Assembly and disassembly
DANGER
Danger to life by electrical voltage
The supply cable may carry high electrical voltage that is fatal. Pay attention to the five safety rules of
electricity:
1. De-energise
2. Secure the supply from being switched on again
3. Ensure the de-energised condition
4. Connect to earth and short circuit
5. Cover or cordon off adjacent live parts
Connecting a conductor to a socket with multi-grip cable gland
QUICK-CONNECT connection
Proceed as follows:
1. Make sure that the cable is de-energised.
2. Depending on the design:
Open the rotary lock or loosen the screws in order to separate the front part from the housing.
3. Push the cable about 50 cm wide through the cable gland and housing.
4. Strip the cable to the required length (16A designs: 60 mm; 32 A designs: 70 mm).
5. Remove the insulation from the individual conductors (16 A designs: 9 mm; 32 A designs:
12 mm). Twist the multi-strand copper conductors slightly by hand. Conductor end sleeves are
not necessary but may be used.
6. The terminals are open at the time of delivery. Guide the bare individual conductors into the
opening near the contact slide (4) and press the contact slide (5) to the right (in the direction
of the arrow). The contact slide get latched and fixes the individual conductor. Take care to en-
sure that only the bare individual conductor (without insulation) is clamped. Pay attention to
the marking of the terminals and ensure that the assignment of the individual conductors to
the terminals is correct.
6
6.1
6.1.1
Installation manual phase inverter (16/32A)