WATER METER
The water meter should be installed in the make up line to the cooling towers
•
Adapters supplied by others. It is recommended to install insulating valve for easier maintenance.
•
Position the water meter with the arrow in the water flow direction
•
Flush the piping before installation, to prevent dirt to enter the water meter. Water meter should be protected
from freezing (protected room or insulation and tracing)
•
Make sure the water meter screen can be viewed and read at any time
Prestrainer should be cleaned on a yearly basis.
Water meter reading information
1.
1 rotation = 1L; 1 graduation = 0,1 L
2.
1 rotation = 10L; 1 graduation = 1 L
3.
1 rotation = 1m³; 1 graduation = 100 L
4.
1 rotation = 100L; 1 graduation = 10 L
Electrical Wiring
Refer to the wiring diagram of the submittal package.
The BCP3D is suitable for connection to networks of 110V - 230V and 50 - 60 Hz (AC POWER).
The BCP3D panel is pre-wired and only requires a main power supply to the controller BACT 600.
A general alarm output is also available as indicated on the wiring.
Wiring of the water meter to the controller BACT 600 (by others).
Optional when specified at order: Analogic output 4-20 mA for conductivity.