PROGRESSIVE/MODULATING TWO-STAGE GAS BURNERS 

WITH MECHANICAL CAM

ITALIANO

Manuale istruzioni per l'installazione, l'uso 

e la manutenzione

IT

Instruction manual for 

installation, use and maintenance

EN

TBG 450LX MC

TBG 510LX MC

TBG 650LX MC

TBG 750LX MC

ISTRUZIONI ORIGINALI (IT)

ORIGINAL INSTRUCTIONS (IT)

0006160271_202007

Summary of Contents for TBG 450LX MC

Page 1: ...TWO STAGE GAS BURNERS WITH MECHANICAL CAM ITALIANO Manuale istruzioni per l installazione l uso e la manutenzione IT Instruction manual for installation use and maintenance EN TBG 450LX MC TBG 510LX...

Page 2: ......

Page 3: ...llegamenti elettrici 17 Descrizione del funzionamento 22 Descrizione del funzionamento a modulazione 23 Accensione e regolazione 24 Apparecchiatura di comando e controllo per bruciatori a gas LME73 27...

Page 4: ...RTENZE GENERALI La data di produzione dell apparecchio mese anno sono indicati sulla targa identificazione bruciatore presente sull apparecchio L apparecchio non adatto a essere usato da persone bambi...

Page 5: ...e quelle parti che potrebbero essere potenziali fonti di pericolo AVVERTENZE PER L AVVIAMENTO IL COLLAUDO L USO E LA MANUTENZIONE L avviamento il collaudo e la manutenzione devono essere effet tuati e...

Page 6: ...essere sosti tuito dall utente In caso di danneggiamento del cavo spegnere l apparecchio Per la sua sostituzione rivolgersi esclusivamente a personale professionalmente qualificato Allorch si decida d...

Page 7: ...e soddisfare i requisiti speciali per interruttori di comando con apertura diretta fare riferimento a EN 60947 5 1 2016 Allegato K Si raccomanda che il dispositivo di arresto di emergenza sia di color...

Page 8: ...N 380V 10 3N 380V 10 3N 380V 10 Grado di protezione IP54 IP54 IP54 IP54 Rilevazione fiamma SONDA IONIZZA ZIONE SONDA IONIZZA ZIONE SONDA IONIZZA ZIONE SONDA IONIZZA ZIONE Apparecchiatura LME 73 LME 73...

Page 9: ...mbustibili gassosi 8 Pressione combustibili gassosi 9 Viscosit combustibili liquidi 10 Potenza motore ventilatore 11 Tensione di alimentazione 12 Grado di protezione 13 Paese di costruzione e numeri d...

Page 10: ...e devono essere rispondenti alla normativa vigente in caso contrario vanno consultati i costruttori Il bruciatore non deve operare al di fuori del campo di lavoro dato CALCOLO DELLA PORTATA TERMICA DE...

Page 11: ...tore aria in aspirazione 12 Presa di pressione gas alla testa di combustione 13 Modulatore regolazione aria gas 14 Dispositivo regolazione testa 15 Targa identificazione bruciatore QUADRO ELETTRICO 1...

Page 12: ...in aspirazione 12 Presa di pressione gas alla testa di combustione 13 Modulatore regolazione aria gas 14 Dispositivo regolazione testa 15 Targa identificazione bruciatore QUADRO ELETTRICO 1 Apparecchi...

Page 13: ...00 TBG 750LX MC 1180 530 650 810 525 285 295 1800 Modello D D1 E F G H I L M N TBG 450LX MC 650 547 597 397 410 DN80 223 480 520 600 M20 415 TBG 510LX MC 650 547 597 397 410 DN80 223 480 520 600 M20 4...

Page 14: ...ella presenza di fiamma tramite elettrodo ionizzatore Apparecchiatura automatica di comando e controllo del bruciatore con microprocessore secondo normativa europea EN298 integrata con controllo tenut...

Page 15: ...ondelle e i relativi dadi in dotazione 7 0002950280 19 13 14 7 APPLICAZIONE DEL BRUCIATORE ALLA CALDAIA CON RAM PA GAS VERSO L ALTO Smontare i golfari di sollevamento 21 dal polmone Smontare la leva d...

Page 16: ...ale idoneo lo spazio tra il canotto del bruciatore e il foro refrattario all interno del portel lone caldaia Montare il mozzo 28 Avvitare l indice leva gas 1 e la vite sul lato opposto del polmone 8 M...

Page 17: ...nare la flangia del ventilatore a contatto con quella del polmone Chiudere il bruciatore utilizzando le viti e i dadi 11 Terminata la fase di collegamento del corpo ventilante al gruppo testa sganciar...

Page 18: ...o possibili diverse soluzioni di montaggio 8 8a 9 9a della rampa gas 0002950430 8 8a 9 9a 0002950440 LINEA DI ALIMENTAZIONE GAS 0002911210 1 4 10 2 3 8 9 7 5 6 11 12 A B 1 Servomotore regolazione aria...

Page 19: ...ta dal bruciatore Prevedere un interruttore onnipolare con distanza d apertura dei contatti uguale o superiore a 3 mm per l allacciamento alla rete elet trica come previsto dalle normative di sicurezz...

Page 20: ...singoli affiancati e non avvolti Prevedere gli eventuali declassamenti in caso di condizioni differenti Le sezioni dei cavi di connessione vanno scelte in base alla distanza dal punto di allacciament...

Page 21: ...di cortocircuito estre mo Icu kA 100 100 100 100 100 100 100 100 Tempo di intervento fusibile Ti 6 sec 0 2 0 07 0 2 0 07 0 2 0 07 0 2 1 Tempi di intervento fusibile Ti 7 sec 5 5 5 5 5 5 5 5 4 Le sezi...

Page 22: ...Ti 5 s Taglia fusibile In 50 A Curva_Tagliafusibili Ia 160 A Inserire il valore di Ia ottenuta dal grafico all interno della formula fornita in A 1 2 della EN60204 2016 per ottenere il valore massimo...

Page 23: ...ento Ti 0 2 s Taglia fusibile In 6 A Curva_Tagliafusibili01 Ia 36 A Inserire il valore di Ia ottenuta dal grafico allinterno della formula for nita in A 2 2 3 della EN60204 2016 per ottenere il valore...

Page 24: ...aia interviene e determina l arresto del bruciatore La serranda aria raggiunge mediante la rotazione del servomotore la posizione di chiusura in sosta Nel caso in cui il dispositivo di controllo non r...

Page 25: ...edente La rotazione all indietro e quindi la riduzione dell erogazione aria e gas avviene a brevi intervalli di tempo Con questa manovra il sistema di modulazione cerca di equilibrare la quantit di ca...

Page 26: ...hiatura di comando riceve cos tensione ed il programmatore determina l inserzione del bruciatore come descritto nel capitolo Descrizione del funzionamento Durante la fase di preventilazio ne accertars...

Page 27: ...ositi strumenti i parametri di combustione in primo stadio CO2 max 10 O2 min 3 CO max 0 1 REGOLAZIONE DELLA PORTATA DI ACCENSIONE Una volta effettuata la regolazione della potenza minima occorre spegn...

Page 28: ...iore a quella a cui regolato Il pressostato di massima utilizza il contatto NC normalmente chiuso che si trova chiuso quando rileva una pressione inferiore a quella a cui regolato La regolazione dei p...

Page 29: ...RATIVO Durante l accensione si hanno indicazioni di stato secondo la seguente tabella Tabella codici colori per la spia LED Condizione Sequenza colori Colori Condizioni di attesa TW altri stati interm...

Page 30: ...rtura aria d accensione maggiore di camma III 30 1 Leva di inserzione ed esclusione accoppiamento motore albe ro camme 2 Indice di riferimento 3 Albero camme 4 Camme regolabili PER MODIFICARE LA REGOL...

Page 31: ...510 10 3 11 TBG 650 10 3 11 TBG 750 10 3 11 0002950270 X 6 8 8 7 Z 6 Entrata gas 7 Flangia attacco bruciatore 8 Pomello regolazione testa di combustione x Distanza testa disco z Indice posizione test...

Page 32: ...esclu sivamente tra lo stesso ed il disco in lamiera forata vedi schema di regolazione testa di combustione e distanza disco elettrodi per la versione senza pilota Fare attenzione durante le operazio...

Page 33: ...AGGIO PATTINO E VITI ANNO LEVE TIRANTI SNODI SFERICI CONTROLLO EVENTUALI USURE LUBRIFICAZIONE COMPONENTI ANNO IMPIANTO ELETTRICO VERIFICA CONNESSIONI E SERRAGGIO MORSETTI ANNO INVERTER PULIZIA VENTOLA...

Page 34: ...o di pagamento sono indipendenti e non fanno riferi mento alla vita attesa di seguito indicata Per condizioni operative normali si intendono applicazioni su caldaie ad acqua e generatori di vapore op...

Page 35: ...ificazione naturale da batteria di bombole o serbatoio utilizzabile solo per impianti di piccola potenza La capacit di erogazione in fase di gas in funzione delle dimensioni del serba toio e della tem...

Page 36: ...lizzatore Riduttore di 2 salto Uscita 30 hPa mbar Portata il doppio del massimo richiesto dall utilizzatore Filtro a Y Filtro Filtro Presa di pressione Riduttore di 2 salto Uscita 30 hPa mbar Portata...

Page 37: ...sfogata dall aria caso di prima accensione La pressione del gas insufficiente o eccessiva Passaggio aria tra disco e testa troppo chiuso RIMEDIO Invertire l alimentazione lato 230V del trasformatore d...

Page 38: ...SCHEMI ELETTRICI ITALIANO 36 46 0006160271_202007...

Page 39: ...ITALIANO 37 46 0006160271_202007...

Page 40: ...ITALIANO 38 46 0006160271_202007...

Page 41: ...ITALIANO 39 46 0006160271_202007...

Page 42: ...ITALIANO 40 46 0006160271_202007...

Page 43: ...ITALIANO 41 46 0006160271_202007...

Page 44: ...ITALIANO 42 46 0006160271_202007...

Page 45: ...ITALIANO 43 46 0006160271_202007...

Page 46: ...ITALIANO 44 46 0006160271_202007...

Page 47: ...ITALIANO 45 46 0006160271_202007...

Page 48: ...RESSOSTATO DI MASSIMA Q1 2 INTERRUTTORE DIFFERENZIALE MAGNETOTERMICO S1 INTERRUTTORE MARCIAARRESTO S2 PULSANTE SBLOCCO S4 SELETTORE AUT MAN S5 COMMUTATORE DI MODULAZIONE MIN O MAX SG1 2 SEZIONATORE GE...

Page 49: ...l connections 17 Operating description 22 Modulation operation description 23 Starting up and regulation 24 LME73 Gas burner control device 27 Detail of the modulation control motor SQM 40 for cam adj...

Page 50: ...re and humidity conditions The storage time is 3 years GENERAL WARNINGS The equipment production date month year is written on the bur ner identification plate located on the equipment The equipment c...

Page 51: ...main switch Cut off the fuel supply using the shut off valve and remove the control wheels from their position Render harmless any potentially dangerous parts WARNINGS FOR START UP TEST USE AND MAINT...

Page 52: ...n case of cable damage turn the equipment off To replace it contact qualified personnel only If you decide not to use the equipment for a certain period of time it is advisable to switch off the elect...

Page 53: ...evice must fulfil the special requirements for control switches with direct opening refer to EN 60947 5 1 2016 Attachment K It is recommended that the emergency stop device is red and the surface behi...

Page 54: ...pply voltage 3N 380V 10 3N 380V 10 3N 380V 10 3N 380V 10 Protection rating IP54 IP54 IP54 IP54 Flame detection IONISATION PROBE IONISATION PROBE IONISATION PROBE IONISATION PROBE Control box LME 73 LM...

Page 55: ...er 6 Liquid fuel power 7 Gaseous fuel power 8 Gaseous fuel pressure 9 Liquid fuel viscosity 10 Fan motor power 11 Power supply voltage 12 Protection rating 13 Country of origin and numbers of certific...

Page 56: ...size of the combustion chamber must correspond to current regulations if not the manufactu rers must be consulted The burner shall not operate outside its specific operating range CALCULATION OF BURNE...

Page 57: ...Intake air conveyor 12 Gas pressure port to combustion head 13 Adjusting air gas modulator 14 Combustion head adjustment device 15 Burner identification plate ELECTRICAL PANEL 1 Control box 2 Air pre...

Page 58: ...ke air conveyor 12 Gas pressure port to combustion head 13 Adjusting air gas modulator 14 Combustion head adjustment device 15 Burner identification plate ELECTRICAL PANEL 1 Control box 2 Air pressure...

Page 59: ...0 TBG 750LX MC 1180 530 650 810 525 285 295 1800 Model D D1 E F G H I L M N TBG 450LX MC 650 547 597 397 410 DN80 223 480 520 600 M20 415 TBG 510LX MC 650 547 597 397 410 DN80 223 480 520 600 M20 415...

Page 60: ...f ionisation electrode Automatic burner command and control equipment with micropro cessor in compliance with European standard EN298 integrated with valve seal control Electrical system with protecti...

Page 61: ...e stud bolts washers and nuts provided 7 0002950280 19 13 14 7 APPLICATION OF BURNER TO BOILER WITH GAS TRAIN UPWARDS Remove the lifting eyebolts 21 from the lung Remove the gas valve control lever 12...

Page 62: ...een the burner sleeve and the hole in the refractory material inside the boiler door with sui table material Fit the hub 28 Screw the gas lever indicator 1 and the screw on lung opposite side 8 Fit th...

Page 63: ...d position fan flange in contact with lung flange Close the burner using the screws and the nuts 11 Once the ventilating body is connected to the head unit release the lifting chains or ropes Connect...

Page 64: ...rain can be assembled 8 8a 9 9a in different ways 0002950430 8 8a 9 9a 0002950440 GAS SUPPLY LINE 0002911210 1 4 10 2 3 8 9 7 5 6 11 12 A B 1 Air gas regulation servomotor 2 Air pressure switch 3 Maxi...

Page 65: ...rt the maximum current absorbed by the burner For the mains supply connection is required an omnipolar switch with a contact opening gap equal or above 3 mm in accordance with current safety regulatio...

Page 66: ...of 40 C considering single cables placed side by side and not wound Provide for any downgrades in case of different conditions The sections of connection cables must be chosen based on the distance f...

Page 67: ...rcuit breaking capacity Icu kA 100 100 100 100 100 100 100 100 Fuse intervention time Ti 6 sec 0 2 0 07 0 2 0 07 0 2 0 07 0 2 1 Fuse intervention time Ti 7 sec 5 5 5 5 5 5 5 5 4 Sections S1 and S2 are...

Page 68: ...ention time Ti 5 s Fuse size In 50 A Curva_Tagliafusibili Ia 160 A Enter the value of Ia obtained from the diagram in the formula provi ded in A 1 2 of EN60204 2016 to obtain the maximum value of Zsn...

Page 69: ...ervention time Ti 0 2 s Fuse size In 6 A Curva_Tagliafusibili01 Ia 36 A Enter the value of Ia obtained from the diagram in the formula provi ded in A 2 2 3 of EN60204 2016 to obtain the maximum value...

Page 70: ...n the boiler The air damper through the rotation of the servomotor will reach the closed position when inactive In the event that the control device does not detect the presence of a flame the control...

Page 71: ...sequently a reduction in gas and air flow take place in short time intervals With this procedure the modulation system attempts to balance the amount of heat supplied to the boiler with respect to the...

Page 72: ...d all enabling si gnals this powers on the control device and the programmer turns on the burner as described in the chapter Operation description During the pre ventilation phase make sure that the p...

Page 73: ...instruments C02 max 10 O2 min 3 CO max 0 1 ADJUSTING THE FLOW RATE FOR IGNITION Once regulation of minimum flame has been carried out the burner needs to be switched off and check that ignition occurs...

Page 74: ...s the NC normally closed contact that is closed when the pressure switch detects a pressure lower than the value it is set to Adjustment of minimum and maximum pressure values on the pres sure switche...

Page 75: ...ignition the following status indications are provided as per the table below Colour code table for the warning light LED Condition Colour sequence Colours Waiting conditions TW other intermediate co...

Page 76: ...than cam IV 20 IV Ignition air opening greater than cam III 30 1 Lever for enabling disabling motor camshaft coupling 2 Reference scale 3 Camshaft 4 Adjustable camshaft TO MODIFY THE SETTING OF THE C...

Page 77: ...11 TBG 510 10 3 11 TBG 650 10 3 11 TBG 750 10 3 11 0002950270 X 6 8 8 7 Z 6 Gas inlet 7 Burner connection flange 8 Combustion head adjustment knob x Head disk distance z Combustion head index positio...

Page 78: ...ition electrode spark takes place exclusively between itself and the drilled disk see combustion head and electrode disk distance regulation diagram for the version without pilot Be careful during the...

Page 79: ...CK OF WEAR AND OPERATION GREASING OF SLIDING BLOCK AND SCREWS YEAR LEVERS TIE RODS BALL JOINTS CHECK OF ANY WEAR COMPONENT LUBRICATION YEAR ELECTRICAL SYSTEM CHECK OF CONNECTIONS AND TERMINAL TIGHTENI...

Page 80: ...ontracts and or delivery or payment notes if necessary are independent and do not refer to the expected lifespan stated below Normal operating conditions means applications on water boilers and steam...

Page 81: ...rect safe operation Natural gasification from sets of cylinders or a tank can be used only in low power systems Gas supply capacity on the basis of tank size and minimum outdoor temperature are shown...

Page 82: ...red by the user 2nd step reducer Output 30 hPa mbar Flow rate double the maximum required by the user Y filter Filter Filter Pressure intake 2nd step reducer Output 30 hPa mbar Flow rate double the ma...

Page 83: ...case of first ignition The gas pressure is insufficient or exces sive Air flow between disk and head too nar row REMEDY Invert the ignition transformer power supply 230V side and check using an analog...

Page 84: ...WIRING DIAGRAMS ENGLISH 36 46 0006160271_202007...

Page 85: ...ENGLISH 37 46 0006160271_202007...

Page 86: ...ENGLISH 38 46 0006160271_202007...

Page 87: ...ENGLISH 39 46 0006160271_202007...

Page 88: ...ENGLISH 40 46 0006160271_202007...

Page 89: ...ENGLISH 41 46 0006160271_202007...

Page 90: ...ENGLISH 42 46 0006160271_202007...

Page 91: ...ENGLISH 43 46 0006160271_202007...

Page 92: ...ENGLISH 44 46 0006160271_202007...

Page 93: ...ENGLISH 45 46 0006160271_202007...

Page 94: ...MINIMUM PRESSURE SWITCH PM MAXIMUM PRESSURE SWITCH Q1 2 DIFFERENTIAL CIRCUIT BREAKER S1 START STOP SWITCH S2 RELEASE BUTTON S4 AUT MAN SELECTOR S5 MIN O MAX MODULATION SWITCH SG1 2 MAIN DISCONNECTING...

Page 95: ......

Page 96: ...Il presente catalogo riveste carattere puramente indicativo La casa pertanto si riserva ogni possibilit di modifica dei dati tecnici e di quant altro in esso riportato Information contained in this c...