C.6.3 Entering communications data
The XGF868i flowmeter is equipped with an RS232 serial
interface. The serial port is used to transmit stored data and
displayed readings to a personal computer by connecting
the meter’s serial interface to the serial port of the PC. In
addition, the XGF868i can receive and execute remote
commands, using
PanaView
software, via this link.
Use the comm port submenu to set the communications
port and MODBUS parameters. While following the
programming instructions, refer to
of
Appendix D, PanaView menu maps
.
C.6.3a Setting up the serial port
1. To enter this submenu from the global menu, highlight
and double-click on the
comm port
option in the
center pane.
2. Enter a
meter address
number between 1 and 254
and click [next item]. The default number is 1.
A meter address is only necessary for communication
with the Panametrics
PanaView
software. See the
PanaView user’s manual
for more information.
IMPORTANT
If the meter address or baud rate is changed,
communication with PanaView must be re-established
with the new address number.
3. Double-click on the desired
baud rate
(from 300
to 19200).
If you have the MODBUS option, proceed to step 4 below.
If you have the standard RS232 serial interface, the meter
exits the comm port submenu and returns to the global
program
prompt.
NOTE:
The XGF868i MODBUS communication settings
chosen in the next four steps must match those of the
MODBUS control system.
4. Double-click on the desired
MODBUS baud rate
(from 2400 to 9600).
5. Double-click on the desired
MODBUS parity
(none, odd or even).
6. Double-click on the desired
MODBUS stop bits
(1 or 2).
7. Enter the desired
MODBUS address
.
The meter exits the comm port submenu and returns
to the global window. Click [exit page] once to return to
the site edit menu, and [close] to exit the
site edit menu
.
IMPORTANT
You must reboot the XGF868i to load the new settings.
Refer to the section
to retrieve data from the XGF868i
using MODBUS.
C.6.3b Requesting parameters using MODBUS
To request specific parameters from the XGF868i via
the MODBUS, the control system must access the
appropriate register number, as shown in
Table 27
below.
Only registers 1–84 are available with the XGF868i for
MODBUS communications. Registers 508–512 are used by
the XGF868i to store the MODBUS parameters.
Table 27: MODBUS registers
MODBUS
reg #
DPR hex
addr
Description
Scaling (decimal places)
Size in bytes
MODBUS
reg #
1
0
1”clear ch1 totalizers”
--
2 (16 bit signed)
1
2
2
1“clear ch2 totalizers”
--
2 (16 bit signed)
2
3
4
Ch1 velocity
2
4 (2 16-bit int)
3
5
8
Ch1 act volumetric
#Q DIGITS
4 (IEEE 32 bit)
5
7
C
Ch1 std volumetric
#Q DIGITS
4 (IEEE 32 bit)
7
9
10
Ch1 fwd totals
#T DIGITS
4 (2 16 bit int)
9
71
Summary of Contents for DigitalFlow XGF868i
Page 1: ...DigitalFlow XGF868i Panametrics flare gas flow transmitter Programming manual...
Page 2: ...ii...
Page 4: ...no content intended for this page iv...
Page 10: ...x...
Page 38: ...28...
Page 46: ...no content intended for this page 36...
Page 54: ...44...
Page 60: ...50...
Page 88: ...78...
Page 94: ...84...