Symptom
Actions
Gate operator does
not respond when
commanded.
1.
Check CONN 9 for power when command is given.
2.
Check overload protector
3.
Check PLC output.
4.
Check that safeties are clear, and that IR Beams are aligned.
5.
Check PLC input.
6.
Check the +24VDC at CONN3 pins 8 and 10
Gate operator drives
the gate in the
incorrect direction.
1.
Refer to step 4.10 of Installing and Programming the LXL
Operator for setting the handing.
2.
Refer to step 4.5 of Installing and Programming the LXL
Operator to check for correct installation of the Limit
Switch Plates.
Operator drives gate
too slowly.
1.
Check for any binding of the gate.
2.
Check for slippage of the drive wheels.
3.
Check the fluid level in the reservoir.
4.
Check the quality of the hydraulic fluid. Old fluid will
become sludgy and clogging of internal filter is possible.
MAX Runtime Error
1.
Check for any binding of the gate.
2.
Check for slippage of the drive wheels.
3.
Check the fluid level in the reservoir.
4.
Check the MAX RUN TIME setting in Parameters to insure
sufficient time is set for the gate size.
5.
REMEMBER – Gate only may only move 1 ft/sec
Date and time flash
on the PLC.
1.
Refer to step 4.11 of Installing and Programming the LXL
Operator for setting the date and time. (Optional, not
required to be set)
Gate does not stop
automatically when
encountering an
obstacle.
1.
Refer to step 4.15 of Installing and Programming the LXL
Operator for setting the Inherent Safety.
2.
Check for system pressure on Inherent Safety screen of the
PLC, if no reading is evident while gate is running suspect a
faulty pressure transducer.
3.
Check the functionality of the safety devices.
4.
Check safety device wiring, refer to sections 6 and/or 8
Operator drive
wheels slip on gate
and gate does not
move.
1.
Check for binding by disengaging the drive wheels, and
ensuring that the gate rides smoothly manually.
2.
Check the tension of the drive wheels, adjust as needed.
3.
Check for any water or precipitation on the drive rail.
Fuses are blowing.
1.
Check for incorrect incoming power to the LXL board.
2.
Ensure all external devices are sending the correct voltage
to the LXL board, and that there are no shorts.
PLC says Stop/Reset
activated.
1.
If using an external push button, ensure that the stop button
is a normally closed contact.
2.
If not using an external push button, ensure there is a
jumper wire between stop/reset and +24 stp/rst on CONN 3.