background image

 

Capacitive Proximity Switches BCS R08RRE…

 

 www.balluff.com  

 

 

Full calibration for object recognition 

 

 

If the object is too close to the sensor, the 

calibration is canceled with an error. See 

Display 

during calibration

Calibration for fill level detection  

Smart

LEVEL

 sensors can be typically be used   

with the factory settings.  
Calibration is only necessary in exceptional cases. 

During a full calibration, the fill level should cover 

about 50% of the active surface. 

Full calibration for fill level  detection 

 

 

For a secure switch-off in applications with 

adhesive build-up or foaming, an empty 
calibration increases the performance. First run a 

fill and empty sequence to get an application 
typical build-up. Subsequently perform an empty 

calibration. 

Empty calibration with build-up 

 

 

Calibration for leakage application  

Perform empty calibration after installation. 

 

Operation with IO -Link  

With IO-Link devices, you can change the behavior 

via additional parameters (see section 

IO-Link

). 

These parameters are also effective in SIO mode. 

Switching output in SIO mode  

If no master is connected to IO-Link devices, they 

automatically use the SIO mode, i.e. the device 
functions as a sensor with a conventional 

switching power amplifier. Via the 

"SIO Output 

Mode"

 parameter, the switching output can be 

configured as PNP, NPN or PushPull. The switching 

output can be set as either N.C. or N.O. via the 

"Switch Point Mode.Logic"

 parameter. 

Adjustable hysteresis 

The difference between the switching point and 

reset point is called hysteresis and can be set via 

the 

"Switch Point Mode.Hysteresis"

 parameter.  0 

corresponds to minimum and 10 to maximum 

hysteresis. 

Adjustable delay  

To suppress short switch-on pulses, the switch 
signal activation can be extended via the 

"Delay.On"

 parameter. This parameter does not 

influence switching off. 

Accordingly, the switch signal deactivation can be 

extended via the 

"Delay.Off"

 parameter. 

Adjustable filter  

The switch signal can be delayed using the 

"Delay.Filter"

parameter. This means that all 

switch signal changes will be delayed by the filter 

time. Any switching impulses that are shorter than 
the filter time are masked. 

 

 

Maintenance

The device is maintenance-free. If necessary, 

contaminations on the device can be removed 

using a nonaggressive cleaner.  

 

Disposal 

 

Repairs to the device are not possible. 

Summary of Contents for BCS R08RRE Series

Page 1: ...Kapazitive N hrungsschalter BCS R08RRE www balluff com 1 Kapazitive N hrungsschalter BCS R08RRE MicroBox Bedienungsanleitung deutsch...

Page 2: ...age mit Halter 6 Leckage Anwendung 7 Haltermontage am Rohr 7 Montage mit BALLUFF Montage System 7 Bedienung 8 Bedienelemente 8 Anzeige 8 Abgleich 8 Abgleich bei Objekterkennung 8 Abgleich bei F llstan...

Page 3: ...LLUFF Zubeh rzugesichert dieVerwendunganderer KomponentenbewirktHaftungsausschluss Ver nderungenamSensorodereine nicht bestimmungsgem e Verwendungsindnicht zul ssigundf hrenzumVerlustvon Gew hrleistun...

Page 4: ...L Bei IO Link Ger tenstehenzus tzlicheParameter zur Verf gungumdas Verhalten einzustellen siehe KapitelBedienungmitIO Link Anwendungen Beispiele f reinige Anwendungsm glichkeiten sind Objekterkennunga...

Page 5: ...L Versorgung Minus 4 BK C Q Schaltausgang bzw Kommunikation Wenn m glich sollte der Teach Eingang DI mit der Minusleitung L verbunden werden w Bei SmartLEVEL Ger tendarf das Kabel nicht aufgerolltwer...

Page 6: ...hStandard Montage sind m glich MaximalesAnzugsdrehmoment0 2 Nm Bei RohrenmitkleinemDurchmesserempfiehlt sichdie Montage mit Kabelbindern Montage mit Halter F r eine schnelle Montage desSensorsverf gtd...

Page 7: ...berwachungverwendetwerden Dazuwerdendie BefestigungslaschenumgeklapptumdenSensormiteinemAbstandvon2mmzumBodenzu montieren Haltermontage am Rohr Montage mit horizontalemKabelaustritt Montage mit vertik...

Page 8: ...tindemderEingangDI mitL verbundenwird die bernahme der Schaltschwelle erfolgtbeimEntfernendes EingangsDI vonL Die Art desAbgleichswird berdie Dauerfestgelegt derAblauf wird ber die Funktions LEDangeze...

Page 9: ...tersindauchim SIO Mode wirksam Schaltausgang im SIO Mode Wennbei IO LinkGer tenkeinMaster angeschlossenistwirdautomatischderSIO Mode verwendet d h dasGer tfunktioniertwie ein SensormitkonventionellerS...

Page 10: ...inem nichtaggressivenReinigerentferntwerden Entsorgung Eine Instandsetzungdes Ger tsist nicht m glich w Das Ger t istgem der Europ ischen Richtlinien2002 96 EG und2003 108 EG Elektro undElektronik Alt...

Page 11: ...ard Technologie SmartLEVEL 50 Hz 10 Hz Spannungsabfall 1 5 V Mechanische Daten Umgebungstemperatur 25 70 C Abmessungen L x B x H 34 x 16 x 10 mm Geh usewerkstoff PP Schutzart IP67 Anzugsdrehmoment M3...

Page 12: ...RE NSM80C EP00 3 GS75 BCS012W Standard NPN Schlie er Kabel 0 3m Stecker M8 4 polig BCS R08RRE NOM80C EP00 3 GS75 BCS012Y Standard NPN ffner Kabel 0 3m Stecker M8 4 polig BCS R08RRE PSMFHC EP02 BCS012H...

Page 13: ...vice Description IODD sowie weitere InformationenzuIO LinkfindenSie unter www balluff com Ohne IO LinkMasterarbeitenIO Link Ger te im SIO Modus Serial Input Output undverhalten sichwie Ger te mitkonve...

Page 14: ...Diagnosis UINT16 6 R 0x8004 32772 Teach Channel 0x000E 14 PDInput Descriptor Array Beschreibungder Prozessdaten Oct Str T3 1 R 0x010100 65792 Schaltsignal BDC1 Oct Str T3 1 R 0x020C04 134148 Sensorwer...

Page 15: ...UINT16 1 R W 0 4095 SchaltpunktSP1 SP2 UINT16 2 R W 0 4095 SchaltpunktSP2 wird nicht verwendet und immer als 0 gelesen 0x003D 61 Switch Point Mode Array Logic UINT8 1 R W 0 Normally Open 1 Normally Cl...

Page 16: ...stellen Ereignisse Events Event dez Typ Modus Device Status Beschreibung 0xFF91 65425 Meldung einmalig Data Storage Upload Request Ger teparameter wurden ge ndert Anforderung an Master die Parameter z...

Page 17: ...8RRE www balluff com 17 Balluff GmbH Schurwaldstrasse9 73765 Neuhausen a d F Phone 49 0 71 58 1 73 0 Fax 49 0 71 58 50 10 balluff balluff de www balluff com Dok Nr 917888 726 DE 02 120140 G15 nderunge...

Page 18: ...Capacitive Proximity Switches BCS R08RRE www balluff com english 1 Capacitive Proximity Switches BCS R08RRE MicroBox User s Guide english...

Page 19: ...et 6 Leakage application 7 Bracket installation on a tube 7 Installation with BALLUFF installation system 7 Operation 8 Operating elements 8 Display 8 Calibration 8 Calibration for object recognition...

Page 20: ...tionsinthe technical dataisensured only whenusingoriginal BALLUFFaccessories Use of any othercomponentswill voidthe warranty Modificationstothe sensorornon approveduse are notpermittedandwill resultin...

Page 21: ...tyreversal Approvals CE UL For IO Linkdevices additional parametersare available forsettingbehavior see section OperationwithIO Link Applications Some example applicationsare Objectdetection Stackingh...

Page 22: ...Supply negative 4 BK C Q Switchingoutput or communication If possible theteach inputDI should be connected to the negativesupply L w For SmartLEVEL devices the cable mustnot be rolledup If possible s...

Page 23: ...erse installationandstandardinstallationare possible Maximumtighteningtorque 0 2 Nm For tubeswithsmall diameters we recommend installationusingcable ties Installation with bracket The enclosedbracketf...

Page 24: ...all the sensorwith adistance of 2 mm fromthe floorfoldthe distance flaps underthe bracketuntil theyclickintothe lockedposition Bracket installation on a tube Installationwith horizontal cableexit Inst...

Page 25: ...L the switchingthresholdisadoptedwhen removingthe DIinputfromL The type of calibrationisdeterminedbasedonthe duration the processis displayedviathe functionLED see Displayduringcalibration w Full cali...

Page 26: ...ut in SIO mode If no masteris connectedtoIO Linkdevices they automaticallyuse the SIOmode i e the device functionsasa sensorwitha conventional switchingpoweramplifier Viathe SIOOutput Mode parameter t...

Page 27: ...E 10 w The device mustbe disposedof inaccordance withthe EuropeanDirectives2002 96 EC and 2003 108 EC Waste Electrical andElectronic Equipment Olddevicesmaynotbe disposed of withhouseholdwaste w Obser...

Page 28: ...technology SmartLEVEL 50 Hz 10 Hz Voltage drop 1 5 V Mechanical data Ambient temperature 25 to 70 C Dimensions L x W x H 34 x 16 x 10 mm Housingmaterial PP Degree of protection IP67 Tightening torque...

Page 29: ...RE NSM80C EP00 3 GS75 BCS012W Standard NPN N O 0 3 m cablewith M8 plug 4 pin BCS R08RRE NOM80C EP00 3 GS75 BCS012Y Standard NPN N C 0 3 m cablewith M8 plug 4 pin BCS R08RRE PSMFHC EP02 BCS012H SmartLE...

Page 30: ...yforconfigurationas well asfurtherinformationat www balluff com Withoutan IO Linkmaster IO Linkdevices operate inthe SIO mode Serial Input Output and behave like deviceswithaconventionaloutput Profile...

Page 31: ...x8004 32772 Teach Channel 0x000E 14 PDInput Descriptor Array Structure of Process Data Oct Str T3 1 R 0x010100 65792 Switch signal BDC1 Oct Str T3 1 R 0x020C04 134148 Sensor ValuePDV1 0x0010 16 Vendor...

Page 32: ...6 1 R W 0 4095 SwitchpointSP1 SP2 UINT16 2 R W 0 4095 SwitchpointSP2 is not used and is always read as 0 0x003D 61 Switch Point Mode Array Logic UINT8 1 R W 0 Normally Open 1 Normally Closed default 0...

Page 33: ...ttings for switchpoint BDC Events Event Type Mode Device Status Description 0xFF91 65425 Notification once Data Storage Upload Request Device Parameters have been changed request master to upload para...

Page 34: ...8RRE www balluff com 17 Balluff GmbH Schurwaldstrasse9 73765 Neuhausen a d F Phone 49 0 71 58 1 73 0 Fax 49 0 71 58 50 10 balluff balluff de www balluff com Doc no 917888 726 EN 02 120140 G15 Subject...

Reviews: