1TT –TIMER + TERMOREGOLATORE - Reference Manual - Pag. 5 di 7
parameters
Description
Values
Default
Note
SP
(*)
Setpoint
- 99 :: [ Maximum Setpoint]
20°C
Disposable
Parameters with the “123” password only
AL
Alarm
[min] :: [max]
100°C
Int
Kind of probe
tcJ
Termocouple J
tcH
Termocouple K
tcb
Termocouple B
tce
Termocouple E
tcn
Termocouple N
tcr
Termocouple R
tcs
Termocouple S
tct
Termocouple T
pt1
Pt100
p10
Pt1000
TC J
Act
Working method
Hot
Heating
Col
Raffreddamento
Hot
Setting
COL
the
controller will work by
ON/OFF method w.algor.
Eco
ECO mod
0 (off) :: 999
0°C
BSC
Gradient of ramp
0 :: 1
1
The setpoint can
automatically change
nSP
Min. setpoint
- 99 :: 999
- 30 °C
mSP
Max. setopoint
- 99 :: 999
400°C
Tc
Time of Cycle
0,1 :: 999
15 s
PB
Proportional Band
0 (regolazione ON-OFF) : 100
2 %
Percentage of the range
Ti
Integral Time
0 :: 999
120 s
Integral Time
td
Derivative Time
- 1 :: 999
30 s
Select -1 to work
automatically in Ti/4
OFS
TemperatureOffset
- 100 :: +100
0 °C
HSO
Positive differential off SET
0 :: 999
0 °C
Used in case of ON-OFF
reg.
HSU
Negative differential off SET
0 :: 999
1 °C
Used in case of ON-OFF
ALM
Relay Alarm Mode
Absolute Band Alarm
Relay
- (
1 off / 2 on
)
Finestra o deviazione
Relay
- (
4 off / 3 on
)
1
ALS
Setpoint Alarm
0 :: 1
0
Solo per allarme relè
finestra o deviazione
ALH
Absolute High Alarm .
0 :: 999
600 °C