278
Standards and certifications • Requirements for immunity to disturbances (immunity)
Panel PC 800 User's Manual V 1.00
4.3 High-speed transient electrical disturbances (burst)
4.4 Surges (surge)
Test carried out according to
EN 61000-4-4
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
AC power I/O
±
2 kV, criteria B
-
AC power inputs
-
±
2 kV, criteria B
AC power outputs
-
±
1 kV, criteria B
DC power I/O >10 m
±
2 kV, criteria B
-
DC power inputs >10 m
-
±
2 kV, criteria B
DC power outputs >10 m
-
±
1 kV, criteria B
Functional ground connections,
signal lines and I/Os >3 m
±
1 kV, criteria B
±
1 kV, criteria B
Unshielded AC I/O >3 m
-
±
2 kV, criteria B
Analog I/O
±
1 kV, criteria B
±
1 kV, criteria B
Table 159: Test requirements - High-speed transient electrical disturbances (burst)
Test carried out according to
EN 61000-4-5
Limits according to
EN 61000-6-2
Limits according to
EN 61131-2
AC power I/O, L to L
±
1 kV, criteria B
±
1 kV, criteria B
AC power I/O, L to PE
±
2 kV, criteria B
±
2 kV, criteria B
DC power I/O, L+ to L-, >10 m
±
0.5 kV, criteria B
-
DC power I/O, L to PE, >10 m
±
0.5 kV, criteria B
-
DC power inputs, L+ to L-
-
±
0.5 kV, criteria B
DC power inputs, L to PE
-
±
1 kV, criteria B
DC power outputs, L+ to L-
-
±
0.5 kV, criteria B
DC power outputs, L to PE
-
±
0.5 kV, criteria B
Signal connections >30 m
±
1 kV, criteria B
±
1 kV, criteria B
All shielded cables
-
±
1 kV, criteria B
Table 160: Test requirements - Surge voltages
Summary of Contents for MAPPC800-ENG
Page 2: ...2 Panel PC 800 User s Manual V 1 00...
Page 4: ...4 Panel PC 800 User s Manual V 1 00...
Page 6: ...6 Panel PC 800 User s Manual V 1 00...
Page 16: ...16 Panel PC 800 User s Manual V 1 00 Table of contents...
Page 32: ...32 General information Model numbers Panel PC 800 User s Manual V 1 00...
Page 350: ...350 Accessories Cables Panel PC 800 User s Manual V 1 00...
Page 378: ...378 Appendix A Glossary Panel PC 800 User s Manual V 1 00...
Page 388: ...Table index 388 Panel PC 800 User s Manual V 1 00...