INSTRUCTIONS FOR DETERMINING THE CAUSE LEADING TO IRREGULARITIES IN THE OPE-
RATION AND THEIR ELIMINATION
IRREGULARITY
The burner does not start.(The
equipment does not perform the
start up program).
Defective flame with sparks.
Flame not properly shaped with
presence of smoke and soot.
Defective flame, flickering or pro
-
truding from combustion orifice.
POSSIBLE CAUSE
1 Thermostats (boiler or room) or pressure
switches are open.
2 Photoresistor in short circuit.
3 Absence of line voltage, main switch open,
meter switch tripped or absence of line
voltage.
4 Thermostat line not wired according to
diagram or open thermostats.
5 Equipment internal fault.
1 Spraying pressure is too low.
2 Too much combustion air.
3 Nozzle inefficient because dirty or worn.
4 Water in the fuel.
1 Insufficient combustion air flow.
2 Nozzle inefficient because dirty or worn.
3 Nozzle capacity too low with respect to
combustion chamber volume.
4 Combustion chamber unsuitably designed
or too small.
5 Unsuitable refractory coating (it reduces
excessively the space of the flame).
6 Boiler or chimney ducts blocked.
7 Spraying pressure is low.
1 Excessive draught, only when there is an
extractor in the chimney.
2 Nozzle inefficient because dirty or worn.
3 Water in the fuel.
4 Dirty flame disk.
5 Too much combustion air.
6 Air passage between flame disk and diffu
-
ser excessively closed.
REMEDY
1 Raise the thermostats settings, or wait that
the contacts close for natural decrease of
temperature or pressure.
2 Replace it.
3 Activate switches or wait for power to return.
4 Check the connections and thermostats.
5 Replace it.
1 Restore it at the required value.
2 Reduce combustion air
3 Clean or replace.
4 Drain water from the tank using a suitable
pump. Never use the burner pump for this
purpose.
1 Increase combustion air.
2 Clean or replace.
3 Decrease diesel flow rate to suit the chamber
(thermal power will obviously be lower than
necessary) or replace the boiler.
4 Increase nozzle flow by replacing it.
5 Modify it, carefully abiding by the instructions
given by boiler manufacturer.
6 Arrange for cleaning.
7 Restore it at the required value.
1 Adjust the suction fan speed by changing the
pulley diameter.
2 Clean or replace.
3 Drain water from the tank using a suitable
pump. Never use the burner pump for this
purpose.
4 Clean.
5 Reduce combustion air.
6 Correct the position of the combustion head
regulating device.
ENGLISH
39 / 54
0006160337_202006
Summary of Contents for TBML 80 ME
Page 2: ......
Page 44: ...SCHEMI ELETTRICI TBML 80 120 160 ITALIANO 42 54 0006160337_202006...
Page 45: ...ITALIANO 43 54 0006160337_202006...
Page 46: ...ITALIANO 44 54 0006160337_202006...
Page 47: ...ITALIANO 45 54 0006160337_202006...
Page 48: ...BT1 BA BP I1 I2 I3 I4 ITALIANO 46 54 0006160337_202006...
Page 50: ...TBML 210 310 ITALIANO 48 54 0006160337_202006...
Page 51: ...ITALIANO 49 54 0006160337_202006...
Page 52: ...ITALIANO 50 54 0006160337_202006...
Page 53: ...ITALIANO 51 54 0006160337_202006...
Page 54: ...BT1 BA BP I1 I2 I3 I4 ITALIANO 52 54 0006160337_202006...
Page 56: ...ITALIANO 54 54 0006160337_202006...
Page 98: ...WIRING DIAGRAMS TBML 80 120 160 ENGLISH 42 54 0006160337_202006...
Page 99: ...ENGLISH 43 54 0006160337_202006...
Page 100: ...ENGLISH 44 54 0006160337_202006...
Page 101: ...ENGLISH 45 54 0006160337_202006...
Page 102: ...BT1 BA BP I1 I2 I3 I4 ENGLISH 46 54 0006160337_202006...
Page 104: ...TBML 210 310 ENGLISH 48 54 0006160337_202006...
Page 105: ...ENGLISH 49 54 0006160337_202006...
Page 106: ...ENGLISH 50 54 0006160337_202006...
Page 107: ...ENGLISH 51 54 0006160337_202006...
Page 108: ...BT1 BA BP I1 I2 I3 I4 ENGLISH 52 54 0006160337_202006...
Page 110: ...ENGLISH 54 54 0006160337_202006...
Page 111: ......