Technical data • Individual components
46
Automation PC 510 User's Manual V 1.01
Green - status
Description
Off
NOT_ACTIVE
Managing Node (MN)
The bus is monitored for POWERLINK frames. If a frame is not received within the configured time window
(timeout), the interface goes directly into PRE_OPERATIONAL_1 status (single flash).
If, however, POWERLINK communication is detected before this time passes, the interface goes directly into the
BASIC_ETHERNET status (flickering).
Controlled Node (CN)
The bus is monitored for POWERLINK frames. If a frame is not received within the configured time window
(timeout), the interface goes directly into BASIC_ETHERNET status (flickering).
If, however, POWERLINK communication is detected during this time, the interface goes directly into the
PRE_OPERATIONAL_1 status (single flash).
Green flickering (approx. 10 Hz)
BASIC_ETHERNET
The interface is in BASIC_ETHERNET status, and is operated purely as an Ethernet TCP/IP interface.
Managing Node (MN)
This status can only be changed by resetting the interface.
Controlled Node (CN)
If POWERLINK communication is detected while in this status, the interface goes into the PRE_OPERATIONAL_1
state (single flash).
Single flash (approx. 1 Hz)
PRE_OPERATIONAL_1
The interface status is PRE_OPERATIONAL_1.
Managing Node (MN)
The MN starts the operation of the "reduced cycle". Collisions are allowed on the bus. There is not yet any cyclic
communication.
Controlled Node (CN)
The CN waits until it receives an SoC frame and then switches to PRE_OPERATIONAL_2 status (double flash).
Double flash (approx. 1 Hz)
PRE_OPERATIONAL_2
The interface status is PRE_OPERATIONAL_2.
Managing Node (MN)
The MN begins with the cyclic communication (cyclic input data is not yet evaluated). The CNs are configured
in this status.
Controlled Node (CN)
In this status, the interface is normally configured by the manager. Once complete, a command changes the
status to PRE_OPERATIONAL_3 (triple flash).
Triple flash (approx. 1 Hz)
READY_TO_OPERATE
The interface status is READY_TO_OPERATE.
Managing Node (MN)
Normal cyclic and asynchronous communication. Received PDO data is ignored.
Controlled Node (CN)
The configuration of the interface is complete. Normal cyclic and asynchronous communication.
The PDO data sent corresponds to the PDO mapping used. However, cyclic data is not yet evaluated.
On
OPERATIONAL
The interface status is OPERATIONAL.
Blinking (approx. 2.5 Hz)
STOPPED
The interface status is STOPPED.
Managing Node (MN)
This status is not possible for the MN.
Controlled Node (CN)
No output data is produced and no input data is received. Only the appropriate command from the manager can
enter or leave this state.
Table 39: Status/Error LED as status LED - POWERLINK operating mode
System failure error codes
Incorrect configuration or defective hardware can cause a system failure error.
The error is indicated via the red error LED using four switch-on phases. The switch-on phases are either 150 ms
or 600 ms long. Error code outputs are repeated cyclically after 2 seconds.
Legend:
• ...
150 ms
− ...
600 ms
Delay ...
2 sec. delay
Error description
Error code displayed by red status LED
RAM Errors
•
•
•
-
Break
•
•
•
-
Break
Hardware errors
-
•
•
-
Break
-
•
•
-
Break
Table 40: Status/error LED as error LED - system failure error codes
Firmware update
The firmware is a component of Automation Studio. The module is automatically changed to this version.
To update the firmware included in Automation Studio, you must upgrade the hardware (see the Help system under
"Project Management - Automation Studio Upgrade").