531 M1 02 A
16-07-2010
4
LED for status
“Low battery”
(< 10 V DC)
LED relays status
DIP switch
Selector
Power input
10...27 V DC
Relays S1 - S2 - S3
LED for
status
of sensors
Sensors inputs
E1 - E2 - E3
Intrinsic safety
circuits
Do not connect yet the main power
Function ON
Function OFF
DIP 1
Audible alarm available
Audible alarm disabled
DIP 2
Audible alarm repeats each 24 h
Audible alarm repeat function disabled
DIP 3
DIP 4
Do not modify the setting of DIP 3 & 4, they must be in OFF position all the time
DIP 5
Relays are NC
(when the unit is powered)
Relays are NO
(when the unit is powered)
DIP 6 *)
Monitoring frequency: each 6 to 54 min
*)
DIP 7 *)
Monitoring frequency: each 3 to 37 h
*)
DIP 8 *)
Monitoring frequency: each 1 to 9 days
*)
DIP switch setting
0
1
2
3
4
5
6
7
8
9
DIP 6
=
ON
Continuous monitoring
6 min
12 min
18 min
24 min
30 min
36 min
42 min
48 min
54 min
DIP 7
=
ON
Continuous monitoring
3 h
6 h
9 h
12 h
15 h
18 h
21 h
24 h
27 h
DIP 8
=
ON
Continuous monitoring
1 day
2 days
3 days
4 days
5 days
6 days
7 days
8 days
9 days
*): When a DIP switch configuration is wrong, the alarm unit will survey continuously
(Example: none of the DIP switch 6, 7 and 8 is in ON position; or, two of them are in ON position).
Selector setting
((Duration of a monitoring cycle + sleep mode period)
Factory setting: DIP 6, 7 and 8 are in the position OFF
Factory setting:
in position 0 for a continuous monitoring
!