INTRODUCTION
I-E96-409A
D - 1
APPENDIX D - IMQRS02 QUICK RESPONSE
SLAVE MODULE CONFIGURATION
INTRODUCTION
Figure
shows the location of the dipswitches and jumpers
used to configure the QRS module. Tables
, and
give the dipswitch and jumper settings to configure the
module. This information is provided as a quick reference
guide for personnel installing the NICS01 module. Configura-
tion consists of setting the slave module address (Switch S1),
analog output default values (Switch S2), analog output mode
(Switch S3), digital input voltage level (Jumpers J1 through
J3), and DC voltage response time (Jumpers J4 through J6).
Refer to the
Quick Response Slave Module (IMQRS02)
instruction manual for detailed instructions.
Figure D-1. Quick Response Slave Module
DIGITAL INPUT TYPE JUMPERS
ANALOG OUTPUT
MODE SWITCH
ANALOG OUTPUT
DEFAULT SWITCH
P1
P3
P2
ADDRESS SWITCH
J7
S1
MODULE STATUS LED
1
8
OPEN
S2
1
6
OPEN
2
1
T00503A
4
1
J6
4
1
J3
4
1
J5
4
1
J2
4
1
J4
4
1
J1
C1
C2
C3
C4
S3
Table D-1. Example Switch S1 Settings
Address
Example
Switch Position
1
2
3
4
5
6
7
8
Binary Value
128
64
32
16
8
4
2
1
0
0
0
0
0
0
0
0
0
16
0
0
0
1
0
0
0
0
32
0
0
1
0
0
0
0
0
48
0
0
1
1
0
0
0
0
63
0
1
1
1
1
1
1
1
NOTE: 0 represents the CLOSED or ON side of the switch. 1 represents the OPEN or OFF side of
the switch. Switch positions 1 and 2 must remain closed.