6.  RFID  Processor  Connection:  Connect  the  male  end  of  a  5-pin, 

male-to-female,  ThinNet  drop  cable  to  the  female  end  on  your 
Drop-T  connector(s).  Attach  the  remaining  female  end  of  the 
ThinNet  drop  cable  to  the  5-pin,  male,  M12  connector  on 

BIS  U

BIS  M-6xx  or  BIS  M-41x  (RS485  models).  Repeat  Step  5  for 
each RFID Processor you plan to install.

 

Note: maximum drop cable length is 2 m. 

7.  Power  Supply  Wiring:  For  ThinNet  Networks:  Using  a  5-pin, 

female,  M12,  ThinNet  connector  (

P/N:  BCC06ZF),  make  a power 

cable  and  connect  it  to  your  power  supply  (SHIELD  wire 
connected to  Earth).  Attach  the  female,  ThinNet  end  to the 5-pin, 
male, ThinNet end on a Drop-T connector (

P/N: BCC07WR). 

8 .   Host  Connection:  Connect  the  Gateway  to  your  host  computer 

via  Category  5e  Ethernet  cabling.  A  crossover  cable  may  be 
required if you are connecting the Gateway directly to a computer 
(rather than to a switch, network hub or router).

 

9 .   Power  On:  Turn  the  power  supply  ON.  The  POWER LED on  the 

Gateway will remain lit while power is applied to the unit.

 

1 0 .  Automatically Configure Subset16™ Node IDs: At this point all 

Processors are powered and should have Node IDs set to 00, (all 
Processor Node LEDs = OFF), and Subnet16™ baudrate = 9600 
(factory defaults).

 

a.  Place the BIS M- or BIS U-Series Configuration Tag in front of 

an  Processor  (the  Processor  's  RF  Activity  LED  blinks  once 
indicating the tag has been read), and wait for the Gateway to 
assign a valid Node ID to it. The processor's Node LEDs now 
indicate  a  valid  Node  ID.  Remove  the  Configuration  Tag  from 
the processor.

 

b.  Repeat  this  step  for  each  node  in  the  Subnet16™  network 

(one Processor at a time). The first is Node ID 1, then 2 and so 
on up to 16 (binary).

 

 
The Subnet16™ network is now configured with the default values and 
can  communicate  with  the  TCP/IP  Ethernet  Gateway  which  in  turn 
communicates with the TCP/IP Ethernet Host. 
 
The BIS Z-GW-001-TCP interface module is designed to receive its IP 
address  via  DHCP.  After  your  DHCP  server  has  assigned  an  IP 
address to a TCP/IP Gateway, the IP address can be identified through 
the use of the "

Digi Device Discovery" software tool. 

 
For  further  information  or  for  application  specific  configuration  using 
the  Dashboard™  Configuration  Tool    utility,  see  the  Gateway  Series 
Reference Manual. 
 

DIMENSIONS 

 

POWER REQUIREMENTS 

The  Gateway  requires  an  electrical  supply  voltage  of  12  to  30 
Vdc.  In  addition,  each  RFID  Processor  connected  to  the 
Gateway  via  the  Subnet16™  network  will  also  require  power. 
Use  a  regulated  power  supply  that  is  capable  of  delivering  the 
requirements listed in the Technical Features. 
 

 

NOTE 

Power  is  applied  directly  to  the  Subnet16™  Network 
trunk and distributed through drop cables to the Gateway 
and  RFID  Processors.  By  positioning  the  power  supply 
near  the  middle  of  the  network,  you  can  limit  voltage 
drop at the ends, (see example layouts). 

 
The  following  information  is  provided  to  assist  you  in 
determining the power requirements of your RFID application. 
 
 

Total System Current Consumption 

 

 

NOTE 

The  current  consumption  values  of  each  product  are 
given in the Technical Features paragraph of the relative 
Installation  manual  and  refer  to  the  min  and  max  input 
voltage  range.  These  values  already  include  an 
adequate  safety  margin.  The  consumption  values  given 
in  the  following  examples  have  been  interpolated  for  an 
input voltage of 24 Vdc. 

 
Max Gateway Current: 200 mA @ 12 Vdc (133 mA @ 24 Vdc). 
 
Max Processor  Current:   366 mA @ 24 Vdc for BIS M-6xx-Series, 87 
mA @ 24 Vdc for BIS M-41X-Series, etc. (refer to Processor ’s spec). 
 
Calculating Total System Current Consumption: 

Total  System  Current  Consumption  =  [Max  Gateway  Current  + 
(Max Processor Current x Number of Processors)] 

 
Example 
A Subnet16™ network powered at 24 Vdc is composed of a BIS Z-GW-
001-TCP connecting eight BIS M-41X-485 Processors. 
 
Total System Current Consumption = [0.133 A + (0.087 A X 8)] = 0.829 A 

 
 

Cable Voltage Drop 

 

In addition, each RFID Processor on the Subnet will experience 
a certain amount of voltage drop depending on the length of the 
cable. 

Cable Resistance per Meter 

 

ThinNet = 0.058 ohms per meter per wire 

 

ThickNet = 0.0105 ohms per meter per wire 

 
Calculating Voltage Drop 

Voltage Drop = 

(Max Processor Current x Number of Processors) x 
(Cable Resistance per Meter per Wire 

1

 x Cable length 

in Meters) 

 

Example 
A  Subnet16™  network  is  composed  of  a  BIS  Z-GW-001-TCP 
connecting eight BIS M-41X-485 Processors  (87 mA each @ 24 Vdc). 
A total of 20 meters of ThinNet cables are used to connect the devices, 
which  have  Cable  Resistance  =  0.058  Ohms  per  meter  per  wire.  The 
network power is 24 Vdc. 

2

 

Voltage Drop = 

[0.133 A GWY + (0.087 A x 8 Processors)] x [(0.058 x 2) 
x 20 meters] = 1.92 Vdc 

24 Vdc - 1.92 = 22.08 Vdc at Processor number 8 

                                                           

1

 The resistance calculation must include both wires (Vdc and GND). 

2

  This  example  assumes  the  power  supply  is  placed  at  the  end  of  the 

network,  therefore  controller  #8  is  the  worst  case.  By  placing  the 
power  supply  in  the  middle  of  the  network  the  voltage  drop  at  the 
ends is reduced. 

It  is  recommended  that  the  voltage  drop  calculation  be  conducted  on 
the  RFID  Processor  that  is  farthest  from  the  Gateway,  as  it  will 
experience the greatest voltage drop. 
 
 

Max Supported Trunk and Drop Cable Lengths 

 

 

ThickNet trunk length up to 300 m. 

 

ThinNet trunk length up to 20 m. 

 

ThinNet drop cable length up to 2 m. 

 
 

Current Rating for Cables 

 

The  maximum current  rating  for  the  Subnet16™  network  using 
Balluff cables and accessories (BCCxxxx), is 

4.0 A

 
 

COMPLIANCE 

This  product  is  intended  to  be  installed  by  Qualified 
Personnel only. 
 
This product must not be used in explosive environments. 
 
See  the  Subnet16™  Gateway  Manual  for  the  Declaration  of 
Conformity. 
 
 

Power Supply 

 
This  device  is  intended  to  be  supplied  by  a  UL  Listed  or  CSA 
Certified Power Unit with «Class 2» or LPS power source. 
 
 

CE Compliance 

 
Warning: This is a Class A product. In a domestic environment 
this  product  may  cause  radio  interference  in  which  case  the 
user may be required to take adequate measures. 
 

 

 
 

32

 [1.26]

8

8

.9

[3

.5

0

]

1

0

0

[3

.9

4

]

4

0

.6

[1

.6

0

]

7

.6

[0

.3

0

]

91.4

[3.60]

107

[4.20]

Ø10.2

[Ø0.40]

Ø5

 [Ø0.20]

14.5

 [0.57]

82.3

[3.24]

mm 

in

 

N

r.

 8

9

0

 4

1

6

 E

 

.

 E

d

it

io

n

 1

3

0

5

S

u

b

je

c

to

 m

o

d

if

ic

a

ti

o

n

Reviews: