Copyright 2013 Baker Hughes Company.
English–DPI
620G Instruction Manual | 103
Troubleshooting
a. Set Basic.
b. Set Link Master.
c. Set Bridge.
3. Restart device.
4. Properties - displays device attributes.
Figure
10
-
8: Device Profile
5. The device Block List can also be fetched from here (default functionality is to use “Device
Focus View” - refer to Section
6. Remove - removes the device.
10.6 Troubleshooting
If no device is found when performing scan check:
1. The field wiring - verify electrical segment connections are in accordance with the specific
user manual supplied with the field device and segment coupler / power supply.
2. The loop is not suffering from interference due to an unstable voltage supply from the
segment power supply and / or electrical interference.
Some bridging devices / LAS implementations provide an optimization whereby some address
ranges are not scanned. This may result in individual device not being found.
After setting address, it may take some time for the device and the Link Active Scheduler (LAS)
to synchronize information including address, identity, and protocol timing information.
10.7 Device Focus View
In this view the specific information of the device is shown.
•
PD tag.
•
Device Id.
•
Block List with Target / Actual Mode.