Maintenance / Service • Installing the UPS fuse kit on the battery unit
Chapter 7
Maintenance / Service
Automation PC 810 with GM45 CPU board user's manual V1.28
395
8 Installing the UPS fuse kit on the battery unit
Information:
The 5AC600.UPSF-00 UPS fuse kit is only needed for battery units up to and including revision D0. A
25 A fuse is integrated on the connector circuit board beginning with revision E0.
8.1 Procedure
1. Power to the 5AC600.UPSB-00 battery unit must be disconnected by unplugging the UPS connection cable
from the B&R Industrial PC.
2. Remove the cover on the battery unit. This is done by unscrewing the two Torx screws (T10) so that the cover
can be removed by sliding it towards the orange connector.
Figure 265: Removing the cover for the battery unit
3. To install the fuse, the red cable must be disconnected from the battery circuit board.
Figure 266: Disconnecting the cable