Network Termination

The com-link cable must be properly terminated to reduce the amount of

interference and noise pickup from the surrounding environment. This is

accomplished by using a termination circuit at both ends of the network cable. The

following figure shows a typical termination circuit. The host termination is only

needed if the host controller’s RS-422/485 adapter does not contain any built-in

terminator circuitry. The end termination must be done at the extreme end of the

com-link cable.

Network Grounding

To communicate properly, serious attention must be paid to the grounding scheme

of the devices connected to the com-link. Improper grounding, improper

termination, and faulty shielding of the com-link are the most common causes of

system failure in a multidrop network.

12

MAP450D

1010-0046A, REV 00

Shield

Signal Ground

From Host +

To Host +

Shield

To OIT

To OIT

Signal Ground

From Host

To Host

From Host -

To Host -

HOST TERMINATION

470 Ohm

to

10 KOhm

Tx+

Tx-

Vcc

Rx+

Rx-

SIGNAL GND

CHASSIS GND

EARTH

GROUND

TERMINA

TO

R

HOST

OIT3600

120 Ohm

to

240 Ohm

FROM HOST +

FROM HOST -

TO HOST +

TO HOST -

SIGNAL GND

SHIELD

DO NOT

CONNECT

END TERMINATION

470 Ohm

to

10 KOhm

120 Ohm

to

240 Ohm

MAP460D

OIT3160

TERMINA

TO

R

Summary of Contents for MAP450D

Page 1: ...C D F E P N V W INSTALLATION MANUAL 1010 0046A REV 00 Secure online ordering 24 7 365 from European Headquarters Westlink Commercial Park Oranmore Co Galway Ireland www bb europe com Phone 353 91 7924...

Page 2: ...ense is granted by implication or otherwise under any patent or patent rights of Maple Systems Inc Maple Systems retains the right to revise or change its products and documentation at any time withou...

Page 3: ...circuitry inside is exposed to possible damage by electrostatic discharge during handling Minimize the possibility of electrostatic discharge by Discharging personal static by grounding yourself prio...

Page 4: ...to a Host Controller 7 2 1 RS 232 Interactive Block modes 9 2 2 RS 422 485 Interactive Block modes 9 2 3 RS 422 485 Network mode 10 2 4 Set Jumper for 3 Wire RS 422 485 13 3 Mounting the MAP450D 14 3...

Page 5: ...e braid should be installed from the hinged control panel to the rest of the enclosure 1 2 Power Supply Selection The power supply used to power the OIT should have an output between 12 and 30 VDC The...

Page 6: ...hes 20 cm of separation between the OIT cables and other power wiring If voltages greater than 120 VAC are used in the system greater separation is required IftheOITcablesmust come nearAC wiring make...

Page 7: ...k tubing from the end of the OIT operating cable 4 Slide the ferrite coil over the OIT operating cable This usually requires rotating the ferrite coil back and forth while simultaneously pulling on th...

Page 8: ...nst the inside wall of the OIT enclosure with the protruding OIT operating cable kept short 9 Tighten the cable strain relief nut 10 Re install the four screws into the back of the OIT enclosure 11 Ro...

Page 9: ...configuration has both transmit and receive on the same pair of wires plus a signal common The 5 wire configuration has differential signal pairs for transmit and receive plus a signal common In both...

Page 10: ...t the same time 3 wire RS 422 485 only supports half duplex communications which means that the host controller cannot transmit and receive data at the same time Although 3 wire RS 422 485 installatio...

Page 11: ...e in this mode Therefore each command sent from the host controller should end with the appropriate line terminator If the host controller sends a command that requires a response from the OIT the hos...

Page 12: ...Network Grounding To communicate properly serious attention must be paid to the grounding scheme of the devices connected to the com link Improper grounding improper termination and faulty shielding o...

Page 13: ...entials and currents Connecting the signal ground to chassis or earth ground can damage the devices connected to the com link 2 4 Set Jumper for 3 Wire RS 422 485 This step is required only if the OIT...

Page 14: ...utout required for proper panel installation The panel cutout should be cleaned and deburred before the OIT is installed 14 MAP450D 1010 0046A REV 00 The OIT is mounted using four 6 32UNC screws sandw...

Page 15: ...to a mounting plate using the four pre tapped holes in the rear cover The OIT enclosure and cable strain relief provide the environmental seal to NEMA 4 and NEMA 12 standards Figure 11 shows the minim...

Page 16: ...r cover has two legs set at a five degree angle to give the display and keypad a sloped front while sitting on a bench Four rubber feet are attached to the legs to prevent slippage as well as damage t...

Page 17: ...e 4 1 Connecting the MAP450D to a PC First remove the operating cable from the terminal block pins Next connect an RS 232 serial communications cable Maple Systems P N 7431 0048 to the proper COM port...

Page 18: ...y industrial environment Power Requirements Input Voltage 12 to 30 VDC Power Usage 2 5 watts typical Display Display Type MAP450D 003 Liquid Crystal Display LCD 5 x 7 dot matrix with cursor Display Ty...

Page 19: ...0 127 0 90 23 depth behind the front of a panel 8 12 206 6 32UNC x 0 50 12 7 screw 4 places SS 6 32UNC x 0 30 7 6 deep threads for Pedestal Mounting only REAR VIEW FRONT VIEW SIDE VIEW Free Standing P...

Page 20: ...mmunity and emissions 5 Local setup mode is entered by pressing and holding the Clear key instead of the S key while the Initializing prompt is on the display Local setup mode can also be entered afte...

Reviews: