Technical data • Individual components
Chapter 2
Technical data
Automation PC 510 User's Manual V 1.01
45
POWERLINK interface
POWERLINK interface board, 2 connections
Cabling
S/STP (Cat5e)
Cable length
Max. 100 m (min. Cat5e)
Speed LED
On
Off
Green / red
see Status / Error LED
Link LED
On
Off
Yellow
Link (POWERLINK net-
work connection available)
Activity (blinking - da-
ta transfer in progress)
Table 35: POWERLINK interface board, 2-port connection
LED STATUS
The status/error LED is a green/red dual LED. The status LEDs can have different meanings depending on oper-
ating mode.
Ethernet TCP/IP mode
The interface can be operated purely as an Ethernet TCP/IP interface.
Green - status
Description
On
The POWERLINK interface is operated purely as an Ethernet TCP/IP interface.
Table 36: Status/Error LED - Ethernet TCP/IP operating mode
POWERLINK V1
Status LED
Green
Red
Status of the POWERLINK station
On
Off
The POWERLINK station is running with no errors.
Off
On
A fatal system error has occurred. The error type can be read using the PLC logbook. An irreparable problem has
occurred. The system cannot properly carry out its tasks. This status can only be changed by resetting the module.
Blinking alternately
The POWERLINK managing node failed. This error code can only occur in controlled node operation.
Off
Blinking
System failure. The red blinking LED signals a certain type of error using a blink code (see section " System
failure error codes" on page 46).
Table 37: Status/error LED - POWERLINK V1 operating mode
POWERLINK V2
Red - error
Description
On
The POWERLINK interface has encountered an error (failed Ethernet frames, increased number of collisions on
the network, etc.).
If an error occurs in the following states, then the green LED blinks over the red LED:
•
BASIC_ETHERNET
•
PRE_OPERATIONAL_1
•
PRE_OPERATIONAL_2
•
READY_TO_OPERATE
t
t
t
S/E LED
Status
Green
Error
Red
Table 38: Status / Error LED as error LED - POWERLINK operating mode