INSTALLATION
SELECTING DEFAULTS
WBPEEUI110505A0
3 - 13
In order to change any calibration or configuration parameters
of transmitters using the Type STT terminal, the field bus
module must be instructed to bring the desired transmitter
offline.
Signal wiring should not be run in conduit or open trays with
wiring used to power other devices and should not be run near
heavy electrical equipment. Twisted shielded pairs are recom-
mended for best results. Reverse polarity protection is built
into the transmitter to protect it against accidental reversal of
the field wiring connections.
GROUNDING
Signal wiring may be either ungrounded (floating) or grounded
at any one point in the signal loop. If more than one transmit-
ter is connected to a single power supply, grounding should be
at the supply. The transmitter housing must also be grounded.
A ground terminal is provided inside the electronics housing
(Figs.
SELECTING DEFAULTS
The configuration of process control equipment within a par-
ticular system dictates the response to the controlled process
of that system. Configuration may include such items as
cross-limits, interlocks and alarms dealing with bad quality,
and safety control equipment. Modern electronic process con-
trol equipment based on semiconductor technology is highly
reliable and can be expected to provide long trouble-free ser-
vice. However, component failures that disrupt process control
are still possible. In addition, power line induced failures, fail-
ures caused by human error, static discharge, conducted and
radiated EMI, acts of nature such as lightning strikes, and
accidents can cause disruption of process control.
Refer to
to select defaults for failure conditions.
HAZARDOUS LOCATION INSTALLATIONS (FLAMMABLE ATMOSPHERES)
The Type PTSDL Platinum Standard Smart Level Transmitter
must not be located in a hazardous (classified) location unless
factory marked as suitable for that location. This equipment
must be installed and operated according to
20 mA Transmitter in a Hazardous Location
.