background image

18

DESCRIPTION OF TWO STAGE PROGRESSIVE OPERATIONS WITH LIGHT OIL
COMIST...DSPGM 

(See BT 8714/2)

This is referred to as a 2-stage progressive operation because the passage from the 1st flame to the 2nd flame
(from the minimum rate to the maximum pre-established rate) takes place gradually both as delivery of combustion
air and of fuel. The burner’s control box (cyclic relay) is connected by operating panel switch ( I ).

Control box specifications

The cyclic relay control box carries out the ignition programme by starting up the fan motor and thus the pump in
order to effect the pre-ventilation and light oil pre-circulation phases.
It is necessary that the air pressure supplied by the fan is sufficient to cause the intervention of the relative
pressure switch, if not, the control box will go to “shut down”.
Oil from the pump reaches the atomizer unit and circulates within it because the passages leading to the outward
and return nozzles are closed. This closure is carried out by “closing pins” applied to the ends of the rods.
These “pins” are pressed against their seats by strong springs which are situated at the opposite ends of the rods.
The oil circulates, comes out of the atomizer unit return and arrives at the return pressure regulator.
It passes through this and reaches the pump return and from there it is discharged back into the return.
Oil circulation, as described above, should be carried out at a pressure value slightly higher (by some bar) than the
minimum pressure at which the return pressure regulator has been set (10 ÷ 12 bar).
Duration of the pre-ventilation and oil pre-circulation phase is not as foreseen by the control box, because it is
effected when the air shutter is in an open position.
The pre-ventilation and pre-circulation time is calculated by summing together the times of the following manoeuvres:
- the delivery regulation servomotor’s opening stroke (fuel/air)  +
- preventilation time foreseen by the control box  +
- the closing stroke of the delivery regulation servomotor (fuel/air) until ignition air position.
Subsequently, the control box continues carrying out the ignition programme by connecting the ignition transformer
which feeds the electrodes with high voltage. The voltage between the electrodes primes the electric spark for
ignition of the fuel/air mixture.  After the insertion spark appears, the control box carries voltage to the magnet
which, by means of appropriate levers, moves backwards the two rods which intercept the flow (outward and
return) of light oil to the nozzle. This moving backwards of the rods also determines a closing of the passage (by-
pass) inside the atomizer unit. Consequently, the pump pressure is taken to the normal value of about 20 ÷ 22 bar.
Deviation of the two rods the closing seat, now permits the fuel to enter the nozzle at the pressure at which the
pump has been regulated at (20 ÷ 22 bar), and comes out of the nozzle adequately atomized.
The return pressure, which determines delivery to the furnace, is regulated by the return pressure regulator.
The value of the ignition flow rate (minimum delivery) should be about 10 ÷ 12 bar.
The atomized light oil which comes out of the nozzle is mixed with air supplied by the fan and is then ignited by the
spark of the electrodes. Flame presence is detected by the photocell UV.
The programme proceeds and surpasses the “shut down” position, disconnects the ignition transformer and by
this point on the burner is operating at minimum output.
If the boiler thermostat (or pressure switch) of the 2nd stage allows it (regulated at a temperature or pressure value
superior to that existing in the boiler), the servomotor which regulates the delivery starts turning and determines a
gradual increase in the fuel delivery and in the relative combustion air until it reaches the maximum delivery value
at which the burner has been regulated. The increase in fuel delivery is determined by a disk with a varied profile
which, by rotating, can determine a greater compression of the return pressure regulator spring and thus an
increase in the pressure itself. When the return pressure increases, there is also a corresponding increase in fuel
delivery. There should also be an adequate increase in combustion air to meet the increase in fuel delivery.
Adjustment can be carried out at first regulation by operating the screws which vary the profile of the commend
disk of the combustion air regulator.

Control box

& relative

Programmer

LFL 1.333

Cyclic relay

Safety

time in

seconds

3

Pre-Ventilation &

Oil Pre-circulation

Time

in seconds

31,5

Pre-ignition

Time

in seconds

6

Post-ignition

Time

in seconds

3

Time between

1st flame & Start

of Modulation

in seconds

12

Summary of Contents for COMIST 122 DSPGM

Page 1: ...DSPGM en The works on the burner and on the system have to be carried out only by competent people Read carefully the instructions before starting the burner and service it The system electric feeding...

Page 2: ...de linea gas certificados CE suministrables a pedido NOTA la presente declaraci n no tiene validez respecto a la Norma CE o UNI para los quemadores de gas y para la parte de gas de los quemadores mixt...

Page 3: ...ACCESSORIES MATERIAL EN DOTACI N STANDARDZUBEH R FLANGIA ATTACCO BRUCIAT BURNER FIXING FLANGE BRIDA UNI N BEFESTIGUNGSFLANSCH 2 2 COLLAREELASTICO ELASTIC COLLAR COLLAR N EL STICO FEDER 1 1 GUARNIZIONE...

Page 4: ...s pressure switch min 5 Gas pressure switch max 6 Gas pressure switch max 7 Butterfly 8 Pilot main valve 9 Hinge 10 Main valve 11 Regulation valve return pressure 12 Safety valve 14 Electric board 15...

Page 5: ...iones N 0002570030 Rev A A1 A2 B B1 B2 B3 C D E F G L M N MIN MAX COMIST 72 DSPGM 670 400 270 810 375 435 265 1410 185 445 227 220 2 240 M16 240 COMIST 122 DSPGM 830 460 370 1170 455 715 1500 195 455...

Page 6: ...ERIALE A CORREDO STANDARD ACCESSORIES MATERIAL EN DOTACI N STANDARDZUBEH R FLANGIA ATTACCO BRUCIAT BURNER FIXING FLANGE BRIDA UNI N BEFESTIGUNGSFLANSCH 1 1 1 1 1 GUARNIZIONEISOLANTE INSULATING GASKET...

Page 7: ...Pilot main valve 9 Pilot safety valve 10 Main valve 11 Regulation valve return pressure 12 Safety valve 14 Electric board 15 Pump motore 16 Combustion head air control knob 17 Burner fixing flange 18...

Page 8: ...M N min max min max COMIST 180 DSP GM 875 460 415 1225 510 715 1725 330 520 260 245 2 1 2G 400 400 M 20 300 COMIST 250 DSP GM1075 540 535 1300 580 720 1750 320 500 320 273 3 G 490 490 M 20 340 COMIST...

Page 9: ...9 COMIST 36 72 122 N 8187 1 Rev COMIST 180 250 300 N 8111 2 Rev...

Page 10: ...10 DRAWING SHOWING THE GAS TRAIN ASSEMBLY COMIST 72 MG DSPGM N 8805 Rev DRAWING SHOWING THE GAS TRAIN ASSEMBLY COMIST 122 180 250 300 MG DSPGM DSPNM N 8797 Rev...

Page 11: ...that the inner faces are parallel between them Since the locking system is highly efficient do not tighten the nuts too much During this operation tightening of the flange locking nuts keep the body...

Page 12: ...o avoid big drops in pressure on ignition the length of the pipeline between the point where the stabilizer or reducer is fitted and the burner should be from 1 5 to 2 m This pipe must have a diameter...

Page 13: ...13 FLOW m3 h METHANE GAS d 0 85 IN COMMERCIAL GAS PIPES UNI 3824 68 LOAD LOSS MAX 5 mm W C N BT 1387 VIRTUAL LENGTH IN METERS FLOW m 3 h...

Page 14: ...e to accurately regulate the delivery and therefore the combustion and thus improve yield The dimension of the gas pipeline should be in function with the quantity of gas it has to deliver We advise m...

Page 15: ...vibration joint 11 A couple of flane D Distance between pressure stabilizer and valve about 1 5 2 m DIAGRAM OF CONNECTING A BURNER TO THE GAS PIPE NETWORK AT AVERAGE PRESSURE N BT 8531 1 1 Measuring...

Page 16: ...l feed pressure at the burner pump 0 2 1 bar should not vary when the burner is at a standstill or when it is operating at the maximum fuel delivery required by the boiler Normally it is possible to r...

Page 17: ...the burner s pump 1 Main cictern 2 Filter 3 Circulation pump 4 Water and system drain 6 Fuel recovery and degasifier 7 One way valve 8 By pass usually closed 9 Feeding circuit presure regulator adjust...

Page 18: ...trodes primes the electric spark for ignition of the fuel air mixture After the insertion spark appears the control box carries voltage to the magnet which by means of appropriate levers moves backwar...

Page 19: ...G OPERATIONS WITH LIGHT OIL COMIST MM See BT 8714 2 The burner s control box cyclic relay is connected by operating panel switch I Control box specifications The cyclic relay control box carries out t...

Page 20: ...rews which vary the profile of the commend disk of the combustion air regulator Fuel and combustion air delivery both increase at the same time until they reach maximum value light oil pressure at the...

Page 21: ...SSURE GAUGE 0 40 BAR 4 ATOMIZER UNIT 5 RETURN NOZZLE WITHOUT PIN 6 ROD WITH CLOSING PINS 7 BY PASS HOLES 8 CLOUSING SPRING 9 OPENING ELECTROMAGNET 10 RETURN PRESSURE REGULATOR MIN 10 12 BAR MAX 18 20...

Page 22: ...22 N 0002900580 BALTUR PUMP...

Page 23: ...the relative combustion air until it reaches the maximum delivery value at which the burner has been regulated N B The V cam of the servomotor regulating air gas delivery see BT 8562 1 inserts almost...

Page 24: ...e which in turn opens completely Gas delivery is not determined by the principle valve but by the position of the gas delivery regulation valve see BT 8816 1 and BT 8813 1 The burner remains in the ma...

Page 25: ...lation shutter 15 Ignition flame valve pilot with delivery regulator D Distance between pressure stabilizer and flange about 1 5 2 m DIAGRAM FOR MODULATING OR TWO STAGE PROGRESSIVE GAS AND DUAL FUEL B...

Page 26: ...16 1 DETAILS ON THE REGULATION OF GAS DELIVERY IN MODULATING BURNERS WITH THROTTLE VALVE COMIST 180 250 300 DSPGM DSPNM N BT 8813 1 The notch shown on the end of the shaft indicates the position pf th...

Page 27: ...out air bubbles and then re close the gate valve 11 Insert a manometer end of the scale about 3 bar into the vacuumeter connection point on the pump and control the value of the pressure at which the...

Page 28: ...ater in the system should be at the right temperature and the burner should have been operating for at least 15 minutes If the appropriate instruments are not available judgement can be based on the c...

Page 29: ...p the burner and make a first adjustment as previously described When maximum delivery desired has been reached proceed with correcting the position of the combustion head move it backwards and forwar...

Page 30: ...ion air regulation shutter must not be modified in such a case it will be necessary to adjust the gas flow to the amount of air already adjusted for the light oil operation If the burner is started up...

Page 31: ...indication for methane gas the percentage should be from at least 8 at minimum burner delivery to an optimum value of 10 for maximum delivery We advise against exceeding the value of 10 to avoid oper...

Page 32: ...topping the burner functioning when the gas pressure is not within the values specified From the specific functions of the pressure switches it is evident that the pressure switch which controls the m...

Page 33: ...ds and forwards in such a way as to obtain an air flow suitable for the light oil delivery with the air regulation shutter in suction considerably open It the combustion head is pushed forwards which...

Page 34: ...e burner to operate for a long time only a few minutes if the output exceeds the maximum allowed for the boiler to avoid possible damage to it it would be timely to stop the burner immediately after h...

Page 35: ...ng Principle feed valve s B Insertion and disinsertion lever Motor connection camshaft Position 1 Disinsertion Position 2 Insertion To modify the regulation of the cams utilized operate the respective...

Page 36: ...e will not be sufficient supply for ignition if the flow feed device E is set at its minimum position Therefore it is essential to open the maximum flow rate control device E sufficiently to ensure ig...

Page 37: ...the open position while the pump and magnetic valve remain powered When the unit receives the signal to close or if power supply is cut off the pump shuts down the magnetic valve opens decompressing...

Page 38: ...opening and closing The VE4000B1 valves are Class A solenoid valves normally closed They may be used as ON OFF valves in the supply trains with Natural Gas Manufactured Gas or GPL on burners or combus...

Page 39: ...tolerated post combustion period The tests will end only at the end of the pre ventilation time of the next start up The validity of working of the flame control circuit is checked each time the burne...

Page 40: ...r fan or burner NTC NTC resistor QRA UV probe R Thermostat or pressure probe RV Fuel valve with continuous regulation S Fuse SA Air damper servomotor SB Safety limiter temperature pressure etc SM Prog...

Page 41: ...power regulator or at valve on terminal 20 18 t6 Post ventilation time with M2 3 t7 Time between consensus for start up and voltage at terminal 7 start delay for fan motor M2 72 t8 Start up duration w...

Page 42: ...z of the air damper servo motor During the probe test and false flame test the flame supervision test is also powered terminals 22 23 and 22 24 Safety standards In association with the use of QRA eart...

Page 43: ...ignal was not sent to terminal 8 by limit switch contact a Terminals 6 7 and 15 remain powered until the defect is eliminated P Lock out stop because of lack of air pressure signal Any lack of pressur...

Page 44: ...During the second verification stage this pressure must remain constant Should it drop this means that the burner on the furnace side has a blow by fault when closing Therefore the DW pressure switch...

Page 45: ...gramme t4 5s Putting control circuit under atmospheric pressure t6 7 5s Time between start up and energizing of main AR relay t1 22 5s 1st verification stage at atmospheric pressure t3 5s Putting cont...

Page 46: ......

Page 47: ......

Page 48: ......

Page 49: ......

Page 50: ......

Page 51: ......

Page 52: ......

Page 53: ......

Page 54: ......

Page 55: ......

Page 56: ......

Page 57: ......

Page 58: ......

Page 59: ......

Page 60: ......

Page 61: ......

Page 62: ......

Page 63: ......

Page 64: ......

Page 65: ......

Page 66: ......

Page 67: ......

Page 68: ......

Page 69: ......

Page 70: ...7 11 Fax 051 685 75 27 28 International Tel 39 051 684 37 1 1 Fax 39 051 683 06 86 http www baltur it http www baltur com E MAIL info baltur it Technical data in this brochure are given as information...

Reviews: