Mounting and
operating instructions
14
No. LED
Description
Factory setting
1
Q
A
V
N
C
QA
OK
FS
Set switching point for switching output Q:
Position the object at the desired switching point. The „OK“ LED must light.
Press
T
until the „Q“ LED lights.
Press
S
once. If the object is detectable and in the operating range, the
„ZA“ LED (red) flashes with 1 Hz.
Exit the Set menu (
T
+
S
) or
go to the next setting with the
T
button.
Set the switching window for switching output Q:
Position the object at the desired first switching window limit. The „OK“ LED
must light.
Press
T
until the „Q“ LED lights.
Press
S
once. If the object is detectable and in the operating range, the
„ZA“ LED (red) flashes with 1 Hz.
Position the object at the desired second switching window limit. The „OK“
LED must light.
Press
S
once. The distance is saved as the second switching window limit if
the object is detectable and in the operating range. The „ZA“ LED lights for
confirmation for as long as
S
is pressed.
Exit the Set menu (
T
+
S
) or
go to the next setting with the
T
button.
If the object was not moved after teaching the first switching window
limit, a minimum switching window (1% of the operating range) is laid
around the teach point.
Switching window
over the whole
operating range,
i.e. switching output
is active when the
object is in the
operating range and
reliably detected.
2
Q
A
V
N
C
QA
OK
FS
Scaling of the analogue output QA
Position the object at the desired 0% point (4mA). The „OK“ LED must light.
Press
T
until the „QA“ LED lights.
Press
S
once. If the object is detectable and in the operating range, the
distance is saved as the 0% point (4mA). The „ZA“ LED (red) flashes with
1 Hz.
If no 100% point is to be set, exit the Set menu (
T
+
S
) or go to the next
setting with
T
.
If a 100% point is to be set, place the object at the desired distance.
The „OK“ LED must light.
Press
S
once. If the object is detectable and in the operating range, the
distance is saved as the 100% point (20mA). The „ZA“ LED lights for confir
-
mation for as long as
S
is pressed.
Exit the Set menu (
T
+
S
) or
go to the next setting with the
T
button.
If the distance between the 0% point is less than 5% of the operating
range, the analogue output is automatically scaled to 5% of the max.
operating range. The middle of the range is placed between the set
0% and 100% points.
Maximum
operating range
6.4 Make settings
6.4.1 Activating the Set Mode (conf):
Press the buttons „S“ and „T“ simultaneously for 3 s (or longer) until the LED BA (green) flashes
(LED flashes when time lock open and Set mode activated).
6.4.2 Setting the Sensor