BES 516-615-_ _-1-PU/S115-05
Analog Switching Amplifier
Check switching points
Move the target object (machine member etc.) towards
the sensor. When a switching point is reached, the
associated LED must come on.
Fig. 2: Connection diagram BES 516-615-PS-1-PU- (PNP)
PNP, NO
C = Control
Copt. = optional input
A = Analog signal
NO1...NO3 = Switching
outputs (normally open)
Connections
Dimensions
Fig. 3: Connection diagram BES 516-615-PS-1-PU- (NPN)
Correct switching points in teach-in mode
1 Connect the Control input (C) through a switch to +
(Fig. 2, 3).
2 Turn on programming mode: Hold the button down for
at least 5 seconds.
3 Select the switching point to be corrected: Press the
button for max. two seconds until the next switching
point is selected.
4 Position the target object (machine member etc.) at
the desired switching location.
5 Save the switching distance: Hold the button down for
two to four seconds.
6 Return to operating mode: Press the button for max.
2 seconds as often as required until the LED no longer
flashes.
7 After programming is complete, connect the analog
switching amplifier to the user-side controller. In
operating mode a fixed connection between the C
input and ground is recommended.
NPN, NO
C = Control
Copt. = optional input
A = Analog signal
NO1...NO3 = Switching
outputs (normally open)
Effective operating voltage U
e
24 V DC
Supply voltage U
B
15...30 V DC
Ripple
< 15% von U
e
Rated isolation voltage U
i
75 V DC
No-load current I
O
at U
e
< 20 mA
Short/overload protected
yes
Reverse polarity protected
yes
Ambient temperature T
a
–10...+70° C
Analog input
Input voltage
0...10 V
Input impedance
4.2 k
W
Switching outputs
Freely programmable switching outputs
3
Hysteresis
< 500 mV
Effective operating current I
e
for one switching output
100 mA
Switching frequency f
2000 Hz
LED display for each output
yes
Enclosure rating per IEC 60529
IP 67
Housing material
Nickel plated CuZn
Connection type in-/output
BES 516-615-...-PU-
conn./cable PUR
BES 516-615-...-S115-
conn./connector
No. of conductors x gauge
BES 516-615-...-PU-
7 x 0.25 mm
2
BES 516-615-...-S115-
6 x 0.25 mm
2
Technical Data
Connector for BES 516-615-..-1-PU-...
For analog sensors with cabel connection the
confectionable connector BKS-S109-RT04 is available
as accessory.
Fig. 6: M12 connector
Fig. 4: Conn. diagram BES 516-615-...-S115 (PNP)
PNP, NO
C = Control
Copt. = optional input
A = Analog signal
NO1...NO3 = Switching outputs
Fig. 5: Dimensions
BES 516-615-...-PU-
BES 516-615-...-S115-