ENGLISH
14 / 32
0006160059_201511
ELECTRICAL CONNECTIONS
• It is advisable to make all connections with flexible electric wire.
•
Conductor minimum section must be 1.5 mm².
•
Electrical lines must be kept away from hot parts.
•
The burner installation is allowed only in environments with
pollution degree 2 as indicated in annex M of the EN 60335-
1:2008-07 regulation.
•
Make sure that the electric line to which the unit will be con-
nected has frequency and voltage ratings suitable for the bur-
ner.
•
The three-phase or single-phase power supply line must have
a switch with fuses. The standards also require a switch on the
burner's power line located outside the boiler room where it can
be accessed easily.
•
The main line, the relevant switch with fuses and the possible
limiter must be suitable to support the maximum current absor-
bed by the burner.
•
The mains supply connection requires an omnipolar switch with
a contact opening gap equal to or greater than 3 mm in accor-
dance with current safety regulations.
•
Refer to the wiring diagram for electrical connections (line and
thermostats).
•
Unsheathe the external insulating cover of the power cable to
the necessary extent for the connection, thus avoiding the wire
from coming into contact with metal parts.
Summary of Contents for 67190010
Page 2: ......
Page 30: ...ITALIANO 28 32 0006160059_201511 SCHEMI ELETTRICI ...
Page 31: ...ITALIANO 29 32 0006160059_201511 ...
Page 32: ...ITALIANO 30 32 0006160059_201511 ...
Page 33: ...ITALIANO 31 32 0006160059_201511 ...
Page 62: ...ENGLISH 28 32 0006160059_201511 WIRING DIAGRAMS ...
Page 63: ...ENGLISH 29 32 0006160059_201511 ...
Page 64: ...ENGLISH 30 32 0006160059_201511 ...
Page 65: ...ENGLISH 31 32 0006160059_201511 ...
Page 67: ......