Balluff BNI PNT-502-102-Z015 User Manual Download Page 15

www.balluff.com 

   

 

 

14 

Integration 

Hardware 
configuration 

  The IO-Link / standard I/O modules must now be configured appropriately for the 

configuration of the header module. 
If necessary, these can be taken over into the configuration table from the hardware catalog 
by means of drag & drop.  
By default, all ports are set to Standard I/O.  
If the port is to be configured as an IO-Link port, the module must be deleted and replaced 
with an IO-Link module. 
  
Slots 2..5 are reserved for the IO-Link ports / standard I/O ports.  
 

Module addressing: 

Double-click on the IO-Link modules and the remaining addressable modules to change the 
addressing in the "Addresses" window.  
 

Configuring the IO-Link module: 

A suitable IO-Link module that corresponds to the process data length of the IO-Link device 
must be selected in the catalog and dragged to the appropriate slot by means of drag & 
drop. 
The process data length required by the device in each case can be obtained from the 
manual of the IO-Link device. 
 

Configuring a standard input / output: 

If one of the possible port pins (pin 4) is to be configured with a standard function (input, 
output), the "Standard I/O" placeholder module must be used for the corresponding slot. 
To address the inputs and outputs, input pin 2 / 4 and output 2 /4 must be taken over from 
the catalog and used in the configuration according to the given modules. 
 
For the SIO function, integrate the "IO-Link input with SIO mode" module. 
 
With the remaining modules, the various functions are mapped into the process data areas. 
 
A description of the individual modules is provided in chapter "Bitmapping and function". 
 

 

Summary of Contents for BNI PNT-502-102-Z015

Page 1: ...BNI PNT 502 102 Z015 IP67 Module User s Guide...

Page 2: ...Grounding 7 PROFINET interface 8 I O port 8 IO Link port 8 Port 8 4 Technical data 9 4 1 Dimensions 9 4 2 Mechanical data 9 4 3 Operating conditions 9 4 4 Electrical data 9 4 5 PROFINET 10 4 6 Functio...

Page 3: ...tartup 25 6 6 Main menu 25 6 7 Factory Reset 26 6 8 Module Info 26 7 Webserver 27 7 1 General 27 7 2 Navigation Info 28 7 3 Login Logout 29 7 4 Home dialog 30 7 5 Ports dialog 32 No appropriate IODD u...

Page 4: ...ce 44 Specifier 44 Direction 44 8 6 Channel Error Type 45 9 Configuration of IO Link devices 46 General 46 Function block 46 Reading 46 Writing 46 10 Appendix 47 10 1 Scope of delivery 47 10 2 Order n...

Page 5: ...Step 2 3 Syntax Numbers Decimal numbers are shown without additional information e g 123 hexadecimal numbers are shown with the additional indicator hex e g 00hex or the prefix 0x e g 0x00 Cross refer...

Page 6: ...oid by Unauthorized tampering Improper use Use installation or handling contrary to the instructions provided in this operating manual Obligations of the Operating Company The device is a piece of equ...

Page 7: ...502 102 Z015 1 Port 3 2 Port 2 3 Port 1 4 Pin Port LEDs 5 Port 0 6 Power IN 7 Label 8 PROFINET port 1 9 Grounding connection 10 PROFINET port 2 11 Display 12 Power OUT 13 Status LEDs 14 Port 4 15 Port...

Page 8: ...nsor bus and actuator Total current 9 A The total current of all modules must not exceed 9A even in the case of series connection of the actuator supply Note Interpretation of leads for power supply o...

Page 9: ...6 A 2 Input output 2A 3 GND 4 Input output 2A 5 FE Note For the digital sensor inputs refer to guideline on inputs EN 61131 2 Type 2 Note Each output receives a maximum current of 2 0 A The total cur...

Page 10: ...ate Supply voltage 7 8 5 pin connector female Input ports output ports M12 A coded 8x female Dimensions W x H x D in mm 68 x 224 x 37 9 Type of installation Screw installation with 2 securing holes Gr...

Page 11: ...status LED Display Function US Green Input voltage OK Red flashing Input voltage low 18 V UA Green Output voltage OK Red flashing Output voltage low 18 V Red No output voltage present 11V SF off No e...

Page 12: ...hort circuit at output at pin 2 4 against pin 3 Red No high signal at diagnostic input IO Link port Status Function Green IO Link connection active Green flashing No IO Link connection or wrong IO Lin...

Page 13: ...k modules the corresponding data modules are assigned to a slot Integration of the module The device can be found by searching in the catalog and inserted in the Profinet section by drag drop The BNIP...

Page 14: ...higher the configuration of pin 4 as IO Link port is not necessary anymore The port is automatically configured to IO Link when an IO Link process data module is used in the hardware configuration Th...

Page 15: ...nk module that corresponds to the process data length of the IO Link device must be selected in the catalog and dragged to the appropriate slot by means of drag drop The process data length required b...

Page 16: ...lluff com 15 5 Integration IO Link configuration Double click on the IO Link module to change the IO Link parameters of the respective port pins A description of the individual modules is provided in...

Page 17: ...com 16 5 Integration Device name Profinet address Double click on the module in the Profinet line to view the communication parameters of the module The device name and the Profinet address IP are con...

Page 18: ...start the tool for assigning the module a device name Assigning device name Select the desired name and use Assign name to assign the marked device that you found The device name must be the same as t...

Page 19: ...uld be a problem in one of the following areas Device relationship not established Scan the network via Target system Ethernet Ethernet user Search and check whether the device is signaling under the...

Page 20: ...to the output of the module Optical diagnostics and diagnostics in configured diagnostics modules are not affected This function is valid only for channels pins that are configured as outputs As input...

Page 21: ...wn pin 4 pin 2 Depicts a short circuit between a set output to ground at the respective port pin Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Port 7 Port 6 Port 5 Port 4 Port 3 Port 2 Port 1 Port 0...

Page 22: ...rt 1 Port 0 Peripheral error socket Feedback indicating the port at which an error occurred Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 Port 7 Port 6 Port 5 Port 4 Port 3 Port 2 Port 1 Port 0 Shor...

Page 23: ...ta The visible data window for the input data can now be adjusted via an IO Link module with appropriate process data length Validation No validation Validation deactivated every device will be accept...

Page 24: ...nly the download is enabled the master always starts a download of the parameter data In this case the download is likewise independent of the upload flag of the IO Link device If no data is stored in...

Page 25: ...isplay 2 Arrow Key 3 Octett Cursor 4 Address type cursor 5 Set Key 6 LEDs Arrow Key This button is used to go through the entries of a menu and is a short time keypress The display shows the default s...

Page 26: ...rt time keypress on Set Key Step in a menu with short time keypress on Arrow Key Actual state Change over S Condition short time keypress on Set Key S Condition long time keypress on Set Key min 3 sec...

Page 27: ...confirmed the device performes a restart Note A factory reset can be performed only after a power reset without an attached network cable Module Info 6 8 Go through the Module Info menu with short tim...

Page 28: ...ure that the module has been correctly integrated into your network In addition the IP subnet of the BNI module must be accessible from the PC on which the browser is running Please use Internet Explo...

Page 29: ...the upper area of the window which allows you to switch between the various dialogs of the web interface To do this click on the corresponding icon When the Info tab is selected the following overview...

Page 30: ...T XXX XXX XXXX BNIPNT BNI EIP XXX XXX XXXX BNIEIP BNI ECT XXX XXX XXXX BNIECT The password cannot be changed After successfully logging in the dialogs are shown as follows Use the Logout button to log...

Page 31: ...ion is also shown about the current process data and the status of the module via the corresponding LEDs After selecting LED Legend a Help dialog appears which explains the meaning of the LEDs If an I...

Page 32: ...Balluff Network Interface ProfiNet www balluff com 31 7 Webserver PNT EIP...

Page 33: ...o appropriate IODD uploaded It is possible to read and write the configuration parameters of the IO Link device via the Parameters option The parameter indexes and subindexes of the IO Link device are...

Page 34: ...for Process Data and Parameters is not displayed but rather an expanded dialog Information from the IODD of the device is used so that the data can be better understood Thus in the following screensh...

Page 35: ...nt modes These modes can be set using an IO Link parameter The parameter values and associated texts are stored in the IODD This means Operation Mode can be read out and displayed Read and Read All bu...

Page 36: ...at i e with a restricted name length Since IODD files are generally published with a long file name these must be renamed and given a shorter naming scheme on the PC before uploading to the fieldbus m...

Page 37: ...The configuration page enables configuration of the module You can change both the module information texts and the port configuration The Set Ports action is not permanently stored in the device and...

Page 38: ...e Configuration and permanently stored in the device The Reboot button reboots the device as if the power to the module had been turned off and on again Clicking on Factory Reset deletes the configura...

Page 39: ...upper table see screenshot below contains important information for all service inquiries Note If you have a detailed question about a specific situation send us a screenshot of this Web site or print...

Page 40: ...ting the module from the outside The system may require troubleshooting Event Informational Notice The fieldbus module has detected an important normal operating event and reports it These may include...

Page 41: ...ed into 3 blocks Block Header Alarm Specifier Channel Properties Byte Value Meaning Block 0 00 Block Type Block Header 1 02 2 00 Block Length 3 1E 4 01 Block Version High 5 00 Block Version Low 6 00 A...

Page 42: ...ype of alarm is provided here Possible values Meaning 0x0001 Diagnostics API 4 bytes default is 0 Possible values Meaning 0x00000000 Default value Slot 2 bytes of data that describe which slot of the...

Page 43: ...es Meaning 0x00 No diagnosis related to manufacturer is pending 0x01 Diagnosis related to channel is pending Submodules Diagnostic State Bit 13 Possible values Meaning 0x00 No further diagnosis of sub...

Page 44: ...ort 2 pin 4 0x0003 Port 3 pin 4 0x0004 Port 4 pin 4 0x0005 Port 5 pin 4 0x0006 Port 6 pin 4 0x0007 Port 7 pin 4 0x000A Port 0 pin 2 0x000B Port 1 pin 2 0x000C Port 2 pin 2 0x000D Port 3 pin 2 0x000E P...

Page 45: ...6 32 bit 0x07 64 bit 0x08 0xFF Reserved Accumulative Bit 8 not used always 0 Maintenance Bit 9 10 Possible values Meaning Bit 9 Bit 10 0x00 0x00 Diagnostics Specifier Bit 11 12 Possible values Meaning...

Page 46: ...rcuit 0x0002 Undervoltage 0x0003 Overvoltage 0x0004 Overload 0x0005 Temperature limit exceeded 0x0006 Cable break 0x0007 Upper threshold exceeded 0x0008 Lower threshold undershot 0x0009 Error 0x001A E...

Page 47: ...r Port number Reserved 2 65098 FI_Index IO Link header is following IO Link header 1 0 255 Task 2 write 3 read 2 0 3276 7 65535 IO Link index Port function 1 0 255 IO Link subindex Data range 232 Rang...

Page 48: ...BNI PNT 502 102 Z015 Balluff network interface ProfiNet Functions 502 IP 67 IO Link master module 4 IO Link ports Versions 102 Display version 2 port switch rotated Mechanical version Z015 Die cast zi...

Page 49: ...www balluff com 48 Notes...

Page 50: ...www balluff com 49 www balluff com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germany Tel 49 7158 173 0 Fax 49 7158 5010 balluff balluff de No 895700 726 E 09 124983 Edition I17 Replaces Ed...

Reviews: