baltur BTG 3 Instruction Manual For Use Download Page 40

16 / 22

0006080742_201306

ENGLISH

The gas valve unit 

DUNGS MB - DLE...

 is made up of:

•  A safety valve which closes opens rapidly. 
•  A principle valve which opens in two stage (5). The first opening 

stage occurs rapidly (release) and is adjustable by unscrewing 

the knob (2) and inserting the back part of the regulating pin 

underneath. The + and symbol can be seen on the head of the 

valve and these indicate the direction in which the pin should 

be turned in order to increase or the ignition output (the first 

stage of the valve opening). By rotating in a clockwise direction, 

the initial delivery (ignition flame) can be reduced; in an anti-

clockwise direction, the initial delivery is increased. The complete 

run from zero to maximum, and viceversa, is slightly more than 

three turns (40% of the total opening). When the first opening 

stage has taken place, the valve comtinues to open slowly 

and takes 15 seconds to reach the maximumopen position. To 

regulate maximum delivery desired, loosen the locking screw 

(4) (the one with the protruding head and not the one locked 

and sealed with paint) and turn knob (3). Rotate in a clockwise 

direction to reduce delivery and in anti-clockwise direction to 

increase it. It should be pointed out that when the regulating 

knob is turned, the end - of - the - run which limits the operating 

of the valve moves; therefore, when the knob has been turned 

untilit reaches the - sign, the valve will not open and the burner 

will not ignite. To get ignition, it’s necessary to turn the knob in 

an anti-clockwise direction towards the + sign. The complete 

run from zero to maximum and viceversa is neary six turns of 

the knob. This regulating operation (for maximum and ignition 

output) must be carried out without forcing against the end - of 

- the - run - positions.

•  The pressure stabilizer (10) can be regulated (see table) by 

manoeuvring the screw which can be reached by sliding the 

cover (1) to one side. The complete run from the maximum to 

the position and viceversais about 80 turns. Do not force against 

the end - of - the - run positions. Around the screw are arrows 

with symbols which indicate the sense of rotation: to increase 

pressure, rotate in a clockwise direction, to reduce it, rotate in 

an anti-clockwise direction. This stabilizer hermetically closes 

“upstream” and “downstream” when there is no flow of gas. 

Dfferent springs to obtain different pressure value from those 

described above are not foreseen. 

to regulate the pressure 

stabilizer, connect a water manometer to the rubber tube 

holder installed on the tap (8) in correspondence with the 

exit of the stabilizer.

•  The small entry filter (12) can be reached for cleaning by 

removing one of the two side closing plates.

•  The minimum pressure switch (14). To regulate it remove the 

transparent cover and operate the black knob. The reference 

mark is the small rectangle to be found on the yellow disk which 

the regulating knob rotates around.

VALVE MODEL

INLET MAX PRESSURE (PE)  

mbar

ADJUSTTABLE OUTLET PRESSURE 

FROM THE STABILIZER (PA) mbar

TYPE OF GAS

MB ...403 B01 S 20

200

from 4 to 20

Natural gas / L.P.G.

MB ...  ....  B01 S 20

360

from 4 to 20

Natural gas / L.P.G.

•  At entry, a tap (13) has been fitted to the connction flange to 

measure the entry pressure. At the exit of the connection flange, 

there is also a tap (7) to measure the pressure in exit.

•  The side pressure taps (9), indicated as Pe, are in communication 

with the entry pressure.

•  The side pressure taps (8) indicated as Pa, are used to  measure 

the pressure coming out of the stabilizer. It might be useful to 

know, that the pressure coming out of the valve unit (to be 

measured at tap 7), corrisponds to the pressure regulated by 

the stabilizer and is reduced in order to overcome the crossing 

resistance of the principle valve (5). It should be pointed out, 

that the valve crossing resistances depend on the opening of 

the valve regulated by knob 3 through wjich the end - of - the - 

run position is adjusted. 

to regulate the pressure stabilizer, 

connct  a  water  manometer  to  the  rubben  tube  holder 

installed on tap (8) in correspondence to the stabilizer 

exit (pa).

•  The holes of the pressure stabilizer bleed (11) should be free and 

unblocked if it’s to function properly.

SUggeStIonS for regULatIng 

tHe gaS VaLVe

•  Connect a water manometer to the pressure tap Pa (indicated 

as n° 8) to measure the pressure coming out of he stabilizer.

•  Put the gas delivery  regulators for ignition (2) and for maximum 

delivery (3) in the positions presumed necessary for the delivery 

desired. Also open adequately the combustion air regulator.

•  Turn on the burner.
•  With the burner on, manoeuvre the regulating screw (1) of the 

stabilizer regulator of the gas pressure and regulator of the gas 

pressure and regulate the pressure at the value considered 

necessary to obtain the output desired, when the maximum 

output regulator (3) is in the maximum opening position. It should 

be pointed out that, normally, the above conditions require about 

40 ÷ 70 mm.W.C.

•  Put the ignition output regulator (2) in the position considered 

necessary to obtain ignition with the minimum delivery possible.

Summary of Contents for BTG 3

Page 1: ...IONS ARE IT INSTRUCCIONES ORIGINALES IT ISTRUCTIONS ORIGINALES IT 0006080742_201306 EN SP FR Notice d instructions Manual de instrucciones Instruction manual for use BRUCIATORI DI GAS MONOSTADIO sigle...

Page 2: ......

Page 3: ...ti pericolosi BALTUR S p A Via Ferrarese 10 44042 CENTO Ferrara ITALIA Tel 051 684 37 11 Fax 051 685 75 27 28 International Tel 39 051 684 37 11 Fax 39 051 683 06 86 http www baltur it http www baltur...

Page 4: ...io assicurarsi sempre che il libretto accompagni l apparecchio in modo che possa essere consultato dal nuovo proprietario e o dall installatore Per tutti gli apparecchi con optionals o kit compresi qu...

Page 5: ...combustibile onde rimuovere eventuali residui che potrebbero compromettere il buon funzionamento del bruciatore Per la prima messa in funzione dell apparecchio far effettuare da personale professiona...

Page 6: ...ZIONAMENTO 8 ACCENSIONE E REGOLAZIONE A GAS METANO 8 REGOLAZIONE ARIA SULLA TESTA DI COMBUSTIONE 10 MANUTENZIONE 11 APPARECCHIATURA DI COMANDO E CONTROLLO bRUCIATORI A GAS LME 12 VALVOLE GAS 15 PRECIS...

Page 7: ...MOTORE VENTOLA kW r p m 0 09 2800 TRASFORMATORE D ACCENSIONE 15kV 25mA Gas naturale PORTATA MIN m n h 1 7 MAX m n h 4 3 PRESSIONE MIN mbar 12 G P L PORTATA MIN m n h 0 6 MAX m n h 1 6 PRESSIONE MIN m...

Page 8: ...o testa 2 Vite di regolazione apertura serranda aria 3 Connettore 7 poli 4 Apparecchiatura 5 Testa di combustione 6 Guarnizione isolante 7 Flangia attacco bruciatore 8 Elettrovalvola gas 9 Pressostato...

Page 9: ...ato solo il rubinetto di intercettazione e giunto antivibrante Solo nel caso in cui la pressione del gas fosse superiore al valore massimo ammesso delle Norme 400 mm C A occorre installare sulla tubaz...

Page 10: ...siano correttamente eseguiti come da nostro schema elettrico Aprire della quantit che si presume necessaria il regolatore dell aria di combustione vedi 0002931131 e aprire di circa un terzo il passagg...

Page 11: ...rificare che i valori della CO2 e del CO siano adeguati CO2 max circa 10 per metano e CO 0 1 Controllare l efficienza dei dispositivi di sicurezza blocco staccando il cavo dell elettrodo di ionizzazio...

Page 12: ...ede a correggere la posizione del dispositivo che chiude l aria sulla testa di combustione spostandolo in avanti o in dietro in modo SCHEMA REGOLAZIONE ARIA SULLA TESTA DI COMBUSTIONE E DISPOSIZIONE D...

Page 13: ...ggio di centrare esattamente gli elettrodi quello di accensione e quello di rilevazione fiamma per evitare che gli stessi si trovino a massa con conseguente bloccaggio del bruciatore REGOLAZIONE COMBU...

Page 14: ...no riepilogate le sequenze dei colori ed il loro significato Per attivare la funzione di diagnosi premere per almeno 3 sec il pulsante di sblocco un lampegg o veloce di colore rosso indicher che la fu...

Page 15: ...e ottica AL al morsetto 10 Possibile cause 2 lampeggi On Assenza del segnale di fiamma alla fine del tempo di sicurezza TSA Malfunzionamento valvole combustibile Malfunzionamento rilevatore fiamma Dif...

Page 16: ...stato di limiti di sicurezza Si Fusibile esterno t Tempo W Termostato di Limiti Pressostato Z Trasformatore dell accensione ZV Valvola a gas pilota A Comando di Avvio accensione da R B B Intervallo pe...

Page 17: ...vola di sicurezza rapida 7 Presa di pressione controllo pressione uscita valvola senso del flusso collegamenti elettrici flangia entrata flangia uscita tappo VALVOLA GAS COMBINATA monoblocco DUNGS mod...

Page 18: ...installato alla presa 8 corrispondente all uscita dello stabilizzatore Pa Filtrino di ingresso 12 accessibile per la pulizia asportando una delle due piastrine laterali di chiusura Pressostato 14 di m...

Page 19: ...r poter variare la portata di gas bisogna agire sul regolatore A mediante chiave esagonale da 8 mm oppure chiave per esagono incassato da 4 mm Ruotando in senso orario si ottiene la riduzione di porta...

Page 20: ...nte vigenti del luogo L utilizzo del gas liquido G P L bruciatore e o caldaia pu avvenire solo in locali fuori terra e attestati verso spazi liberi Non sono ammesse installazioni che utilizzano il gas...

Page 21: ...seguire la regolazione del pressostato aria dopo aver effettuato tutte le altre regolazioni del bruciatore con il pressostato aria regolato a inizio scala Con il bruciatore funzionante alla potenza ri...

Page 22: ...tura e il funzionamento del pressostato aria Il bruciatore si avvia si ha formazione della fiamma quindi va in blocco Mancata o insufficiente rivelazione della fiamma da parte dell elettrodo di contro...

Page 23: ...ELETTRICO COLLEGAMENTI ELETTRICI Le linee elettriche devono essere convenientemente distanziate dalle parti calde E consigliabile che tutti i collegamenti siano eseguiti con filo eletrico flessibile S...

Page 24: ...22 22 0006080742_201306 ITALIANO...

Page 25: ...A Tel 051 684 37 11 Fax 051 685 75 27 28 International Tel 39 051 684 37 11 Fax 39 051 683 06 86 http www baltur it http www baltur com E MAIL info baltur it 18 11 2010 Declaration of Conformity We de...

Page 26: ...ER 7 DESCRIPTION OF OPERATIONS 8 NATURAL GAS STARTING UP AND REGULATION 8 AIR REGULATION ON THE COMBUSTION HEAD 10 MAINTENANCE 11 GAS BURNER CONTROL DEVICE GAS LME 12 GAS VALVES 15 SPECIFICATIONS FOR...

Page 27: ...or if the owner moves and leaves the equipment make sure that the booklet always goes with the equipment so it can be consulted by the new owner and or installer For all equipment with optionals or ki...

Page 28: ...t oIL or otHer fUeL SUppLIeS General warning notes Installation of the burner must be carried out by qualified technicians and in compliance with current law and regulations since incorrect installati...

Page 29: ...EUR MOTOR kW r p m 0 09 2800 IGNITION TRANSFORMER 15kV 25mA Natural Gas FLOW RATE MIN m n h 1 7 MAX m n h 4 3 PRESSURE MIN mbar 12 L P G FLOW RATE MIN m n h 0 6 MAX m n h 1 6 PRESSURE MIN mbar 30 BTG...

Page 30: ...on reference 2 Adjustable screw for air damper opening 3 7 pole connector 4 Control box 5 Combustion head 6 Insulating gasket 7 Burner mounting flange 8 Gas electrovalve 9 Air pressure switch 10 Motor...

Page 31: ...o flange boiler and fasten to screw A with nut C The DUNGS mod MB valve in cor porates a filter and a gas pressure stabilizer and therefore only a cut off cock and an anti vibration joint have to be f...

Page 32: ...ually regulated At first ignition successive shut downs could occur due to the following reasons The gas pipeline has not been adequately purged of air and therefore the quantity of gas is not suffici...

Page 33: ...be inserted the burner remains at as standstill It must be specified that if the contact is not closed during working the control box will carry out its cycle but the ignition transformer will not be...

Page 34: ...stion head move it backwards or forwards in such a way as to obtain an air flow suitable to the delivery with the air regulation shutter in suction considerably open When reducing the air passage on t...

Page 35: ...ing to earth or short circuiting which would result in the shut down of the burner COMBUSTION ADJUSTMENTS N B The figures given in the table are indicative only Optimum burner performance is obtained...

Page 36: ...transparent cover of the lockout reset button There are 2 diagnostics choices 1 Visual diagnostics Operational status indication or diagnostics of the cause of fault 2 Interface diagnostics With the...

Page 37: ...nks llllllll On Free 9 blinks lllllllll On Free 10 blinks llllllllll Off Wiring error or internal error output contacts other faults During the time the cause of fault is diagnosed the control outputs...

Page 38: ...ssurestat RV Gas regulation damper SA Actuator SQN SB Safety limiter STB Safety limit thermostat Si External pre fuse t Time W Limit thermostat pressure switch Z Ignition transformer ZV Pilot gas valv...

Page 39: ...nob 5 Principle valve 2 stage opening 6 Safety valve rapid 7 Pressure tap to control pressure in exit from valve 8 Pressure tap to control pressure in exit from stabilizer Pa flow direction electrical...

Page 40: ...ate the pressure stabilizer connect a water manometer to the rubber tube holder installed on the tap 8 in correspondence with the exit of the stabilizer The small entry filter 12 can be reached for cl...

Page 41: ...gonal wrench turn the regulator clockwise to reduce the release time and counter clockwise to increase it BRAHMA SOLENOID VALVE MOD EG 12 and E6G FOR GAS BURNERS LOW PRESSURE The symbol EG 12 S E6G no...

Page 42: ...ons using liquid gas are not allowed in underground or semi underground premises Premises where liquid gas is used must have ventilation openings which cannot be closed on their outside walls with a s...

Page 43: ...ulate the air pressure switch after first carrying out all the other burner adjustments with the air pressure switch adjusted to the start of the scale With the burner operating at the requested power...

Page 44: ...ROBABLE CAUSE RIMEDY The burner does not start Lack of currente Gasdoesnotreachtheburner Check the fuses of the feed line Check the fuses of the control box Check the line of the thermostats and the g...

Page 45: ...NGLISH ELECTRIC DIAGRAM ELECTRIC CONNECTIONS The electrical lines should be at an adeguate distance from hot parts It is advisable to make all the connections with flexible elecric wire Conductor s mi...

Page 46: ...22 22 0006080742_201306 ENGLISH...

Page 47: ...an accidentes peligrosos BALTUR S p A Via Ferrarese 10 44042 CENTO Ferrara ITALIA Tel 051 684 37 11 Fax 051 685 75 27 28 International Tel 39 051 684 37 11 Fax 39 051 683 06 86 http www baltur it http...

Page 48: ...ENCENDIDO Y REGULACI N CON GAS METANO 8 REGULACI N DEL AIRE EN LA CABEZA DE COMBUSTI N 10 MANTENIMIENTO 11 EQUIPO DE MANDO Y CONTROL PARA QUEMADORES DE GAS LME 12 V LVULAS DEL GAS 15 MATIZACIONES SOB...

Page 49: ...bro de instruccionesest siempreconelaparatoparaquepuedaserconsultado por el nuevo propietario y o instalador Para todos los aparatos con elementos opcionales o kits incluidos los el ctricos hay que ut...

Page 50: ...os de la instalaci n de abastecimiento del combustible para evitar posibles residuos que podr an comprometer el buen funciona miento del quemador La primera vez que se pone en funcionamiento el aparat...

Page 51: ...TOR DEL VENTILADOR kW r p m 0 09 2800 TRANSFORMADOR DE ENCENDIDO 15kV 25mA Gas natural CAUDAL M N m n h 1 7 M X m n h 4 3 PRESI N M N mbar 12 G P L CAUDAL M N m n h 0 6 M X m n h 1 6 PRESI N M N mbar...

Page 52: ...ornillo de regulaci n de la apertura de la clapeta del aire 3 Conector de 7 polos 4 Equipo 5 Cabezal de combusti n 6 Junta aislante 7 Brida de uni n al quemador 8 Electrov lvula del gas 9 Presostato d...

Page 53: ...o la llave de interceptaci n y la junta antivibrante Solo en el caso de que la presi n del gas fuese superior al valor m ximo admitido por las Normas 400 mm C A es necesario instalar en la tuber a del...

Page 54: ...l nea principal est n preparadas para el valor de tensi n disponible Abrir en la cantidad que se presume necesaria el regulador de aire de combusti n v ase 0002931131 y abrir aproximadamente un tercio...

Page 55: ...ico potencia de la caldera obviamente es necesario verificar tambi n que los valores de la CO2 y del CO sean adecuados CO2 m x aproximadamente 10 para metano y CO 0 1 Controlar la eficiencia de los di...

Page 56: ...de aire en el cabezal de combusti n desplaz ndolo hacia adelante o hacia atr s para conseguir un flujo de aire adecuado para el suministro con la clapeta de regulaci n del aire en posici n ligerament...

Page 57: ...te los electrodos el de encendido y el de detecci n de llama para evitar que hagan contacto provocando el consiguiente bloqueo del quemador REGULACI N DE LA COMBUSTI N Potencia t rmica kW Presi n de l...

Page 58: ...cias de los colores y su significado Para activar la funci n de diagn stico pulsar durante al menos 3 s el bot n de desbloqueo un parpadeo r pido de color rojo indicar que la funci n est activa v ase...

Page 59: ...de desbloqueo Indicaci n ptica AL en el borne 10 Posibles causas 2 parpadeos On No hay presencia de llama al finalizar el TSA tiempo de seguridad en el encendido V lvulas de combustible defectuosas o...

Page 60: ...de l mites de seguridad Si Fusible externo t Tiempo W Termostato de L mites Pres stato Z Transformador de encendido ZV V lvula a gas piloto A Control de Encendido encendido por R B B Intervalo para la...

Page 61: ...a de seguridad r pida 7 Toma de presi n control de la presi n de salida de la sentido del flujo conexiones el ctricas brida de entrada brida de salida tap n V LVULA DE GAS COMBINADA monobloque DUNGS m...

Page 62: ...dor de presi n conectar el man metro de agua al portagomas instalado en en la toma 8 correspondiente a la salida del estabilizador Pa Filtro de entrada 12 accesible para la limpieza quitando una de la...

Page 63: ...dal Para poder variar el caudal de gas es necesario accionar el regulador A mediante una llave hexagonal de 8 mm o una llave para hex gono encajado de 4 mm Gir ndolo en sentido horario se logra la dis...

Page 64: ...r La utilizaci n del gas l quido GPL quemador y o caldera puede realizarse s lo en locales desenterrados y con orientaci n hacia espacios libres No est n permitidas instalaciones que utilicen gas l qu...

Page 65: ...a cabo la regulaci n del pres stato del aire tras haber efectuado las dem s regulaciones del quemador con el pres stato del aire regulado al principio de la escala Mientras el quemador funciona a la p...

Page 66: ...to del aire El quemador se enciende se crea la llama luego se bloquea Falta de detecci n o detecci n insuficiente de la llama por parte del electrodo de control Controlar la colocaci n del electrodo d...

Page 67: ...CTRICO CONEXIONES EL CTRICAS Las l neas el ctricas se deben colocar oportunamente lejos de las piezas calientes Es aconsejable que todas las conexiones sean efectuadas con cable el ctrico flexible Se...

Page 68: ...22 22 0006080742_201306 ESPA OL...

Page 69: ...lite de causer de dangereux incidents BALTUR S p A Via Ferrarese 10 44042 CENTO Ferrara ITALIA Tel 051 684 37 11 Fax 051 685 75 27 28 International Tel 39 051 684 37 11 Fax 39 051 683 06 86 http www b...

Page 70: ...T 8 ALLUMAGE ET REGLAGE POUR LE GAZ NATUREL 8 R GLAGE DE L AIR SUR LA T TE DE COMBUSTION 10 ENTRETIEN 11 APPAREILLAGES DE COMMANDE ET DE CONTR LE DES BR LEURS GAZ LME 12 VANNES DU GAZ 15 PRECISIONS CO...

Page 71: ...r ce dernier toujours v rifier que la notice accom pagne l appareil afin qu il puisse tre consulter par le nouveau propri taire et ou par l installateur Pour tous les appareils avec options ou kit y c...

Page 72: ...es tuyaux d arriv e du combustible afin d liminer les ventuels r sidus susceptibles de compromettre le bon fonctionnement du br leur Lors de la premi re mise en service de l appareil faire effectuer l...

Page 73: ...50Hz 230V MOTEUR VENTILATEUR kW r p m 0 09 2800 TRASFORMATEUR D ALLUMAGE 15kV 25mA Gaz Naturel DEBIT MIN m n h 1 7 MAX m n h 4 3 PRESSION MIN mbar 12 G P L DEBIT MIN m n h 0 6 MAX m n h 1 6 PRESSION M...

Page 74: ...n disque t te 2 Vis de r glage ouverture clapet d air 3 Connecteur 7 p les 4 Appareillage 5 T te de combustion 6 Joint isolant 7 Bride de fixation du br leur 8 lectrovanne du gaz 9 Pressostat d air 10...

Page 75: ...obinet de barrage et un joint anti vibrant sur ce tuyau Uniquement lorsque la pression du gaz est sup rieure la valeur maximum admise par les Normes 400 mm C E il est n cessaire d installer sur le tuy...

Page 76: ...t conform ment notre sch ma lectrique Ouvrir plus ou moins en fonction de la n cessit le r gulateur de l air de combustion voir 0002931131 et ouvrir d environ un tiers le passage de l air entre la t t...

Page 77: ...urs de CO2 et de CO soient correctes CO2 max environ 10 pour le gaz naturel et CO 0 1 Contr ler l efficacit des dispositifs de s curit blocage en d branchant le c ble de l lectrode de ionisation press...

Page 78: ...ion maximale souhait e est atteinte on corrige la position du dispositif qui ferme l air sur la t te de combustion en le d pla ant vers l avant ou vers l arri re de mani re obtenir un SCHEMA DE REGLAG...

Page 79: ...es lectrodes lectrode d allumage et lectrode de d tection de flamme afin d viter qu ils se trouvent la masse ou en court circuit avec pour cons quence un blocage du br leur REGLAGE DE LA COMBUSTION Pu...

Page 80: ...sont indiqu s dans le tableau ci apr s Pour activer la fonction de diagnostic appuyer pendant au moins 3 secondes sur le bouton poussoir de d blocage Un clignotement rapide de couleur rouge indiquera...

Page 81: ...de d blocage Indication optique AL la borne 10 Causes possibles 2 clignotements Allum Absence du signal de la flamme au terme du temps de s curit TSA Dysfonctionnement des vannes du combustible Dysfo...

Page 82: ...limites de s curit Si Fusible externe t Temps W Thermostat des Limites Pressostat Z Transformateur d allumage ZV Vanne pilote de gaz A Commande de D marrage allumage depuis R B B Intervalle pour la fo...

Page 83: ...x temps 6 Vanne de s curit rapide 7 Prise de pression contr le pression sortie vanne sens du flux connexions lectriques bride entr e bride sortie bouchon VANNE GAZ COMBINEE monobloc DUNGS mod MB DLE B...

Page 84: ...e pression autre que celles indiqu es Pour le r glage du stabilisateur de pression brancher le manom tre eau l embout install la prise 8 correspondant la sortie du stabilisateur Pa Filtre d entr e 12...

Page 85: ...NE EG12 AR EG 12 SR R glage du d bit Pour varier le d bit de gaz on doit agir sur le r gulateur A au moyen d une cl hexagonale de 8 mm ou d une cl six pans creux de 4 mm En tournant dans le sens horai...

Page 86: ...G P L br leur et ou chaudi re est possible uniquement dans des locaux hors de terre et dirig s vers des espaces libres Des installations utilisant du gaz liquide ne sont pas autoris s dans des locaux...

Page 87: ...AT D AIR Effectuer le r glage du pressostat de l air apr s avoir effectu tous les autres r glages du br leur avec le pressostat d air r gl au d but de l chelle Lorsque le br leur fonctionne la puissan...

Page 88: ...le fonctionnement du pressostat de l air Le br leur d marre il y a la formation de la flamme et puis le br leur se bloque D tection de flamme manqu e ou insuffisante de la part de l lectrode de contr...

Page 89: ...TRIQUE CONNEXIONS ELECTRIQUES Les lignes lectriques doivent tre une distance appropri e des parties chaudes Il est souhaitable que toutes les connexions soient ex cut es avec du fil lectrique flexible...

Page 90: ...22 22 0006080742_201306 FRAN AIS...

Page 91: ......

Page 92: ...ste carattere puramente indicativo La casa pertanto si riserva ogni possibilit di modifica dei dati tecnici e quant altro in esso riportato El presente cat logo tiene car cter puramente indicativo La...

Reviews: