X20 system modules • X20 interface module communication • X20IF2181-2
1860
X20 system User's Manual 3.10
4.23.25 X20IF2181-2
4.23.25.1 General information
The X20IF2181-2 interface module is used to expand the X20 CPU for specific applications. It is equipped with
an POWERLINK interface.
POWERLINK is a standard protocol for Fast Ethernet with hard real-time properties. The Ethernet POWER-
LINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed.
Systems with redundant cabling can be implemented easily using POWERLINK. Unlike ring redundancy, cable
redundancy does not require cable looping, which can sometimes be problematic. This allows the creation of all
types of tree structures. When using a device with the link selector function, data is always transferred via the
highest quality network lines. The link selector function is integrated in the X20IF2181-2 module (see 4.23.25.9
"POWERLINK cable redundancy system" on page 1866).
•
POWERLINK V2 for real-time Ethernet communication
•
Integrated link selector function (preconfigured)
•
Redundant Managing Node for CPU redundancy
•
Integrated hub for efficient cabling (configurable)
•
Configurable ring redundancy
•
Poll response chaining
•
Dynamic Node Allocation (DNA)
4.23.25.2 Order data
Model number
Short description
Figure
X20 interface module communication
X20IF2181-2
X20 interface module, 1x link selector for POWERLINK cable
redundancy, POWERLINK functions: - Managing node - Con-
trolled node for iCN operation - Redundant managing node for
CPU redundancy - Ring redundancy - 2x hub - Multi ASend -
PRC function 2x RJ45 connection
Table 646: X20IF2181-2 - Order data
Optional accessories
Model number
Short description
X20CA0E61.xxxxx
POWERLINK connection cable RJ45 to RJ45, 0.2 to 20.0 m
X20CA0E61.0500
POWERLINK connection cable RJ45 to RJ45, 50.0 m
4.23.25.3 Technical data
Product ID
X20IF2181-2
Short description
Communication module
1x POWERLINK managing or controlled node
General information
B&R ID code
0xC3B3
Status indicators
Module status, bus function
Diagnostics
Module status
Yes, using status LED and software
Bus function
Yes, using status LED and software
POWERLINK cable redundancy system
Configurable
CPU redundancy
Configurable
Power consumption
2.0 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Table 647: X20IF2181-2 - Technical data