Balluff Network Interface / IO-Link  

www.balluff.com 

   

 

 

User Instructions 

  About this Manual 

  This manual describes the Balluff IO-Link I/O module, also called a sensor/actuator hub. 

The IO-Link protocol is used to link to the higher-level master module. 
In terms of function, this compact, cost-effective module is similar to a passive splitter box; it 
records digital sensor signals and transmits them over the IO-Link interface. It passes 
control signals coming over IO-Link to the connected actuators. 

 

  Structure of the 

Manual 

  The manual is organized so that the sections build on one another. 

Chapter 2: Basic safety information. 
…….. 

 

  Typographical 

Conventions 

 

The following typographical conventions are used in this manual. 

 

Enumerations 

  Enumerations are shown as a list with an en-dash. 

 

Entry 1. 

 

Entry 2. 

 

Actions 

  Action instructions are indicated by a preceding triangle. The result of an action is indicated 

by an arrow. 

 

Action instruction 1. 

 

Action result. 

 

Action instruction 2. 

 

Syntax 

 

Numbers: 

Decimal numbers are shown without additional indicators (e.g. 123), hexadecimal numbers 
are shown with the additional indicator

 hex 

(e.g. 3F

hex

). 

 

Cross references 

  Cross references indicate where additional information on the topic can be found. 

 

  Symbols 

 

Attention! 

This symbol indicates a safety instruction that must be followed without exception. 

 
 

 

Note 

This symbol indicates general notes. 

 

  Abbreviations 

  BNI 

DPP 
I/O port 
IOL 
ISDU 
EMC 
FE 
LSB 
MSB 
SC 
UA 
US 

Balluff Network Interface 
Direct Parameter Page 
Digital input/output port 
IO-Link 
Indexed Service Data Unit (former SPDU) 
Electromagnetic compatibility 
Function ground 
Least Significant Bit 
Most Significant Bit 
Short circuit 
Actuator supply 
Sensor supply 

 

  Differing views 

  Product views and images in this manual may differ from the product described. They are 

intended to serve only as illustrations. 

Summary of Contents for BNI IOL-104-S02-Z012

Page 1: ...BNI IOL 104 S02 Z012 IO Link 1 1 Sensor Hub with extension port User s Guide...

Page 2: ...nfiguration of the Extension Port 11 Data handling with the Extension Port 12 5 Configuration BNI IOL 104 S02 Z012 extension port off 13 Extension Port Configuration 13 IO Link Data 13 Process Data In...

Page 3: ...utputs 42hex 25 Voltage monitoring 44hex 27 Output monitoring 45hex 28 Setting the serial number 54hex 28 Configuration of the extension port 55hex 28 8 Error Codes and Events 29 Error Codes Errors 29...

Page 4: ...tructions are indicated by a preceding triangle The result of an action is indicated by an arrow Action instruction 1 Action result Action instruction 2 Syntax Numbers Decimal numbers are shown withou...

Page 5: ...oid by Unauthorized tampering Improper use Use installation or handling contrary to the instructions provided in this user s guide Obligations of the operating company The device is a piece of equipme...

Page 6: ...overview Figure 3 1 Connection overview 1 Mounting hole 2 Label 3 Communication state 4 Port 1 5 Port 3 6 Port 5 7 Port 7 Extension Port 8 Pin Port LED Signal status 9 Port 6 10 Port 4 11 Port 2 12 Po...

Page 7: ...kept as short as possible IO Link connection The IO Link connection is established via an M12 connector A coded male This connector is used for powering the module In some devices this connector is al...

Page 8: ...Requirement 1 24V 200mA 2 PNP Input 2 3 0V GND 4 PNP Input 1 5 FE Note For the digital inputs the input guideline specified in EN 61131 2 Type 3 applies Note Unused input port sockets must be fitted w...

Page 9: ...e modules provide using the Port 7 in various ways By default it is used as a digital input port where both pin 2 and pin 4 can be used as a digital input Additionally this port can be used as an Exte...

Page 10: ...Process Data In Configuration of Extension Port Process Data Input Bytes 0 1 2 3 4 5 6 7 0 BNI IOL 104 S02 Z012 Input State Diagnostic Info 1 BNI IOL 104 S02 Z012 same device Input State Diagnostic I...

Page 11: ...K007 The device which is connected to the Extension Port is called as Second Device in this manual Note The Factory reset command does not affect the configuration of the extension port in any way Not...

Page 12: ...ort When the Extension Port is activated the content and length of the Process Data or ISDU is calculated as the union of the process data or ISDU provided by the two parties PD result PD of first dev...

Page 13: ...ration is Extension Port off Configuration ISDU Index 55hex value Device alone Extension Port not active 0 Device with same device 1 Device with BNI IOL 751 V08 K007 2 Device with BNI IOL 751 V10 K007...

Page 14: ...t 7 Pin 4 Port 6 Pin 4 Port 5 Pin 4 Port 4 Pin 4 Port 3 Pin 4 Port 2 Pin 4 Port 1 Pin 4 Port 0 Pin 4 Port 7 Pin 2 Port 6 Pin 2 Port 5 Pin 2 Port 4 Pin 2 Port 3 Pin 2 Port 2 Pin 2 Port 1 Pin 2 Port 0 P...

Page 15: ...ame BNI IOL 104 S02 Z012 13hex 19 0 Product ID 7 bytes BNI00CR 14hex 20 0 Product text Sensor Hub M12 15hex 21 0 Serial number 16 bytes various 16hex 22 0 Hardware Revision 17hex 23 0 Firmware Revisio...

Page 16: ...SC Port 6 Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Undervoltage US1 Setting the serial number 54hex The serial number has a factory default...

Page 17: ...n Configuration ISDU Index 55hex value Device alone Extension Port not active 0 Device with same device 1 Device with BNI IOL 751 V08 K007 2 Device with BNI IOL 751 V10 K007 3 Device with BNI IOL 751...

Page 18: ...4 3 2 1 0 Voltage monitoring SC Port 7 Pin 1 SC Port 6 Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Undervoltage US1 Byte 4 5 Bit 7 6 5 4 3 2...

Page 19: ...12 with BNI IOL 104 S02 Z012 13hex 19 0 Product ID BNI00CR with BNI00CR 14hex 20 0 Product text Sensor Hub M12 extended with Sensor Hub M12 15hex 21 0 Serial number 16 bytes various 16hex 22 0 Hardwar...

Page 20: ...2 Pin 4 Port 1 Pin 4 Port 0 Pin 4 Port 6 Pin 2 Port 5 Pin 2 Port 4 Pin 2 Port 3 Pin 2 Port 2 Pin 2 Port 1 Pin 2 Port 0 Pin 2 Byte 2 3 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Sub index 24 23 22 21 20 19 18...

Page 21: ...sion Port Voltage monitoring SC Port 7 Pin 1 SC Port 6 Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Undervoltage US1 Setting the serial number...

Page 22: ...not active 0 Device with same device 1 Device with BNI IOL 751 V08 K007 2 Device with BNI IOL 751 V10 K007 3 Device with BNI IOL 751 V13 K007 4 However BNI IOL 104 S02 Z012 is a digital input module...

Page 23: ...Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Outputs off UA too low Undervoltage UA Undervoltage US1 Process Data Output Data No function for B...

Page 24: ...BNI00CR with BNI006P BNI00CR with BNI006R 14hex 20 0 Product text Sensor Hub M12 extended with Valve Plug CG25 24 2 3 Sensor Hub M12 extended with Valve Plug CG13 24 2 3 Sensor Hub M12 extended with V...

Page 25: ...erted Safe state of the outputs 42hex The safe state parameter makes it possible to configure the outputs in case of a fault If no IO Link communication is possible or the valid flag of the output pro...

Page 26: ...A Valve 01 Coil A Byte 4 5 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Sub index 24 22 20 18 Valve terminal on extension port Safe State of Valve 12 Coil B Valve 11 Coil B Valve 10 Coil B Valve 09 Coil B No...

Page 27: ...Sub index 8 7 6 5 4 3 2 1 16 15 14 13 12 11 10 9 Voltage monitoring SC Port 7 Pin 1 SC Port 6 Pin 1 SC Port 5 Pin 1 SC Port 4 Pin 1 SC Port 3 Pin 1 SC Port 2 Pin 1 SC Port 1 Pin 1 SC Port 0 Pin 1 Out...

Page 28: ...2 Valve terminal on extension port Short circuit of Valve 12 Coil B Valve 11 Coil B Valve 10 Coil B Valve 09 Coil B Valve 08 Coil B Valve 07 Coil B Valve 06 Coil B Valve 05 Coil B Valve 04 Coil B Val...

Page 29: ...available Events IO Link Revision 1 0 Event code Description 0x5112 Low sensor voltage US 0x5114 Low actuator voltage UA 0x5410 Output stages 0x8DF0 Retry at the extension port 0x8DF1 Device lost at t...

Page 30: ...stored configuration is automatically transferred to the new device This guarantees minimal downtime Validation must be switched on in order to use the data storage For information about the configur...

Page 31: ...sions H x W x D without connector 68 x 181 5 x 31 8 mm Electrical Data Supply voltage 18 30 2 V DC corresponding to EN 61131 2 Supply power on M12 connector 4 A Ripple 1 Current consumption without lo...

Page 32: ...puts Indicator Description LED 0 Input on Pin4 LED 1 Input on Pin2 Status Function Yellow Input signal 1 Red Sensor power supply short circuit Off Input signal 0 Extension port The table is valid if t...

Page 33: ...S02 Z012 BNI00CR BNI IOL xxx xxx Zxxx Balluff Network Interface IO Link interface Functions 104 16 PNP inputs Variants S02 with IO Link 1 1 extension port and single channel monitoring Mechanical conf...

Page 34: ...www balluff com www balluff com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germany Tel 49 7158 173 0 Fax 49 7158 5010 balluff balluff de No 940290 E Edition E18 Subject to modification...

Reviews: