5.1
Installation
For dimensions, see Fig. 4-1 on page 8.
►
Fasten the module with 2 M6 screws and a maximum
tightening torque of 3 Nm using the mounting holes
5.2
Electrical connection
Requirements for complying with the protection
classes:
For IP68/IP69K, all plugs and caps must be properly
connected and the tightening torque of 0.6 Nm must be
observed (see data sheets of connectors and caps)
5.2.1 Power supply
NOTICE
Unwanted voltage dips
Non-separated electric circuits of the power supplies for
sensor and actuator can lead to unwanted voltage dips
of the sensor supply when switching actuators.
►
Fuse the power supplies for sensors and actuators
separately.
►
Make sure that the power supply of the device is
sufficiently dimensioned to cover start-up and peak
currents and design the fuse protection concept
accordingly.
– Establish power supply of sensor/bus and
actuator via a separate power source if possible.
– Due to the galvanic isolation of
BNI PNT-538-055-P067, devices without
galvanic isolation such as the
BNI PNT-508-055-P067 must not be supplied
with the same power source (see Tab. 5-1 and
Tab. 5-3).
– The total current for the sensor and actuator
supply must not exceed 16 A each.
– For UL: Observe cable requirements and power
supply requirements (see chapter 8.8.2 on
page 16)!
5
Installation and connection
M12 plug (L-coded)
M12 socket (L-coded)
Fig. 5-1: Top view of M12 plug (left) and socket (right)
Pin
Signal
Description
BNI
…-508-…
BNI
…-538-…
1
+ 24 V US
Module/sensor
voltage
2
GND UA
N24
1)
Actuator supply
3
GND US
1)
Sensor supply
4
+ 24 V UA
P24
Actuator supply
–
FE
Function ground
1)
GND: Pin 2 and pin 3 are galvanically isolated on variant
BNI PNT-538-055-P067
Tab. 5-1: Power supply pin assignment
5.2.2 PROFINET interface
Fig. 5-2: M12 socket, D-coded (top view of socket)
Pin
Signal
Description
1
Tx+
Transmit Data +
2
Rx+
Receive Data +
3
Tx−
Transmit Data −
4
Rx−
Receive Data −
Tab. 5-2: PROFINET interface pin assignment
BNI PNT-508-055-P067 / BNI PNT-538-055-P067
Network interface
Summary of Contents for PROFINET BNI PNT-508-055-P067
Page 2: ...www balluff com...
Page 3: ...BNI PNT 508 055 P067 BNI PNT 538 055 P067 Betriebsanleitung deutsch...
Page 4: ...www balluff com...
Page 19: ...BNI PNT 508 055 P067 BNI PNT 538 055 P067 User s Guide english...
Page 20: ...www balluff com...
Page 35: ...BNI PNT 508 055 P067 BNI PNT 538 055 P067 Notice d utilisation fran ais...
Page 36: ...www balluff com...
Page 51: ...BNI PNT 508 055 P067 BNI PNT 538 055 P067 Manuale d uso italiano...
Page 52: ...www balluff com...
Page 67: ...BNI PNT 508 055 P067 BNI PNT 538 055 P067 Instrukcja obs ugi polski...
Page 68: ...www balluff com...
Page 83: ......