Technical data
194
Panel PC 2100 user's manual V1.17
2.3.5.7 5ACCIF01.FPSC-001
2.3.5.7.1 General information
Interface option 5ACCIF01.FPSC-001 is equipped with a POWERLINK, RS232, CAN bus master and X2X Link
master interface. 512 kB of nvSRAM is also installed.
•
1x POWERLINK interface for managing or controlled node
•
1x CAN bus master interface
•
1x X2X Link master interface
•
1x RS232 interface
•
512 kB nvSRAM
•
Compatible with APC2100/PC2100 and APC2200/PPC2200
This interface option can only be operated with Automation Runtime.
2.3.5.7.2 Order data
Model number
Short description
Figure
Interface options
5ACCIF01.FPSC-001
Interface card - 1x RS232 interface - 1x CAN interface - 1x X2X
Link interface - 1x POWERLINK interface - 512 kB nvSRAM - For
APC2100/PPC2100/APC2200/PPC2200 - Only available with a
new device
Optional accessories
Terminal blocks
0TB1210.3100
Connector 300 VDC - 10-pin female - Cage clamp terminal block
- Protected against vibration by the screw flange
Table 187: 5ACCIF01.FPSC-001 - Order data
2.3.5.7.3 Technical data
Information:
The following specifications, properties and limit values apply only to this accessory and may deviate
from those that apply to the complete system. For the complete system in which this accessory is
installed, for example, the data specified for that complete system applies.
Model number
5ACCIF01.FPSC-001
General information
LED status indicators
L1, L2, L3
B&R ID code
0xE9BC
Certifications
CE
Yes
UL
cULus E115267
Industrial control equipment
HazLoc
cULus HazLoc E180196
Industrial control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T4
1)
Controller
nvSRAM
Size
512 kB
Data retention
20 years
Read/Write endurance
Min. 1,000,000
Remanent variables in power failure mode
256 kB
(e.g. for Automation Runtime, see Automation Help)
Interfaces
COM
Quantity
1
Type
RS232, not modem-capable, not electrically isolated
Design
10-pin, male
UART
16550-compatible, 16-byte FIFO
Max. baud rate
115 kbit/s
Table 188: 5ACCIF01.FPSC-001 - Technical data