X20 system modules • Other functions • X20CM4810
2166
X20 system User's Manual 3.10
FrequencyBandLowerFrequencyRead
Name:
FrequencyBand01LowerFrequencyRead to FrequencyBand32LowerFrequencyRead
Registers for reading the minimum frequency of individual frequency bands.
The minimum frequency is specified in 1/4 Hz.
Data type
Value
UINT
1 to 40,000
FrequencyBandUpperFrequency
Name:
FrequencyBand01UpperFrequency to FrequencyBand32UpperFrequency
Maximum frequency for calculating the frequency band if it is not speed-dependent.
The maximum frequency must be specified in 1/4 Hz.
Data type
Value
UINT
1 to 40,000
FrequencyBandUpperFrequencyRead
Name:
FrequencyBand01UpperFrequencyRead to FrequencyBand32UpperFrequencyRead
Registers for reading the maximum frequency of individual frequency bands.
The maximum frequency is specified in 1/4 Hz.
Data type
Value
UINT
1 to 40,000
4.26.2.5.6.3 AutogainDelay01
This register can be used to configure the autogain delay for all four channels.
To ensure that even smaller signals can be calculated precisely, the autogain can be increased in steps. This
happens if there has been no overflow in the number of measurement cycles configured in this register and all
conditions for the next step were always met. If an overflow does occur, then autogain is reduced immediately
by one step.
The unit for delaying autogain is specified in measurement cycles (300 ms). Only values from 1 - 200 are valid.
4.26.2.5.6.4 AutogainDelay01Read
Register for reading the current "AutogainDelay01" configuration.
4.26.2.5.6.5 Control01
General control register for the X20CM4810
Bit
Description
15-2
Reserved = 0
1
MinMaxUpdate01, asynchronous min. and max. values refreshed at each edge
0
RequestBufferLock01 or RequestDataLock01 (0 = Don't lock data, 1 = Lock data)
Table 749: Control01
Summary of Contents for X20 System