BMF 235
Sensor family
16
5
Teaching in switchpoints
Index
Name
Sub-
index
Name
Data
type
Access
Values
Comment
0x4007
(16391)
Switch
Point
Config.
BDC6
0x01
Switchpoint
logic
UINT8
R/W
0x00 = N.O.
0x01 = N.C.
0x02
Switchpoint
mode
UINT8
R/W
0x01 = Single Point Mode
0x00 = Deactivated
0x03
Switchpoint
hysteresis
UINT16
R/W
1…10
Factory setting: 5
0x4008
(16392)
Set Point
Value
BDC7
0x01
Setpoint SP1 UINT16
R/W
0x00…0xffff
Symbolic value
(not functional)
0x02
Setpoint SP2 UINT16
R/W
0x00
0x4009
(16393)
Switch
Point
Config.
BDC7
0x01
Switchpoint
logic
UINT8
R/W
0x00 = N.O.
0x01 = N.C.
0x02
Switchpoint
mode
UINT8
R/W
0x01 = Single Point Mode
0x00 = Deactivated
0x03
Switchpoint
hysteresis
UINT16
R/W
1…10
Factory setting: 5
0x400A
(16394)
Set Point
Value
BDC8
0x01
Setpoint SP1 UINT16
R/W
0x00…0xffff
Symbolic value
(not functional)
0x02
Setpoint SP2 UINT16
R/W
0x00
0x400B
(16395)
Switch
Point
Config.
BDC8
0x01
Switchpoint
logic
UINT8
R/W
0x00 = N.O.
0x01 = N.C.
0x02
Switchpoint
mode
UINT8
R/W
0x01 = Single Point Mode
0x00 = Deactivated
0x03
Switchpoint
hysteresis
UINT16
R/W
1…10
Factory setting: 5
5.2.4 Switching modes
Single Point Mode
Switch mode
Single Point Mode
Window Mode
Two Point Mode
Deactivated
Switching behavior
Binary Data Channel
NO
NC
NO
NC
NO
NC
-
BDC1
SIO
SIO
-
-
-
-
-
IO
IO
-
-
-
-
BDC2
SIO
SIO
-
-
-
-
SIO
IO
IO
-
-
-
-
IO
BDC3…8
IO
IO
-
-
-
-
IO
IO = IO-Link operation
SIO = SIO operation
Deactivated
– N.O.: BDCx = 0
– N.C.: BDCx = 0