X20 system modules • X20 CPUs • X20CP1483 and X20CP1483-1
X20 system User's Manual 3.10
897
4.12.2.3 Technical data - X20CP148x
Product ID
X20CP1483
X20CP1483-1
Short description
Interfaces
1x RS232, 1x Ethernet, 1x POWERLINK (V1/V2), 2x USB, 1x X2X Link
System module
CPU
General information
Cooling
Fanless
B&R ID code
0xA239
0xAEC5
Status indicators
CPU function, overtemperature, Ethernet, POWERLINK, CompactFlash, battery
Diagnostics
Battery
Yes, using status LED and software
CPU function
Yes, using status LED
CompactFlash
Yes, using status LED
Ethernet
Yes, using status LED
POWERLINK
Yes, using status LED
Overtemperature
Yes, using status LED
ACOPOS capability
Yes
Visual Components support
Yes
Power consumption without memory card, interface
module and USB
6.0 W
Internal power consumption of the X2X Link and I/
O supply
1)
Bus
1.42 W
Internal I/O
0.6 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Electrical isolation
IF1 - IF2
Yes
IF1 - IF3
Yes
IF1 - IF4
No
IF1 - IF5
No
IF1 - IF6
Yes
IF2 - IF3
Yes
IF2 - IF4
Yes
IF2 - IF5
Yes
IF2 - IF6
Yes
IF3 - IF4
Yes
IF3 - IF5
Yes
IF3 - IF6
Yes
IF4 - IF5
No
IF4 - IF6
Yes
IF5 - IF6
Yes
PLC - IF1
No
PLC - IF2
Yes
PLC - IF3
Yes
PLC - IF4
No
PLC - IF5
No
PLC - IF6
Yes
Certification
CE
Yes
cULus
Yes
cCSAus HazLoc Class 1 Division 2
Yes
-
ATEX Zone 2
Yes
KC
Yes
GL
Yes
GOST-R
Yes
CPU and X2X Link supply
Input voltage
24 VDC -15% / +20%
Input current
Max. 2.2 A
Fuse
Integrated, cannot be replaced
Reverse polarity protection
Yes
X2X Link supply output
Nominal output power
7.0 W
Parallel operation
Yes
2)
Redundant operation
Yes
Input I/O supply
Input voltage
24 VDC -15% / +20%
Fuse
Required line fuse: Max. 10 A, slow-blow
Output I/O supply
Rated output voltage
24 VDC
Permitted contact load
10.0 A
Supply - General information
Status indicators
Overload, operating status, module status, RS232 data transfer
Table 260: X20CP1483, X20CP1483-1 - Technical data