INSTALLATION
SETUP/PHYSICAL INSTALLATION
I-E96-415A
2 - 7
NKTD02 AND NKTD12 CABLES
This cable connects the IRL module to a first NDIS01, NDCS03
or IISAC01 station. To install the cable:
1. Remove the NDIS01, NDCS03 or IISAC01 station from the
station housing.
2. Insert the J2 end of the cable into the station housing
backplane. Viewing the station from the back, the cable inserts
into the right slot (use the left slot for an NDCS03 station with-
out analog output bypass capability). The cable should latch
securely into place. Card edge connector P1 of the station cir-
cuit board connects to this end of the cable.
3. Insert the J1 end of the cable into the J4 connector of the
IRL module. The cable should latch securely into place.
4. Install the NDIS01, NDCS03 or IISAC01 station into the
station housing.
NKTL01 CABLE
This adapter cable connects an NKCL01 or NKCL02 cable to an
IRL module. To install the cable:
1. Connect the BNC type plug end of the cable to the J1 (of the
local or RMP node) or J2 (of the remote or RSP node) connector
of the IRL module.
2. Connect the N type plug end of the cable to the NKCL01 or
NKCL02 cable.
Figure 2-5. Example NKPL03 or NKPL04
Cable Connection
GREEN WIRE
BLACK BAND
T00537A
11
10
SHIELD
5
DCS–
6
7
8
O–
9
O+
4
DCS+
3
+24 VDC
2
COMMON
1
GROUND
NKPL03/04