices available on the market B R cannot guarantee their functionality Functionality is ensured when using the USB devices available from B R Because of general PC specifications these USB interfaces should be handled with extreme care with ...

Page 80: ...CAN bus and 1x RS232 Figure Terminal Pinout IF8 RS232 1 TxD Transmit signal 2 GND Ground 3 RxD Receive signal IF6 CAN bus 4 CAN_H CAN high 5 GND Ground 6 CAN_L CAN low Required accessories 0TB5106 2110 01 Accessory terminal block 6 pin 2 5 cage clamp terminal block 0 5 mm2 1 6 Front touch screen Back A terminating resistor can be switched on individually and independently for each interface via so...

Page 81: ...rth grounding clip on the device and the GND connection of the power supply are con nected internally in the Power Panel Front touch screen Back The pinout for the power supply is listed in the following table and printed on the back of the Power Panel The Power Panel has reverse polarity protection that prevents the supply voltage from being connected incorrectly and damaging the device Terminal ...

Page 82: ...mportant installation information The environmental conditions must be observed When installed in a closed housing enough space must be available for air to circulate sufficiently The device must be installed on a flat clean and burr free surface Ventilation holes are not permitted to be covered You must observe the permissible mounting orientations when installing the device When connecting cable...

Page 83: ...e installed in a protective housing with sufficient rigidity per UL61010 1 and UL61010 2 201 4 1 2 Mounting with retaining clips Figure Retaining clip The retaining clips are designed for a certain thickness of the material to be clamped max 6 mm min 2 mm A large flat blade screwdriver is needed to tighten and remove the screws Devices must be installed on a flat clean and burr free surface tight ...

Page 84: ...ng torque 0 4 Nm Figure Securing the retaining clips 4 1 3 Installation instructions The Power Panel must be mounted using the retaining clips included in delivery tightening torque 0 4 Nm In order to ensure sufficient air circulation the specified clearance values must be observed above below to the side and behind the Power Panel The minimum specified spacing is indicated in the following schema...

Page 85: ... temper ature must be monitored by the user and appropriate measures taken if they are exceeded see Tem perature monitoring on page 15 4 1 4 Mounting orientations Important Possible damage to device An ambient temperature that is too high can cause damage to the device or faulty behavior For the maximum permissible ambient temperature see the technical data for the respective device The following ...

Page 86: ...mmissioning 86 Power Panel C70 User s manual V1 30 Tilted mounting orientation 25 25 Rotated mounting orientation The Power Panel is permitted to be rotated in 90 increments and installed 90 270 90 180 0 ...

Page 87: ... Information In the Power Panels ground and GND potential are connected together internally in the device Important Possible malfunction of interfaces and touch screen If functional ground is not present faults in interface communication and touch screen functionality can occur The device is only permitted to be operated if properly grounded Built in grounding plate 2 1 1 Grounding plate with clip...

Page 88: ...rference All cable shields must be con nected to ground with good conductivity using a cable tie on the grounding plate or some other method 3 Unshielded lines All unshielded lines must be relieved of tension by using a cable tie to tie them to the grounding plate 2 1 3 Grounding in the control cabinet Control cabinet Grounding rail Ground connection 4 mm Figure Grounding in the control cabinet Im...

Page 89: ...The list of target systems found also includes the Power Panel Since an IP address has not yet been assigned to the Power Panel address 0 0 0 0 is displayed Command Set IP parameters Power Panel shortcut menu opens the dialog box where all required network configurations can be made temporarily they should be identical to the settings defined in the project Information The data required for manual...

Page 90: ...ay itself it may occur that multiple touches also outside of the display area can lead to a command being triggered unintentionally This can happen when the Power Panel is held in your hands Defined touch keys The following touch keys virtual keys are predefined if the Visual Components object is used for designing the HMI application in Automation Studio VK1 VK2 1 In addition to the Hand button V...

Page 91: ...ouch screen calibration from the application using Visual Components Touch screen calibration is started in the application The several options available to the user are described in Automation Help in section Visual Components See the following keywords Data points CalibrationDatapoint and CalibrationStateDatapoint Key action CalibrateTouch 4 3 1 2 Set brightness with the application Function VA_...

Page 92: ...ld be moistened with water and detergent a screen cleaning agent or alcohol ethanol The cleaning agent should be applied to the cloth beforehand not sprayed directly on the Power Panel Never use aggressive solvents chemicals scouring agents pressurized air or steam jet air ejectors Important Cleaning the label on the back of the unit is only permitted with a dry cloth This ensures readability of t...

Page 93: ...g time of 50 000 hours would mean that the display brightness would still be 50 after this time How can the service life of backlights be extended Set the display brightness to the lowest value comfortable for the eyes Use dark images Reducing the brightness by 50 can increase the half brightness time by approximately 50 5 2 3 Image persistence Image persistence refers to the burning in of a stati...

Page 94: ...e persistence be reduced Switch continuously between static and dynamic images Prevent excessive differences in brightness between foreground and background elements Use colors with similar brightness Use complementary colors for subsequent images Use screensavers ...

Page 95: ... X20CA0E61 00800 POWERLINK Ethernet connection cable RJ45 to RJ45 8 m X20CA0E61 01000 POWERLINK Ethernet connection cable RJ45 to RJ45 10 m X20CA0E61 01200 POWERLINK Ethernet connection cable RJ45 to RJ45 12 m X20CA0E61 01500 POWERLINK Ethernet connection cable RJ45 to RJ45 15 m X20CA0E61 02000 POWERLINK Ethernet connection cable RJ45 to RJ45 20 m X20CA0E61 0300 POWERLINK Ethernet connection cable...

Page 96: ...040 X2X Link attachment cable angled 4 m X67CA0X31 0050 X2X Link attachment cable angled 5 m X67CA0X31 0100 X2X Link attachment cable angled 10 m X67CA0X31 0150 X2X Link attachment cable angled 15 m X67CA0X31 0500 X2X Link attachment cable angled 50 m 99 X2X Link cables X67CA0X99 1000 Cable for custom assembly 100 m X67CA0X99 5000 Cable for custom assembly 500 m 99 ...

Page 97: ...specifications for the complete system take precedence over those of individual components The technical data in this manual is current as of its creation publication We reserve the right to make changes Model number 0TB6102 2010 01 0TB6102 2110 01 Terminal block Number of pins 2 female Type of terminal block Screw clamp terminal block Cage clamp terminal block Cable type Only copper wires no alum...

Page 98: ...eviate from those that apply to the complete system The data specifications for the complete system take precedence over those of individual components The technical data in this manual is current as of its creation publication We reserve the right to make changes Model number 0TB5104 2110 01 0TB5106 2110 01 Terminal block Number of pins 4 6 Type of terminal block Cage clamp terminal block 1 Cage ...

Page 99: ...g documentation This can be located and downloaded by searching for the data storage device s model number at www br automa tion com 6 5 Cable accessories For technical data and additional information about cables see the corresponding documentation This can be lo cated and downloaded by searching for the cable s model number on the B R website at www br automation com ...

Page 100: ... at the following locations Chapter Device description in section Technical data for the individual products On the website www br automation com in section Technical data for the individual products possible to search using model number On the product label see Power Panel housing Changes and new certifications are promptly made available in electronic form on the B R website at www br automation...

Page 101: ...cable standards from this directive EN 61131 2 Programmable logic controllers Part 2 Guidance for inspection and routine testing EN 61000 6 2 Electromagnetic compatibility EMC Part 6 2 Generic standards Immunity standard for industrial environments EN 61000 6 4 Electromagnetic compatibility EMC Part 6 4 Generic standards Emissions standard for industrial environments The corresponding declaration ...

Page 102: ...t 3 Classification of groups of environmental parameters and their severities Section 3 Stationary use at weather protected locations EN 61000 4 2 Electromagnetic compatibility EMC Part 4 2 Testing and measurement techniques Electrostatic discharge immunity test EN 61000 4 3 Electromagnetic compatibility EMC Part 4 3 Testing and measurement techniques Radiated radio frequency electromagnetic field...

Page 103: ...tended Temporary degradation of performance must be self recover able C Loss of functions accepted but no destruction of hardware or software program or data The PLC system shall continue to operate as intended auto matically after manual restart or power off power on D Degradation or failure of functionality that can no longer be re stored PLC system permanently damaged or destroyed Electrostatic...

Page 104: ...0 AM 1 kHz Criteria A 1 Only for connections with a permitted line length greater than 3 m Magnetic fields with electrical frequencies Testing performed per standard EN 61000 4 8 Requirements per standard EN 61131 2 Zone B Requirements per standard EN 61000 6 2 Housing completely wired 30 A m 3 axes x y z 50 60 Hz 1 Criteria A 1 Mains frequency per manufacturer data Voltage dips Testing performed ...

Page 105: ...standard EN 61131 2 Zone B Limit values per standard EN 61000 6 4 150 to 500 kHz 79 dB µV quasi peak value 66 dB µV average value AC mains connection 150 kHz to 30 MHz 500 kHz to 30 MHz 73 dB µV quasi peak value 60 dB µV average value 150 to 500 kHz 97 to 87 dB µV quasi peak value 53 to 40 dB µA quasi peak value 84 to 74 dB µV average value 40 to 30 dB µA average value Telecommunications network c...

Page 106: ...z 1 octave per minute Vibration sinusoidal Transport packaged Testing performed per stan dard EN 60068 2 6 Requirements per standard EN 60721 3 2 Class 2M1 Requirements per standard EN 60721 3 2 Class 2M2 Requirements per standard EN 60721 3 2 Class 2M3 Frequency Amplitude Frequency Amplitude Frequency Amplitude 2 to 9 Hz Deflection 3 5 mm 2 to 9 Hz Deflection 3 5 mm 2 to 8 Hz Deflection 7 5 mm 9 ...

Page 107: ... fingers Back IP20 Second number IPx0 Not protected Requirement per manufacturer Explanation of code num bers per standard EN 60529 Meaning for the protection of equipment Meaning for the protection of personnel First number IP6x Dust proof Protected against touching dangerous parts with conductor Front IP65 Second number IP x5 Protection against water jets 7 3 Underwriters Laboratories UL UL mark...

Page 108: ...information 108 Power Panel C70 User s manual V1 30 Publishing information B R Industrial Automation GmbH B R Strasse 1 5142 Eggelsberg Austria Telephone 43 7748 6586 0 Fax 43 7748 6586 26 office br automation com ...