Compliance Test Set-Up
1. Configure a test set-up as in Figure
Figure 39
Compliance Voltage Test Set-Up
2. Send 4 mA to the test set-up.
3. Increase the potentiometer value until the loop current
reaches 3.95 mA.
4. Read the voltage across the potentiometer, which should
be > 11 VDC. This is the available system voltage at the
minimum output.
5. Send 20 mA to the test set-up.
6. Increase the potentiometer value until the loop current
reaches 19.95 mA.
7. Read the voltage across the potentiometer, which should
be > 9 VDC. This is the available system voltage at the
maximum output.
17 lists some compliance voltage readings at positioner
terminals at several currents.