FREQUENCY CONVERTER
Technical data
Ratings
Current and power
The current and power ratings are given below. The symbols are described below the table.
Type
Input
Output
Frame
size
ACS350-
x = E/U
I
1N
A
I
2N
A
I
2,1min/10min
A
I
2max
A
P
N
kW
HP
3-phase UN = 380...480 V
(380, 400, 415, 440, 460, 480 V)
03x-01A2-4
2.2
1.2
1.8
2.1
0.37
0.5
R0
03x-01A9-4
3.6
1.9
2.9
3.3
0.55
0.75
R0
03x-02A4-4
4.1
2.4
3.6
4.2
0.75
1
R1
03x-03A3-4
6.0
3.3
5.0
5.8
1.1
1.5
R1
03x-04A1-4
6.9
4.1
6.2
7.2
1.5
2
R1
03x-05A6-4
9.6
5.6
8.4
9.8
2.2
3
R1
03x-07A3-4
11.6
7.3
11.0
12.8
3
3
R1
03x-08A8-4
13.6
8.8
13.2
15.4
4
5
R1
03x-12A5-4
18.8
12.5
18.8
21.9
5.5
7.5
R3
03x-15A6-4
22.1
15.6
23.4
27.3
7.5
10
R3
Symbols
Input
I
1N
continuous rms input current Output
I
2N
continuous rms current. 50% overload is allowed for one minute every ten minutes.
I
2,1
min/10min
maximum (50% overload) current allowed for one minute every ten minutes
I
2
max
maximum output current. Available for two seconds at start, otherwise as long as allowed by
the drive temperature.
PN
typical motor power. The kilowatt ratings apply to most IEC 4-pole motors. The horsepower
ratings apply to most NEMA 4-pole motors.
3-phase UN = 380...480 V
(380, 400, 415, 440, 460, 480 V)
03x-01A2-4
10
gG
10
UL Class T
03x-01A9-4
10
gG
10
UL Class T
03x-02A4-4
10
gG
10
UL Class T
03x-03A3-4
10
gG
10
UL Class T
03x-04A1-4
16
gG
15
UL Class T
03x-05A6-4
16
gG
15
UL Class T
03x-07A3-4
16
gG
20
UL Class T
03x-08A8-4
20
gG
25
UL Class T
03x-12A5-4
25
gG
30
UL Class T
03x-15A6-4
35
gG
35
UL Class T
Power cable sizes and fuses
Cable dimensioning for rated currents (I1N) is shown in the table below together with the corresponding fuse types for short-
circuit protection of the input power cable. The rated fuse currents given in the table are the maxima for the mentioned fuse
types.
Check that the operating time of the fuse is below 0.5 seconds. The operating time depends on the fuse type, the supply network
impedance as well as the crosssectional area, material and length of the supply cable. In case the 0.5 seconds operating time is
exceeded with the gG or T fuses, ultra rapid (aR) fuses will in most cases reduce the operating time to an acceptable level.
Note: Larger fuses must not be used.