Teaching in switchpoints
BDCx
SP1-Hyst
SP1+Hyst
SP1
N.O.
S
BDCx
SP1-Hyst
SP1+Hyst
SP1
N.C.
S
Direction
5.2.5 Events
Event code
Meaning
Mode
Type
Instance
Device status
0x5000
Hardware error
Incoming/outgoing
Error
Application
Error
0x5111
Undervoltage
Incoming/outgoing
Warning
Application
Out-of-Specification
0x4210
Overheating
Incoming/outgoing
Warning
Application
Out-of-Specification
0x8CA1
Teach Timeout
Once
Message
Application
5.2.6 Teach-in procedures
General information
– Setpoint 2 (SP2) as per Smart Sensor profile is not supported for this sensor (always 0x0000).
– For the Single Value Teach applied here, both teach-in points (TP1 and TP2) are taught in at the same time and
are assigned the same value (the status bits are therefore not supported).
Preconditions
The sensor is mounted, aligned, and in IO-Link mode.
Teach-in
1.
Move the cylinder to the desired position.
2.
Select the teach-in channel as follows:
Access
Index
Values
Comment
W
0x003A (58)
0x00
BDC1 (Standard)
0x01-0x08
BDC1-BDC8
0xFF
All BDC
3.
Start teach-in: Send system command 0x41 to the sensor.
Access
Index
Values
Comment
W
0x0002 (2)
0x41
Single Value Teach
4.
Confirm teach-in: Send system command 0x40 to the sensor.
Access
Index
Values
Comment
W
0x0002 (2)
0x40
Teach Apply
5.
Check whether teach-in was successful: read out the teach-in status
Access
Index
Values
Comment
Result
R
0x003B (59)
0x01
Teach-In Status = SP1 SUCCESS
Teach-in completed
successfully
0x07
Teach-In Status = ERROR
Return to step 2