Capacitive Proximity Switches BCS R08RRE…
www.balluff.com
9
Full calibration for object recognition
If the object is too close to the sensor, the
calibration is canceled with an error. See
Display
during calibration
.
Calibration for fill level detection
Smart
LEVEL
sensors can be typically be used
with the factory settings.
Calibration is only necessary in exceptional cases.
During a full calibration, the fill level should cover
about 50% of the active surface.
Full calibration for fill level detection
For a secure switch-off in applications with
adhesive build-up or foaming, an empty
calibration increases the performance. First run a
fill and empty sequence to get an application
typical build-up. Subsequently perform an empty
calibration.
Empty calibration with build-up
Calibration for leakage application
Perform empty calibration after installation.
Operation with IO -Link
With IO-Link devices, you can change the behavior
via additional parameters (see section
IO-Link
).
These parameters are also effective in SIO mode.
Switching output in SIO mode
If no master is connected to IO-Link devices, they
automatically use the SIO mode, i.e. the device
functions as a sensor with a conventional
switching power amplifier. Via the
"SIO Output
Mode"
parameter, the switching output can be
configured as PNP, NPN or PushPull. The switching
output can be set as either N.C. or N.O. via the
"Switch Point Mode.Logic"
parameter.
Adjustable hysteresis
The difference between the switching point and
reset point is called hysteresis and can be set via
the
"Switch Point Mode.Hysteresis"
parameter. 0
corresponds to minimum and 10 to maximum
hysteresis.
Adjustable delay
To suppress short switch-on pulses, the switch
signal activation can be extended via the
"Delay.On"
parameter. This parameter does not
influence switching off.
Accordingly, the switch signal deactivation can be
extended via the
"Delay.Off"
parameter.
Adjustable filter
The switch signal can be delayed using the
"Delay.Filter"
parameter. This means that all
switch signal changes will be delayed by the filter
time. Any switching impulses that are shorter than
the filter time are masked.
Maintenance
The device is maintenance-free. If necessary,
contaminations on the device can be removed
using a nonaggressive cleaner.
Disposal
Repairs to the device are not possible.