background image

555 M1 01 B

03-01-2008

Page 2

CAUTION

Trained personnel may only perform installation, initial start-up and maintenance. 
All applicable European and national regulations regarding installation of electrical equipment must be adhered to.

•  The device may only be connected to supply power complying with the specifications included in the technical data and on the

serial plate.

•  The device must be disconnected from all sources of power during installation and maintenance work!
•  The device may only be operated under the conditions specified in the operating instructions!

DESCRIPTION

The MAXIMAT C, compact overfill sensor, is used as an overfill monitoring device for permanently installed containers used for
the storage of non-flammable, water endangering liquids. 

It is equipped with three different output circuits: 

•  A binary output for controlling a coupling relay or the digital input at a PLC 
•  A 0 to 20 mA current output for controlling an analog input channel, e.g. a programmed logic controller (PLC) 
•  Self-monitoring measuring circuit in combination with the MAXIMAT SHR C... measuring transducer with a 2 wires connection. 

Applications: 

Note that stored liquids may not tend to precipitate insulating or conductive sediments.

CE mark: 

In accordance with low-voltage directive (73/23/EWG), EMC directive (89/336/EWG)

TECHNICAL FEATURES

Supply power: 

24 V DC ± 10% (power supply with current limiting or 250 mA fuse recommended 

Connected load: 

Approx. 3 W 

Ambient temperature: 

-20 to +60°C 

Container pressure: 

Atmospheric (0.8 to 1.1 bar) 

Outputs: 
+DO / -DO 

NPN max. 30 mA / max. 24 V DC 

+AO / -AO 

0 to 20 mA

Housing: 

IP 65 – PBT – EN 60529

Terminals: 

Screw terminals, IP 20 

Cable: 

Maximal wire cross-section = 2.5 mm_ 

Input T / OV: 

External connection for device test. 
Alarm ON when test is positive. 

Indicators: 

Green LED on the connector PCB 
LED illuminated = Run 
LED off = Alarm / error 

Measuring circuit for use with SHR C...
Cable inductance: 

Maximum approx. 5 mH 

Cable capacitance: 

Maximum approx. 0.5 μF 

Measuring circuit cable:

Maximal length = 300 m 

Wire cross-section: 

Minimum 0.5 mm

2

DIBT Approval

Approval N° Z-65.13-294 for overfill sensors and leakage sensors in accordance with WHG §19 

Note: The accompanying “General Building Supervisory Approval N° Z-65.13-294” is an integral part of the operating instructions and all
stipulations contained therein must be adhered to! 

Reviews: