International and national certifications
Power Panel T30 User's manual V1.42 - Translation of the original documentation
131
ATEX Directive 2014/34/EU
ATEX markings
II 3G Ex nA IIA T5 Gc
II 3D Ex tc IIIC T70°C Dc
TÜV 16 ATEX 7815 X
Power Panel T30 devices are suitable for use in the described environment or in non-
explosive atmospheres.
Certification of these products is performed exclusively in cooperation with EU-autho-
rized bodies (Notified Bodies).
Each device is also accompanied by an information sheet providing detailed installa-
tion and safety guidelines.
Europe (EU)
Applicable standards from this directive:
EN 60079-0
Explosive atmospheres
Part 0: Equipment - General requirements
EN 60079-15
Explosive atmospheres
- Part 15: Equipment protection by type of protection "n"
EN 60079-31
Explosive atmospheres
- Part 31: Equipment dust ignition protection by enclosure "t"
The declaration of conformity and certificate can be downloaded from the B&R website. For information about the
versions of applicable standards, see the declaration of conformity.
Declaration of conformity
Certificate
(type approval certificate)
Website > Downloads > Certificates > ATEX > Power T30
Ex marking in detail:
Ex Zone 2
(gas zone )
Ex Zone
22 (dust zone)
Markings for explosion protection (product complies with ATEX Directive 2014/34/EU)
II
Device group II (Ex areas other than mines susceptible to firedamp)
II
3G
Device category G (gases) / D (dusts)
3D
Ex
Ex protection in accordance with EN 60079-xx (-0, -15)
Ex protection in accordance with EN 60079-xx (-0, -31)
Ex
nA
Ignition protection "nA" (non-sparking equipment)
Ignition protection "tc" (protection through enclosure)
tc
IIA
Ex group II (gases)
Ex group III (dusts)
IIIC
T5
Temperature class T5 (≤100°C)
Maximum surface temperature (≤70°C)
T70°C
Gc
Equipment protection level (EPL)
Equipment protection level (EPL)
Dc
Type approval certificate: TÜV 16 ATEX 7815 X
IP protection (EN 60529 ): IP65 front / IP20 back
Ex ambient temperature range (Ta): -20 to 55°C
In addition to the general installation guidelines, the instructions listed in section
"Instructions for use in Ex zone
must also be followed for use in explosive atmospheres!