4.
GAS CONNECTION:
The gas pressure regulator supplied must be installed at the gas inlet of each broiler. Each regulator is
adjusted to yield a manifold pressure of 5 in. water column for natural gas or 10 in. water column for propane
gas. No pressure regulator is required for propane gas in Canada.
For units using propane gas, supply lines less than ½” inside diameter should not be used, even for a small
unit.
On the XX and CH series, the gas connection is located on the right rear of the unit.
NOTE:Ashut-off valve in a readily accessible location must be mounted on the gas supply line before the unit.
When making gas pipe connections, pipe joint compound resistant to the action of liquefied petroleum gases
should be used.
The broiler and its individual shutoff valve must be disconnected from the gas supply piping system during any
pressure testing of that system at test pressures in excess of ½ psig (3.45 kPa).
The broiler must be isolated from the gas supply piping system by closing its individual manual shutoff valve
during any pressure testing of the gas supply piping system at test pressures equal to or less than ½ psig (3.45
kPa).
BE SURE TO CAP WHICHEVER SIDE IS NOT CONNECTED.
I. INSTALLATION INSTRUCTIONS
1.
GENERAL:
2.
INSTALLATION:
3.
ACCEPTABLE CLEARANCES:
The instructions in this manual apply to all XX series and CH series Broilers.
The XX series may include the following options:
Ceramic briquettes designated by a GS Suffix on the model number.
(a)
INSTALLATION of this broiler must conform with the latest edition of the
National Fuel Gas Code,ANSI Z223.1 and/or local codes.
(b)
INSTALLATION must conform with the latest edition of the National Gas
I n s t a l l a t i o n C o d e , C A N / C G A - B 1 4 9 . 1 o r t h e P r o p a n e I n s t a l l a t i o n C o d e ,
CAN/CGA-B149.2, as applicable and/or local codes.
Due to intense heat generated by radiation, these broilers should be installed in non-combustible locations
only including above the grate level.
Right Side
0 inches
0 inches
Left Side
0 inches
0 inches
Back
0 inches
0 inches
!
In USA,
In CANADA,
Series XX
Series CH
MINIMUM CLEARANCE FROM NON-COMBUSTIBLE CONSTRUCTION
RECOMMENDED MINIMUM GAS SUPPLY LINES ARE LISTED BELOW
All XX Models
CH-4 thru CH-8
CH-10 thru CH-16
3/4”
1”
1 1/2”