ASSEMBLING THE GAS TRAIN
The EN 676 approved gas train is sold separately from the burner.
To ensure optimal functioning of the pressure regulator, it should be
applied to the horizontal pipe after the filter.
The gas pressure regulator must be regulated when the burner is
working at the maximum flow.
The delivery pressure must be adjusted to a level slightly below the
maximum attainable (i.e. that obtained when the regulation screw is
screwed in almost fully).
The gas train can be assembled in different ways: (8), (8a) .
GAS SUPPLY LINE
A
B
000291
1151
1
Air/gas regulation servomotor
2
Air pressure switch
3
Maximum gas pressure switch
4
Gas supply control butterfly valve
5
Operating gas valve with pressure regulator
6
Valve seal control device (mandatory for burners with maximum rated
heating capacity higher than 1200kW)
7
Safety gas valve for ignition flame
8
Minimum gas pressure switch and gas leak control
9
Gas filter
10
Air regulation damper
11
Vibration-proof joint
12
Manual shut-off valve
A
To be carried out by the installer
B
Baltur supply limit
12 / 30
0006160266_202106
ENGLISH
Summary of Contents for TBG 900 MC
Page 2: ......
Page 28: ...SCHEMI ELETTRICI TBG 800 MC 900 MC 1100 MC 26 30 0006160266_202106 ITALIANO...
Page 29: ...TBG 800 MC 900 MC 1100 MC 27 30 0006160266_202106 ITALIANO...
Page 30: ...TBG 800 MC 900 MC 1100 MC 28 30 0006160266_202106 ITALIANO...
Page 31: ...TBG 800 MC 900 MC 1100 MC 29 30 0006160266_202106 ITALIANO...
Page 58: ...WIRING DIAGRAMS TBG 800 MC 900 MC 1100 MC 26 30 0006160266_202106 ENGLISH...
Page 59: ...TBG 800 MC 900 MC 1100 MC 27 30 0006160266_202106 ENGLISH...
Page 60: ...TBG 800 MC 900 MC 1100 MC 28 30 0006160266_202106 ENGLISH...
Page 61: ...TBG 800 MC 900 MC 1100 MC 29 30 0006160266_202106 ENGLISH...
Page 63: ......