Time functions
Using IO-Link (parameter 0x00B8 and 0x00B9) a
switch-on and/or switch-off delay or a single pulse can be
assigned to the digital switching outputs. Possible times lie
between 0…65535 ms.
Switch-on delay
The switch-on point is output on the switching output with
a delay. The switch-off point is directly output on the
switching output.
Single pulse
Only the switch-on point is determinate. It is output directly
on the switching output, and the switching signal remains
in effect for the configured time.
Switch-off delay
The switch-off point is output on the switching output with
a delay. The switch-on point is output with no delay.
On/off delay
The switch-on and switch-off points are output on the
switching output with a delay.
Fig. 12:
Light received
Switch-on delay
Single pulse
switch-off delay
On/off delay
Light
No light
on
off
on
off
on
off
on
off
Overview of time functions
Applications for the time functions include for example
adjusting the length of the switching signal to the controller
or debouncing of the light reception signal.
Dark measurement
Enabling dark measurement (parameter 0x0421) makes
the sensor less sensitive to ambient light. Interference is
filtered out. The measurement does however take longer
and the switching frequency may be reduced.
Count function
In IO-Link mode parameter 0x00B6 can be used to
configure the count function. A preselected value is
specified (Limit). The counter begins with counter value 0.
Each time an object is detected by SSC1 the counter value
is incremented by 1. When the preselected value is
reached the counter output and process data bit
OK
are
set.
As soon as the count function is enabled Pin 4 in SIO
mode represents the counter output (always normally
open, output type remains configurable).
In IO-Link mode the process data bit
OK
is set as soon as
the preselected value is reached. The absolute counter
value is output with the process data.
If the counter value is less than the preselected value, the
process data bit
Too Low
is also set. If the counter value is
greater than the preselected value, the process data bit
Too High
is also set.
After turning the sensor on the counter value is always 0.
The counter can be reset in various ways:
– Counter Mode STATIC (with Reset command)
– Counter Mode AUTO (automatic Reset)
Counter Mode STATIC (with Reset command)
The counter value and counter output are reset by the
Reset signal.
In IO-Link mode therefore the Reset bit is set in the
process data.
For SIO mode Pin 2 must be configured as an input
(parameter 0x00BC). A High signal on the Reset input
resets the counter output.
The rising edge is always used. When there is a continuous
Reset signal the counter value and counter output are
reset only once.
Fig. 13:
Count pulses
RESET
Count Value
Counter output
on
off
Switch Counter Limit
Preselect counter with Reset command
A debounce time (parameter 0x00BA) between
0…65535 ms can be assigned to the Reset input.
Summary of Contents for BOD 21M-LBI05-S4
Page 1: ...deutsch Betriebsanleitung english User s guide fran ais Notice d utilisation BOD 21M LBI05 S4...
Page 2: ...www balluff com...
Page 3: ...BOD 21M LBI05 S4 Betriebsanleitung deutsch...
Page 25: ...BOD 21M LBI05 S4 User s Guide english...
Page 47: ...BOD 21M LBI05 S4 Notice d utilisation fran ais...
Page 69: ...www balluff com f r Notizen to make notes pour vos notes personelles...