Assembly and disassembly

 

 DANGER

Danger to life by electrical voltage

The supply cable may carry high electrical voltage that is fatal. Pay attention to the five safety rules of 

electricity:

 1. De-energise
  2.  Secure the supply from being switched on again
  3.  Ensure the de-energised condition
  4.  Connect to earth and short circuit
  5.  Cover or cordon off adjacent live parts

 

Connecting a conductor to a socket with multi-grip cable gland

QUICK-CONNECT connection

Proceed as follows:

  1.  Make sure that the cable is de-energised.
  2.  Depending on the design:  

Open the rotary lock or loosen the screws in order to separate the front part from the housing.

  3.  Push the cable about 50 cm wide through the cable gland and housing.
  4.  Strip the cable to the required length (16A designs: 60 mm; 32 A designs: 70 mm).
  5.  Remove the insulation from the individual conductors (16 A designs: 9 mm; 32 A designs: 

12 mm). Twist the multi-strand copper conductors slightly by hand. Conductor end sleeves are 

not necessary but may be used.

  6.  The terminals are open at the time of delivery. Guide the bare individual conductors into the 

opening near the contact slide (4) and press the contact slide (5) to the right (in the direction 

of the arrow). The contact slide get latched and fixes the individual conductor. Take care to en-

sure that only the bare individual conductor (without insulation) is clamped. Pay attention to 

the marking of the terminals and ensure that the assignment of the individual conductors to 

the terminals is correct.

6

6.1

6.1.1

Installation manual phase inverter (16/32A)

(08.2016) 

10 / 28

Summary of Contents for QuickConnect

Page 1: ...EN Installation manual phase inverter 16 32A 60003247 Issue 08 2016 2016 08 30...

Page 2: ...6 Assembly and disassembly 10 6 1 Connecting a conductor to a socket with multi grip cable gland 10 6 1 1 QUICK CONNECT connection 10 6 1 2 Screw terminal connection 12 6 2 Disconnecting a conductor...

Page 3: ...oduct and must be kept in safe custody during the product service life must be read carefully and understood before use and any work Structure of the warnings The following picture illustrates the str...

Page 4: ...arns of dangers that may lead to serious injuries or to death and or cause considerable damage to property if the instructions are not followed CAUTION Warns of dangers that may lead to reversible inj...

Page 5: ...r life and limb as well as damage to the plugs and sockets or loads connected Factory fitted labels and markings on the distributors should not be removed modified or blurred Protect against foreign b...

Page 6: ...the laws ordinances and standards Keep easily combustible and explosive materials away from the product Handle the cables with care by always pulling at the plug and not the cable when unplugging by p...

Page 7: ...acility If this is not possible dispose of the packag ing materials according to the locally applicable regulations Transport Check the delivery for completeness and integrity If you identify transit...

Page 8: ...lowing table displays the possible conductor cross sections that can be connected Design Possible conductor cross section QUICK CONNECT Screw terminals 16A 1 mm2 2 5 mm2 1 mm2 2 5 mm2 32A 2 5 mm2 10 m...

Page 9: ...Socket insert with connections for all types of copper Conductor cross sections The following table displays the possible conductor cross sections that can be connected Design Possible conductor cros...

Page 10: ...ugh the cable gland and housing 4 Strip the cable to the required length 16A designs 60 mm 32 A designs 70 mm 5 Remove the insulation from the individual conductors 16 A designs 9 mm 32 A designs 12 m...

Page 11: ...th the screws until the snap on lock 6 latches or fix the housing and front part together with the screws foreseen for this purpose 9 Next tighten the cable gland 3 The tightening torque must be betwe...

Page 12: ...Depending on the design Open the rotary lock or loosen the screws in order to separate the insert with the screw termi nals from the from the housing 3 Remove the insert with the screw terminal in fro...

Page 13: ...e of at least 0 8 Nm Take care to see that only the individual conductor without insulation is clamped Pay attention to the marking of the terminals and ensure that the assignment of the individual co...

Page 14: ...le gland 3 is secured with the help of a screw 8 loosen this screw 3 Loosen the cable gland 4 Disconnect the joint between the housing 2 and the front part 1 Depending on the design loosen the connect...

Page 15: ...ccessible 6 Open the contact slide 4 by sliding it to the right in the direction of the arrow and pull the individual conductors from the terminals 7 Pull the cable out of the housing and out of the c...

Page 16: ...open the snap on lock with the help of a screwdriver and remove the housing from the front part by unscrewing it 5 Push the housing and the cable gland back on the cable until the connections in the f...

Page 17: ...emove the insulation from the individual conductors 16 A designs 9 mm 32 A designs 12 mm Twist the multi strand copper conductors slightly by hand for flexible conductors Conductor end sleeves are not...

Page 18: ...e for the application 6 Push the cable through the sealing plugs 4 into the housing Open the sealing plugs only as far as necessary so that they can still get sealed Generally we recommend using a sep...

Page 19: ...ductors to the terminals is correct 8 Check whether the individual conductors are seated tightly by pulling them lightly If this is not the case open the terminal and repeat the previous step 9 For wa...

Page 20: ...evice connector Proceed as follows 1 Make sure that the cable is de energised 2 For wall mounted device connectors Loosen the two housing screws in order to open the housing 6 4 Installation manual ph...

Page 21: ...21 28 3 Loosen the screws 5 and pull out the individual conductors from the terminals 4 Pull out the cable from the housing and for wall mounted device connectors also out of the cable gland 4 5 Fix t...

Page 22: ...direction of rotation of the attached consumer to be changed Proceed as follows 1 Take a suitable screwdriver and push the phase inversion element inwards 2 Rotate the phase inversion element by 180 u...

Page 23: ...ectrical voltage The device contains parts that carry hazardous voltage that may be fatal 1 Pull out the connectors to the loads before cleaning them 2 Make sure that the connector covers are closed 3...

Page 24: ...proper disposal Always make sure to observe and fol low the local regulations The product should not be disposed of in household waste Environmental damage and risk to person al health are avoided wit...

Page 25: ...Installation manual phase inverter 16 32A 08 2016 25 28...

Page 26: ...Installation manual phase inverter 16 32A 08 2016 26 28...

Page 27: ...08 2016 27 28 Notes...

Page 28: ...Bals Elektrotechnik Kunshan Co Ltd 301 Add 301 Xiongying Road Kunshan Jiangsu Province Tel 86 512 86167886 111 Fax 86 512 86167880 Web http www bals com cn...

Reviews: