X20 system modules • X20 interface module communication • X20IF10X0
X20 system User's Manual 3.10
1857
4.23.24 X20IF10X0
4.23.24.1 General information
Interface module for the operation of redundant CPUs.
•
CPU-CPU data synchronization module for redundant CPU systems
4.23.24.2 Order data
Model number
Short description
Figure
X20 interface module communication
X20IF10X0
X20 interface module, 1 redundancy link interface 1000BASE-
SX, CPU-CPU data synchronization module for controller redun-
dancy
Table 643: X20IF10X0 - Order data
4.23.24.3 Technical data
Product ID
X20IF10X0
Short description
Communication module
CPU redundancy link module
General information
B&R ID code
0xC3B4
Status indicators
Module status, bus function
Diagnostics
Module status
Yes, using status LED and software
Bus function
Yes, using status LED and software
Data transfer
Yes, using status LED and software
Power consumption
1.93 W
Additional power dissipation caused by the actua-
tors (resistive) [W]
-
Certification
CE
Yes
cULus
Yes
ATEX Zone 2
Yes
KC
Yes
GOST-R
Yes
Interfaces
Fieldbus
Redundancy link
Standard (compliance)
IEEE Std 802.3, 2002 Edition, Clause 38
Design
1x duplex LC
Transfer rate
1 Gbit/s
Transmission
Physical interfaces
1000BASE-SX
Wave length
850 nm
Cable fiber type
Multimode fiber with 62.5/125 μm or 50/125 μm core diameter
LC connector on both sides
Cable length
MMF 50/125 µm
Min: 2 m, max: up to 500 m
MMF 625/125 µm
Min: 2 m, max: up to 300 m
Operating conditions
Mounting orientation
Horizontal
Yes
Vertical
Yes
Installation at elevations above sea level
0 to 2000 m
No limitations
>2000 m
Reduction of ambient temperature by 0.5°C per 100 m
EN 60529 protection
IP20
Table 644: X20IF10X0 - Technical data
Summary of Contents for X20 System