![B&B Electronics GW-7472 User Manual Download Page 10](http://html1.mh-extra.com/html/bandb-electronics/gw-7472/gw-7472_user-manual_3070099010.webp)
GW-7472 User Manual, Version 1.0, Dec 2010
--- 10
2.2
Features
General Features:
Powerful 32-bit MCU handles efficient network traffic
10/100 Base-TX Ethernet, RJ-45 x1
(Auto-negotiating, auto MDI/MDIX, LED Indicators)
Redundant power inputs: PoE (IEEE 802.3af, Class 1) and DC jack
Automatically RS-485 direction control
Support ARP,TCP, UDP, ICMP, DHCP, BOOTP and TFTP protocols
Easy firmware update via Ethernet
Removable terminal block connector
Tiny form-factor and low power consumption
RoHS compliant with Halogen-free
Fire retardant materials (UL94-V0 Level)
EtherNet/IP Features:
Ethernet Protocol: EtherNet/IP adapter
Maximum number of connections for Explicit Messages: 6
Maximum number of connections for Implicit Messages: 1
Supported I/O connection methods:
Transport and trigger: Exclusive-Owner, Cyclic
Original to Target Type: POINT2POINT
Target to Original Type: POINT2POINT, MULTICAST
Device Configuration Option: EDS, Utility tool
Address Configuration: DHCP, Utility tool
EtherNet/IP Input/Output command data size: maximum 500 bytes
The numbers of the Modbus RTU slave input registers mapping to the input registers of
the EtherNet/IP adapter of the GW-7472: maximum 500 bytes
The numbers of the Modbus RTU slave output registers mapping to the output registers
of the EtherNet/IP adapter of the GW-7472: maximum 500 bytes