 Balluff Network Interface / IO-Link BNI IOL-104-S02-R012 

 

  www.balluff.com

 

   

 

 

1

 

User Instructions 

1.1.

 

About This 
Manual 

  This manual describes the Balluff IO-Link I/O module, also called a sensor/actuator hub. 

The IO-Link protocol is used to link to the higher-level master module. 
In terms of function, this compact, cost-effective module is similar to a passive splitter box; it 
records digital and analog sensor signals and transmits them over the IO-Link interface. It 
passes control signals coming over IO-Link to the connected actuators. 

 

1.2.

 

Structure of the 
Manual 

  The manual is organized so that the sections build on one another. 

Chapter 2: Basic Safety Information. 
…….. 

 

1.3.

 

Typographical 
Conventions 

 

The following typographical conventions are used in this manual. 

 

Enumerations 

  Enumerations are shown as a list with an en-dash. 

 

Entry 1. 

 

Entry 2. 

 

Actions 

  Action instructions are indicated by a preceding triangle. The result of an action is indicated 

by an arrow. 

 

Action instruction 1. 

 

Action result. 

 

Action instruction 2. 

 

Syntax 

 

Numbers: 

Decimal numbers are shown without additional indicators (e.g. 123). 
Hexadecimal numbers are shown with the additional indicator 

hex

 (e.g. 00

hex

).

 

 

Cross-references 

  Cross-references indicate where additional information on the topic can be found. 

 

1.4.

 

Symbols 

 

Caution! 

This symbol indicates a safety instruction that must be followed without exception 

 
 

 

Note, tip 

This symbol indicates general notes. 

 

1.5.

 

 Abbreviations 

  BNI 

DPP 
I/O port 
EMC  
FE  
IOL  
LSB 
MSB  
SPDU 
 

Balluff Network Interface 
Direct Parameter Page 
Digital input/output port 
Electromagnetic compatibility 
Functional Ground 
IO-Link 
Least Significant Bit 
Most Significant Bit 
Service Protocol Data Unit 
 

Summary of Contents for BNI IOL-104-S02-R012

Page 1: ...BNI IOL 104 S02 R012 IO Link 1 1 sensor hub with extension port User s Guide...

Page 2: ...uration Extension Off 10 4 1 IO Link Data 10 4 2 Process Data Input Data 10 4 3 Parameter Data Demand Data 11 Parameter Data Demand Data 11 Inversion of the inputs 40hex 12 Voltage monitoring 44hex 12...

Page 3: ...ctory Settings 27 8 Technical Data 28 8 1 Dimensions 28 8 2 Mechanical Data 28 8 3 Electrical Data 28 8 4 Operating conditions 28 9 Function Indicators 29 9 1 Function Indicators 29 LED indicator modu...

Page 4: ...re used in this manual Enumerations Enumerations are shown as a list with an en dash Entry 1 Entry 2 Actions Action instructions are indicated by a preceding triangle The result of an action is indica...

Page 5: ...roper use Use installation or handling contrary to the instructions provided in this user s guide Obligations of the operating company The device is a piece of equipment in accordance with EMC Class A...

Page 6: ...1 Connection overview BNI IOL 104 S02 R012 1 Mounting hole 2 Label 3 Status LED communication 4 Port 1 5 Port 3 6 Port 5 7 Port 7 extension port 8 Pin Port LED signal status 9 Port 6 10 Port 4 11 Port...

Page 7: ...odules are equipped with a ground connection Figure 3 3 BNI ground connection IOL 104 xxx Connect the sensor hub module to the ground connection Note The functional ground connection from the housing...

Page 8: ...puts Sensor interface Digital input port M12 A coded female Pin Function 1 24 V 2 Input 2 3 0 V GND 4 Input 1 5 FE Note For the digital inputs the input guideline specified in EN 61131 2 Type 3 applie...

Page 9: ...Extension port configuration Configuration Index 0x55 value BNI IOL 104 S02 R012 0 BNI IOL 104 S02 R012 with BNI IOL 104 S02 R012 1 BNI IOL 104 S02 R012 with BNI IOL 751 V08 K007 2 BNI IOL 104 S02 R0...

Page 10: ...Port 7 Pin 4 Input Port 6 Pin 4 Input Port 5 Pin 4 Input Port 4 Pin 4 Input Port 3 Pin 4 Input Port 2 Pin 4 Input Port 1 Pin 4 Input Port 0 Pin 4 Input Port 7 Pin 2 Input Port 6 Pin 2 Input Port 5 Pin...

Page 11: ...20 24 bytes BNI IOL 104 S02 R012 13hex 19 0 Product ID 7 bytes BNI0090 14hex 20 0 Product text 16 bytes Sensor Hub M12 15hex 21 0 Serial number 16 bytes 0hex 16hex 22 0 Hardware revision 17hex 23 0 Fi...

Page 12: ...n of Port 0 Pin 4 Inversion of Port 7 Pin 2 Inversion of Port 6 Pin 2 Inversion of Port 5 Pin 2 Inversion of Port 4 Pin 2 Inversion of Port 3 Pin 2 Inversion of Port 2 Pin 2 Inversion of Port 1 Pin 2...

Page 13: ...ut Port 6 Pin 4 Input Port 5 Pin 4 Input Port 4 Pin 4 Input Port 3 Pin 4 Input Port 2 Pin 4 Input Port 1 Pin 4 Input Port 0 Pin 4 Input Port 7 Pin 2 Input Port 6 Pin 2 Input Port 5 Pin 2 Input Port 4...

Page 14: ...Port 3 Pin 4 Input Port 2 Pin 4 Input Port 1 Pin 4 Input Port 0 Pin 4 Input Port 7 Pin 2 Input Port 6 Pin 2 Input Port 5 Pin 2 Input Port 4 Pin 2 Input Port 3 Pin 2 Input Port 2 Pin 2 Input Port 1 Pin...

Page 15: ...S02 R012 with BNI IOL 104 S02 R012 13hex 19 0 Product ID 7 bytes BNI0090 with BNI0090 14hex 20 0 Product text 16 bytes Sensor hub M12 extended with Sensor hub M12 15hex 21 0 Serial number 16 bytes 0he...

Page 16: ...2 Inversion of Port 4 Pin 2 Inversion of Port 3 Pin 2 Inversion of Port 2 Pin 2 Inversion of Port 1 Pin 2 Inversion of Port 0 Pin 2 Byte 2 3 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Sub index 24 23 22 21...

Page 17: ...rvoltage US1 Byte 2 3 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Sub index 24 23 22 21 20 19 18 17 32 31 30 29 28 27 26 25 Extension port Description Short circuit Port 7 Pin 1 Short circuit Port 6 Pin 1 Sho...

Page 18: ...put Data Byte 0 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Description Input Port 6 Pin 4 Input Port 5 Pin 4 Input Port 4 Pin 4 Input Port 3 Pin 4 Input Port 2 Pin 4 Input Port 1 Pin 4 Input Port 0 Pin 4 I...

Page 19: ...Valve 10 Coil A Valve 09 Coil A Valve 08 Coil A Valve 07 Coil A Valve 06 Coil A Valve 05 Coil A Valve 04 Coil A Valve 03 Coil A Valve 02 Coil A Valve 01 Coil A No function for V013 Byte 2 3 Bit 7 6 5...

Page 20: ...V13 K007 13hex 19 0 Product ID 7 bytes BNI0090 with BNI006N BNI006P BNI006R 14hex 20 0 Product text 16 bytes Sensor hub M12 extended with Valve plug CG25 24 2 5 Sensor hub M12 extended with Valve plug...

Page 21: ...nversion of Port 6 Pin 4 Inversion of Port 5 Pin 4 Inversion of Port 4 Pin 4 Inversion of Port 3 Pin 4 Inversion of Port 2 Pin 4 Inversion of Port 1 Pin 4 Inversion of Port 0 Pin 4 Inversion of Port 7...

Page 22: ...et by the master then each output adopts the configured status The following statuses can be configured for each pin Byte 0 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Sub Index 23 21 19 17 Valve terminal o...

Page 23: ...11 Coil B Valve 10 Coil B Valve 09 Coil B No function for V013 Byte 6 7 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Sub Index 16 14 12 10 8 6 4 2 Valve terminal on extension port Description Valve 08 Coil B V...

Page 24: ...2 1 16 15 14 13 12 11 10 9 Description Short circuit Port 7 Pin 1 Short circuit Port 6 Pin 1 Short circuit Port 5 Pin 1 Short circuit Port 4 Pin 1 Short circuit Port 3 Pin 1 Short circuit Port 2 Pin 1...

Page 25: ...oil A Valve 01 Coil A No function for V013 Byte 2 3 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Sub Index 24 22 20 18 16 14 12 10 8 6 4 2 Extension port Description Valve 12 Coil B Valve 11 Coil B Valve 10 Co...

Page 26: ...not available 0x8036 Function temporarily unavailable 6 6 Events IO Link Revision 1 0 Event code Description 0x5112 Low sensor voltage US 0x5114 Low actuator voltage UA 0x5410 Output stages 0x8DF0 Re...

Page 27: ...ransferred to the new device This guarantees minimal downtime Validation must be switched on in order to use the data storage For information about the configuration of data storage and validation ple...

Page 28: ...3 5 x 68 x 36 8 mm 8 3 Electrical Data Supply voltage 18 30 2 V DC corresponding to EN 61131 2 Ripple 1 Current consumption without load 40 mA Load current PIN 1 Max 200 mA temperature dependent Total...

Page 29: ...cators LED indicator module status Indicator Function COM Green No communication Green negatively pulsed Communication OK US1 LED Green Sensor power supply is OK Red Undervoltage 18 V UA LED Green Act...

Page 30: ...gnal 1 Red Sensor power supply short circuit Off Input output signal 0 Extension port The table is valid if the extension port is active If the extension port is used as a standard I O then the descri...

Page 31: ...04 S02 R012 BNI0090 BNI IOL 104 S02 R012 Balluff Network Interface IO Link interface Functions 104 16 inputs Variants S02 with IO Link 1 1 extension port Mechanical configuration R012 Plastic housing...

Page 32: ...www balluff com www balluff com Balluff GmbH Schurwaldstrasse 9 73765 Neuhausen a d F Germany Phone 49 7158 173 0 Fax 49 7158 5010 balluff balluff de No 926589 E Edition L15 Subject to modification...

Reviews: