Accessories
ACOPOSinverter P84 User's Manual 2.10
371
Properties
•
Improved protection against overvoltages in the mains supply and reduced distortion factor of the current
generated by the inverter.
•
Limitation of the mains current.
•
Using mains chokes is recommended when the following conditions apply:
–
Multiple inverters connected in parallel with little space between them
–
Mains supply with disturbances from other devices (interference, overvoltage)
–
Line supply with voltage imbalance between phases > 1.8% of the rated voltage
–
Inverter supplied via a line with very low impedance (10x higher than the rated voltage of the
inverter close to power transformers)
–
Large number of frequency inverters connected on one line
–
Reduction of overloads on capacitors for cosine ϕ correction if the system has equipment for
power factor correction
4.3.3 Wiring
4.3.3.1 8I0CTXXX.000-1
8I0CTXXX.000-1
E1 S1 E2 S2 E3 S3
8I0CT004.000-1 8I0CT010.000-1
8I0CT016.000-1 8I0CT030.000-1
8I0CT060.000-1
E1 E2 E3
S1 S2 S3
8I0CT100.000-1 8I0CT184.000-1
S1
S2
S3
E1
E2
E3
L1
L2
L3
U
/T
1
V/
T2
W
/T
3
M1
3 ~
ACOPOSinverter
3 ~
Summary of Contents for ACOPOSinverter P84
Page 2: ......
Page 391: ...Accessories ACOPOSinverter P84 User s Manual 2 10 391 4 7 2 Installation 8I0XF084 020 1...
Page 392: ...Accessories 392 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 030 1...
Page 393: ...Accessories ACOPOSinverter P84 User s Manual 2 10 393 8I0XF084 040 1...
Page 394: ...Accessories 394 ACOPOSinverter P84 User s Manual 2 10 8I0XF084 050 1...
Page 395: ...Accessories ACOPOSinverter P84 User s Manual 2 10 395 8I0XF084 0x0 1...
Page 400: ...Accessories 400 ACOPOSinverter P84 User s Manual 2 10...