Annex I 
 

CABLE GLAND 

– ADAPTOR - REDUCER MOUNTING RULES 

CABLE GLAND 

ADAPTOR - REDUCER 

7700E positioner Housing 

certified II 2 GD 

Ex db IIC / Ex tb IIC 

Cable gland  

certified II 2 GD 

Ex db IIC / Ex tb IIC 

Housing 

certified II 2 GD 

Ex db IIC / Ex tb IIC 

Adaptor-Reducer 

certified II 2 GD 

Ex db IIC / Ex tb IIC 

           

 

          

A

B

 

 
TYPE : 

Male Taper (conical) threaded joint: 

 ¾

” 

NPT 

 

  Conform to NPT requirements of ANSI/ASME B1.20.1 

  A minimum of 5 threads provided on each part 

 

MOUNTING RULE: 

  Thread cleaning with Loctite 7063 or equivalent 

product with similar efficiency. 

  Cemented with Loctite 5400 (low strength thread 

sealant) or equivalent product with similar efficiency. 
This is mandatory to meet an IP67. 

  Tightening torque (see Cable Gland instruction 

manual) 

 

Check threads engagement (see Cable Gland 
instruction manual)

 

 
A : 
TYPE :

 Male Taper (conical) threaded joint: 

¾

” 

NPT 

 

  Conform to NPT requirements of ANSI/ASME B1.20.1 

  A minimum of 5 threads provided on each part 

 

MOUNTING RULE: 

  Thread cleaning with Loctite 7063 or equivalent product with 

similar efficiency. 

  Cemented with Loctite 2700 (high-strength threadlocker) or 

equivalent product with similar efficiency. This is mandatory to 
meet an IP67. 

  Tightening torque (see Adaptor-Reducer instruction manual) 

  Check threads engagement (see Adaptor-Reducer instruction 

manual) 

B: 
TYPE: 

Female Taper (conical) thread joints: ½” NPT or other NPT size 

  Conform to NPT requirements of ANSI/ASME B.1.20.1 

  A minimum of 5 threads provided on each part 

 
TYPE: 

Female Cylindrical threaded joints: M20 x 1.5 or other sizes 

  Conform to ISO 965-1 and ISO 965-3 requirements 

  Minimum thread engaged: 5 

  Depth of engagement

: ≥ 8 mm 

 

MOUNTING RULE: 

  Thread cleaning with Loctite 7063 or equivalent product with 

similar efficiency. 

  Cemented with Loctite 5400 (low strength thread sealant) or 

equivalent product with similar efficiency. This is mandatory to 
meet an IP67. 

  Tightening torque (see Cable Gland instruction manual) 

  Check threads engagement (see Cable Gland instruction 

manual)

 

 

 
 

Summary of Contents for Masoneilan 7700E

Page 1: ...Baker Hughes Data Classification Public Masoneilan Type 7700EElectro Pneumatic Positioner with I P 4000 Converter Ukrainian UA TR Instruction Manual Rev A...

Page 2: ...REQUIREMENTS FOR OPERATION OF OTHER EQUIPMENT AT THE SITE THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIBLE CONTINGENCY TO BE MET IN...

Page 3: ...Assembly of a 7700E Positioner on a Valve 7 7 Pneumatic Connection of Positioner 7700E 7 8 Electrical Connection Installation and Start Up 7 8 1 Conduit entry in flameproof application 8 8 2 Electrica...

Page 4: ...y qualified and competent professionals who have undergone suitable training for instrumentation used in areas with potentially explosive atmospheres Such trainings are not supported by Baker Hughes I...

Page 5: ...pneumatic signal Model 7700E electro pneumatic positioner can be used only on Varipak valve 28000 2 Numbering System Unique positioner 7700 E with I P 4000 module Different versions Housing material...

Page 6: ...Pi 0 33 W Li 0 Ci 0 IP66 Warning Potential electrostatic charging hazard See instructions for safe use 5 Flameproof Marking and Electrical Safety Parameters The marking on the serial plate stamped on...

Page 7: ...Series instruction manual Ref 30857 for more details 7 Pneumatic Connection of Positioner 7700E Make sure that the air supply pressure is suitable for the installation and for the instrument When usin...

Page 8: ...y on the single NPT ANSI ASME B1 20 1 housing conduit connection The cable entry has to be suitable to the equipment operating zone IP 6X for zones 20 21 and 22 If an adaptor or reducer is needed it m...

Page 9: ...allation for explosible atmosphere with d protection mode Intrinsically safe installation for explosible atmosphere with ia protection mode Note It is under the user responsibility to check the instal...

Page 10: ...ke sure that the local conditions in the potentially explosive atmosphere permit the safe opening of the cover Connect the wires to the instrument s terminals taking care of complying with polarities...

Page 11: ...ment are not damaged In the event of damage replace the defective parts with genuine manufacturer s replacement parts Pay particular attention to the following o General condition of the housing o Che...

Page 12: ...vertical position uppermost the required ingress protection against water is invalidated therefore it shall only be installed in this orientation if its location provides protection against falling wa...

Page 13: ...ss 123112 Russia Moscow Presnenskaya embankment house 10 room III floor 3 room 22 Tel 7 495 739 68 11 MoscowHelpDesk bakerhughes com 14 Design and Manufactured by Products are designed and controlled...

Page 14: ...PT requirements of ANSI ASME B1 20 1 A minimum of 5 threads provided on each part MOUNTING RULE Thread cleaning with Loctite 7063 or equivalent product with similar efficiency Cemented with Loctite 27...

Page 15: ...com Copyright 2021 Baker Hughes Company All rights reserved Baker Hughes provides this information on an as is basis for general information purposes Baker Hughes does not make any representation as t...

Reviews: