Balluff BMP 01-EL1PP 1A Series User Manual Download Page 27

www.balluff.com

27

english

7.6 

Diagnostic data

The BMP reports diagnostic data (events) to the controlling 

system (see Tab. 7-15), or the controlling system can read 

out the status using the diagnostic parameters.

7.6.1  Diagnostic parameters

Index

Subindex

Parameter

Size

Access

Values

0x0024 (36) 0

Device Status

1 Byte

Read Only

0 = Normal state

2 = Warning

4 = Error

0x0025 (37) 0

Detailed Device 

Status

9 Byte

Read Only

Up to 3 active events:

1st byte event type (0 = No event, 

0xE4 = Warning, 0xF4 = Error)

2nd and 3rd byte event code (see Sec. 7.6.2)

0x0028 (40) 0

Process Data Input

6 Byte

Read Only

Most recent valid process data (see Sec. 7.2)

Tab. 7-15:  Diagnostic parameters

7.6.2  Event list

Event 

code

Expression

Meaning

0x8D00

Notification

LIMITED ACCURACY PLUS – The target is located in the detection range, but outside of the 

configured measuring range.

0x8D01

Notification

LIMITED ACCURACY MINUS – The target is located in the detection range, but outside of 

the configured measuring range.

0x8D02

Warning

OUT OF RANGE PLUS – The target is located outside of the detection range. No valid data 

is output. The transmitted process data value is 0×7FFFFFF8 or 2'147'483'640.

0x8D03

Warning

OUT OF RANGE MINUS – The target is located outside of the detection range. No valid data 

is output. The transmitted process data value is 0x80000008 or –2'147'483'640.

0x8D04

Error

NO MEASUREMENT DATA – No target detected. No valid data is output. The transferred 

process data value is 0×7FFFFFFC or 2147483644.

0x8D06

Warning

MEASUREMENT DATA UNSAFE – The excess gain of the measurement is low. The 

application must be reviewed.

0x4210

Warning

DEVICE TEMPERATURE OVERRUN (see section 7.5.6) – The configured upper temperature 

threshold is exceeded.

0x4220

Warning

DEVICE TEMPERATURE UNDERRUN (see section 7.5.6) – The configured lower temperature 

threshold is not met.

0x4000

Error

TEMPERATURE OVER RUN ERROR – The temperature has exceeded the specified 

maximum temperature. The heat source must be removed.

0x5000

Error

HARDWARE FAULT – There is a problem with the device hardware. Restart the BMP by 

interrupting the supply. If the event occurs again, the BMP must be replaced.

0x8D07

Error

OPEN CIRCUIT AT CURRENT OUTPUT – The analog current output is open, check the 

installation.

Tab. 7-16:  Event list

7

 

IO-Link interface (continued)

BMP 01- EL1PP _ 1A- _ _ _ _ -00 -P _ _ /P _ _ -S4/P _ _ -S75

Magnetic Field Positioning System

Summary of Contents for BMP 01-EL1PP 1A Series

Page 1: ...BMP 01 EL1PP_1A _ _ _ _ 00 P_ _ S75 BMP 01 EL1PP_1A _ _ _ _ 00 P_ _ S4 BMP 01 EL1PP_1A _ _ _ _ 00 P_ _ User s Guide english...

Page 2: ...www balluff com...

Page 3: ...and function 7 3 1 Construction 7 3 2 Function 7 3 2 1 Analog and switching output 8 3 2 2 IO Link interface 8 3 3 LED display 8 4 Installation and connection 9 4 1 Mounting to a pneumatic cylinder u...

Page 4: ...ccess locks Device Access Locks 26 7 5 11 Profiles and functions ProfileCharacteristic 26 7 5 12 Process data structure PD Input Descriptor 26 7 6 Diagnostic data 27 7 6 1 Diagnostic parameters 27 7 6...

Page 5: ...ystem Condensed guide The target and mounting accessories depend on the application and are to be ordered sepa rately 1 4 Approvals and markings UL approval File no E227256 The CE Mark verifies that o...

Page 6: ...s responsible for ensuring that local safety regulations are observed In particular the operator must take steps to ensure that a defect in the BMP will not result in hazards to persons or equipment I...

Page 7: ...marily for the non contact detection of the piston stroke of pneumatic cylinders grippers and slides with axially magnetized permanent magnets The BMP ensures continuous absolute position measurement...

Page 8: ...for the measured value and switching signals Functions for state monitoring Temperature detection Operating hours counter Boot cycle counter The IO Link interface is described in section 7 on page 17...

Page 9: ...oper installation can compromise the function of the BMP and result in increased wear The target must not contact the BMP Shield any magnetic fields that can influence the measurement Position the BMP...

Page 10: ...Align slot nuts T slot at left C slot at right in the image 3 Guide slot nuts into the slot Fig 4 4 Guiding slot nuts into the slot T slot at left C slot at right in the image Fig 4 5 Slot nuts in th...

Page 11: ...entation of the holder see Fig 4 8 Fig 4 8 BMP Round cylinder Round cylinder holder Attaching holder to the BMP 2 Slide hose clamps over the BMP and the holders Fig 4 9 Hose clamp Applying hose clamps...

Page 12: ...Direct and inverse mounting The BMP can be mounted directly sensing surface pointing to mounting surface or inversely Fig 4 12 N S Installation with floating target inverse mounting axially polarized...

Page 13: ...re that there is sufficient distance between the BMP and holding cylinder and any strong external magnetic fields Cable routing Do not route cables between the BMP control system and power supply near...

Page 14: ...t or system manufacturer 1 Check connections for tightness and correct polarity Replace damaged connections 2 Turn on the system 3 Check measurement values and adjustable parameters and readjust the B...

Page 15: ...switching output 6 3 Switching output Switching signal factory setting Fig 6 3 active inactive Switching signal factory setting Taught in switching signal Teach 1 switch on point and Teach 2 switch of...

Page 16: ...ton briefly Teach switch point Green off Yellow 5 Hz Red off Adjusting the switch point logic Green on off Green on Normally closed Yellow 5 Hz Green off Normally open Red 5 Hz Convert Press the butto...

Page 17: ...sion Revision ID 0x11 Version 1 1 Amount of process data from the device to the master ProcessDataIn 6 byte 0xC5 Amount of process data from the master to the device ProcessDataOut 0 byte 0x00 Manufac...

Page 18: ...h information for the third switch point 1 SSC 2 Switch information for the second switch point 0 SSC 1 Switch information for the first switch point SSC 1 is placed on output OUT 1 in SIO mode Tab 7...

Page 19: ...Read Only 0 0018 24 0 Application Specific Tag Max 32 bytes Read Write X 0 0019 25 0 Function Tag Max 32 bytes Read Write X 0 001A 26 0 Location Tag Max 32 bytes Read Write X Tab 7 4 Identification d...

Page 20: ...he currently measured position as Setpoint 1 0x42 66 SP2 Single Value Teach Saves the currently measured position as Setpoint 2 0x4E 78 Teach Reset Deletes the SP1 and SP2 values of all SSCs 0x80 128...

Page 21: ...16385 0 1 2 3 SSC3 Configurartion 4 bytes Read Write X 0x4002 16386 0 1 2 SSC4 Parameter 8 byte Read Write X 0x4003 16387 0 1 2 3 SSC4 Configurartion 4 bytes Read Write X Device Configuration 0x00B4 1...

Page 22: ...arameters can influence each other Therefore it is recommended to configure the settings in the following order Range Teach Output Characteristics Offset Preset Teach Range Teach The measuring range o...

Page 23: ...385 SSC4 0x4003 16387 1 Logic 1 byte Read Write 0 Normally open NO default 1 Normally closed NC 2 Mode 1 byte Read Write 0 Deactivated 2 Window mode default 3 Hysteresis 2 bytes Read Write 100 to 3000...

Page 24: ...ed 1 PNP default 2 NPN 3 Push Pull 2 Out 2 1 byte Read Write 0 Deactivated 5 Current 4 to 20 mA 6 Voltage 0 to 10 V default Tab 7 10 Configuration of the outputs 7 5 4 Diagnostic suppression If diagno...

Page 25: ...25 85 C If these threshold values are exceeded or not met the BMP outputs a warning see Event list on page 27 If the internal temperature of the BMP exceeds 95 C error Excess temperature is output 7 5...

Page 26: ...to common profile Subindex 3 FunctionClassID 0 8001 SSC function class Subindex 4 FunctionClassID 0 8004 teach channel 7 5 12 Process data structure PD Input Descriptor This parameter describes the c...

Page 27: ...utput The transmitted process data value is 0 7FFFFFF8 or 2 147 483 640 0x8D03 Warning OUT OF RANGE MINUS The target is located outside of the detection range No valid data is output The transmitted p...

Page 28: ...available 0x8023 Access denied 0 8030 Value out of range 0 8033 Parameter length overrun 0 8034 Parameter length underrun 0 8036 Function temporarily unavailable 0x8040 Invalid parameter set 0x8082 A...

Page 29: ...of Ue 10 Load resistance RL Analog I 500 Ohm Output current Analog U 5 mA Load capacity of switching output 100 mA 8 4 Electrical connection Bending radius fixed routing 3 cable diameter Cable diamete...

Page 30: ...x 10x Mounting screws 9 4 Holders for round cylinders BAM MC MP 054 01 R Order code BAM037Z 2 holders for round cylinders Fig 9 4 22 5 14 4 6 5 9 5 Holder for round cylinder 9 4 1 Hose clamps for atta...

Page 31: ...Rising factory setting programmable Switching output 1 1 programmable switching output Setting A Characteristic and switch points adjustable using Teach In or IO Link Measuring range 4 digit e 0128 Me...

Page 32: ...3 1 Order code 2 Type 3 Serial number Fig 11 1 Part label example 11 Appendix BMP 01 EL1PP_1A _ _ _ _ 00 P_ _ P_ _ S4 P_ _ S75 Magnetic Field Positioning System No 939733 726 EN 02 Vorserie L18 subjec...

Reviews: