BES 516-615-_ _-1-PU/S115-05

Analog Switching Amplifier

 Check switching points

Move the target object (machine member etc.) towards
the sensor. When a switching point is reached, the
associated LED must come on.

Fig. 2: Connection diagram BES 516-615-PS-1-PU- (PNP)

PNP, NO

C = Control

Copt. = optional input

A = Analog signal

NO1...NO3 = Switching
outputs (normally open)

 Connections

 Dimensions

Fig. 3: Connection diagram BES 516-615-PS-1-PU- (NPN)

 Correct switching points in teach-in mode

1 Connect the Control input (C) through a switch to +

(Fig. 2, 3).

2 Turn on programming mode: Hold the button down for

at least 5 seconds.

3 Select the switching point to be corrected: Press the

button for max. two seconds until the next switching
point is selected.

4 Position the target object (machine member etc.) at

the desired switching location.

5 Save the switching distance: Hold the button down for

two to four seconds.

6 Return to operating mode: Press the button for max.

2 seconds as often as required until the LED no longer
flashes.

7 After programming is complete, connect the analog

switching amplifier to the user-side controller. In
operating mode a fixed connection between the C
input and ground is recommended.

NPN, NO

C = Control

Copt. = optional input

A = Analog signal

NO1...NO3 = Switching
outputs (normally open)

Effective operating voltage U

e

24 V DC

Supply voltage U

B

15...30 V DC

Ripple

< 15% von U

e

Rated isolation voltage U

i

75 V DC

No-load current  I

O

 at U

e

< 20 mA

Short/overload protected

yes

Reverse polarity protected

yes

Ambient temperature T

a

–10...+70° C

Analog input
Input voltage

0...10 V

Input impedance

4.2 k

W

Switching outputs
Freely programmable switching outputs

3

Hysteresis

< 500 mV

Effective operating current I

e

for one switching output

100 mA

Switching frequency f

2000 Hz

LED display for each output

yes

Enclosure rating per IEC 60529

IP 67

Housing material

Nickel plated CuZn

Connection type in-/output

BES 516-615-...-PU-

conn./cable PUR

BES 516-615-...-S115-

conn./connector

No. of conductors x gauge

BES 516-615-...-PU-

7 x 0.25 mm

2

BES 516-615-...-S115-

6 x 0.25 mm

2

 Technical Data

 Connector for BES 516-615-..-1-PU-...

For analog sensors with cabel connection the
confectionable connector BKS-S109-RT04 is available
as accessory.

Fig. 6: M12 connector

Fig. 4: Conn. diagram BES 516-615-...-S115 (PNP)

PNP, NO

C = Control

Copt. = optional input

A = Analog signal

NO1...NO3 = Switching outputs

Fig. 5: Dimensions

BES 516-615-...-PU-

BES 516-615-...-S115-