32
english
5.4
Switching Profiles
5.4.1 Description
Sensor Principle / Evaluation Logic
The sensor performs measurement value acquisition as a
continuous signal that is evaluated for switching signal
generation. The measurement value is only evaluated if it is
within this valid measurement range. If the measurement
value is outside of this range, the output switches to
always active. For switching sensors, this value is
permanently defined according to the product. Evaluation
takes place based on the value
Transducer Signal
0xFFF7
(65527).
Switching points are defined by means of setpoints that
can be determined using various teach processes.
Alternatively, the setpoints can also be set directly via
ISDUs, but under observation of the same requirements
and rules as defined for the teach processes.
The setpoint setting can also be used to deactivate the
switching point evaluation. This is performed with the
No
Measurement Data
setting:
Status
Value
No Measurement Data (16 bit)
32.764 (0x7FFC)
(AdSS))
2.147.483.644
(0x7FFFFFFC)
(LSSC)
Measurement Range, Lower Limit
1000 (0x03E8)
Measurement Range, Upper Limit
4000 (0x0FA0)
Tab. 5-7: Switching Profiles – Deactivate switching point evaluation
Overview AdSS – Profile
– Only one switching channel (Switching Signal Channel
(SSC)) available.
– Only one switching point (setpoint) per switching
channel.
– Permanently defined hysteresis according to the
product.
– As switching mode, only the
Single Point Mode
is
available.
– The following teach commands are available:
Single
Value Teach
,
Two Value Teach
and
Dynamic Teach
(profile spec.).
5
Primary Device Functions (continued)
Overview of LSSC – Profile
– Multiple switching channels are possible (up to
4 channels currently supported).
– Two switching points (setpoints) per switching channel.
– Adjustable hysteresis.
– Multiple switching modes are possible:
Single-Point
Mode
,
Two-Point Mode
and
Window Mode
.
– The following teach commands are available for both
setpoint 1 and setpoint 2:
Single Value Teach
,
Two
Value Teach
and
Dynamic Teach
(profile spec. and
Balluff spec.).
Switchpoint Logic
With switching logic
High Active
, the switching output
switches to high if the current measurement value is
greater than the set (taught) setpoint. With
Low Active
this
logic is inverted.
High Active
Fig. 5-2:
High
SP1
Low
Measurement value
Switching output
Switchpoint logic
High Active
Low Active
Fig. 5-3:
High
SP1
Low
Measurement value
Switching output
Switchpoint logic
Low Active
BOS R254K-UUI-RH11-S4
Photoelectric Sensors
Summary of Contents for BOS R254K-UUI-RH11-S4
Page 1: ...deutsch Konfigurationsanleitung english Configuration Guide BOS R254K UUI RH11 S4...
Page 2: ...www balluff com...
Page 3: ...BOS R254K UUI RH11 S4 Konfigurationsanleitung deutsch...
Page 4: ...www balluff com...
Page 108: ......
Page 109: ...BOS R254K UUI RH11 S4 Configuration Guide english...
Page 110: ...www balluff com...