3. Technical Specifications
3.1. Models 8007 and 8008 Transducers
• Input signal : 4-20 mA
• Hysteresis : 0.8 % of output range
• Linearity : ± 0.85% of output range
• Sensitivity : 0.5 % of input range
• Accuracy : ± 1.0 % of output range
• Housing electrical protection index : IP 65
• Maximum service temperature range : (refer also to the marking on the apparatus as some limitation may apply)
8007 : -20°C to +80°C and optional -55°C to +80°C
8008 : -20°C to +80°C
• Storage and transportation : -55°C to +90°C
• Air supply and output range
Transducer
PRESSURE in bar (psi)
Air supply
Output signal range
8007
1.586 (23)
0.207 to 1.035 (3 to 15)
8008
1.586 (23)
0.207 to 1.035 (3 to 15)
2.413 (35)
0.414 to 2.068 (6 to 30)
3.2. Model 8013 Positioner
• Input signal : 4-20 mA
• Hysteresis : 0.8 % of output range
• Sensitivity : 0.3 % of input range
• Accuracy : ± 1.0 % of output range
• Housing electrical protection index : IP 65
• Maximum service temperature range : (refer also to the marking on the apparatus)
Standard instrument : -20°C to +80°C
Low temperature instrument : -55°C to +60°C
• Storage and transportation temperature : -55°C to +90°C
• Maximum air supply pressure : 5.20 bar (75 psi)